Anhydrous AmmoniaChapter 296-826, WAC |
Effective Date: 09/01/06 |
Appurtenances |
![]()
YOUR RESPONSIBILITY:
To follow the requirements in this section when using appurtenances
|
Appurtenance requirements for all systems |
|
|
Nonrefrigerated stationary containers |
|
|
Refrigerated tanks |
WAC 296-826-50015 |
| Systems mounted on trucks, semi-trailers and trailers | WAC 296-826-50020 |
| Systems mounted on farm trucks or trailers for transportation of ammonia | WAC 296-826-50025 |
| Systems mounted on farm equipment for ammonia application |
WAC 296-826-50030 |
| Portable DOT containers | WAC 296-826-50035 |
Appurtenance requirements for all systems
|
|
Definition: Appurtenance means all devices such as pumps, compressor, safety relief devices, liquid-level gauging devices, valves and pressure gauges. |
You must
- Make sure each appurtenance installed before
February 8, 1973, is determined to be safe by meeting one of
the following:
- -Approved, tested, and installed by either:
- The American National Standard for the Storage and Handling of Anhydrous Ammonia (in effect at the time of installation)
- The Fertilizer Institute Standards for the Storage and Handling of Agricultural Anhydrous Ammonia (in effect at the time of installation)
- -Accepted, certified, listed, or labeled, by a nationally recognized testing laboratory
- -Inspected or tested by a federal, state, municipal, or local authority responsible for enforcing occupational safety provisions, when no nationally recognized laboratory will provide approval
- -Tested and approved by a registered professional engineer or other qualified person if the system is a custom-designed or custom-built unit and no other recognized entity will provide approval
- -Keep a document on file signed by the qualified person that indicates the unit is safe. Include the test bases, test data and results and the qualifications of the qualified person.
You must
- Make sure container appurtenances are both
of the following:
- -Designed for at least the working pressure
for the portion of the system where installed
and - -Fabricated from materials suitable for anhydrous ammonia service.
- -Designed for at least the working pressure
for the portion of the system where installed
- Make sure fixed liquid level gauges, except
on refrigerated storage:
- -Are designed so the maximum volume of
the container filled by liquid doesn't exceed 85 percent
of its water capacity
and - -Have a coupling into which it's threaded
that's placed at the 85 percent level of the container
- If located elsewhere, install the dip tube of this gauge so it can't be easily removed.
- -Are designed so the maximum volume of
the container filled by liquid doesn't exceed 85 percent
of its water capacity
- Equip each container, except those filled
by weight, with an approved liquid level gauging device that
does all of the following:
- -Has a design pressure equal to or greater than the design pressure of the container
- -Are arranged so the maximum liquid fill level of containers can be readily determined.
- Follow additional requirements found in Table 5, Appurtenance Requirements for all Systems
If you have |
Then make sure they |
|
Safety relief devices |
Don't have discharge termination in or beneath any building. |
|
| Safety relief valves |
Have a flow capacity that isn't restricted by any connection to it on either the upstream or downstream side. |
|
Connections to containers
|
Have shut off valves located as close to the container as possible. Exemption: Safety relief devices, gauging devices or devices fitted with a No. 54 drill size hole aren't required to have shut off valves located as close to the container as possible. |
|
| Connections and the line, including valves and fittings |
Have a greater rated flow than the excess flow valves that protects them |
|
Excess flow valves, where required |
Meet all of the following:
|
|
| Excess flow valves provided with shut off valves Excess flow and back pressure check valves, where required |
Are designed to close if the shut off valve breaks during installation Are located either:
|
|
| Liquid level gauging devices that: Require bleeding of the product into the atmosphere such as the rotary tube, fixed tube, and slip tube devices
|
Are either:
Exemption:
|
|
You must
- Follow Table 6, Safety
Valve Start to Discharge Rate, and Table
7, Safety Relief Valve Rate of Discharge, for the following
systems:
- -Nonrefrigerated stationary containers
- -Mounted on trucks, semi-trailers, and trailers used for the transportation of ammonia
- -Mounted on farm wagons for the transportation of ammonia
- -Mounted on farm equipment for the application of ammonia
|
The rate of discharge of spring-loaded safety relief valves installed on underground containers may be reduced to 30 percent of the rate of discharge specified in Table 6, Safety Relief Valve Rate of Discharge so long as the container isn't uncovered after installation until the liquid ammonia has been removed. |
| Containers |
Minimum |
Maximum.* |
| ASME U-68, U-69 |
110% |
125% |
| ASME U-200, U-201 |
95% |
100% |
| ASME 1952, 1956, 1959, 1962, 1965, 1968, or 1971 |
95% |
100% |
| API-ASME |
95% |
100% |
| U.S. Coast Guard |
(As required by U.S.C.G. regulations) |
|
| DOT |
(As required by DOT regulations) |
|
|
|
Note: A relief valve manufacturer's tolerance of plus 10 percent is permitted. |
Surface Area sq. ft. |
Flow Rate CFM Air |
Surface Area sq. ft. |
Flow Rate CFM Air |
Surface Area sq. ft. |
Flow Rate CFM Air |
Surface Area sq. ft. |
Flow Rate CFM Air |
||||||||
20 |
|
258 |
|
145 |
|
1,310 |
|
340 |
|
2,640 |
|
1,350 |
|
8,160 |
|
| 25 |
|
310 |
|
150 |
|
1,350 |
|
350 |
|
2,700 |
|
1,400 |
|
8,410 |
|
30 |
|
360 |
|
155 |
|
1,390 |
|
360 |
|
2,760 |
|
1,450 |
|
8,650 |
|
| 35 |
|
408 |
|
160 |
|
1,420 |
|
370 |
|
2,830 |
|
1,500 |
|
8,900 |
|
40 |
|
455 |
|
165 |
|
1,460 |
|
380 |
|
2,890 |
|
1,550 |
|
9,140 |
|
| 45 |
|
501 |
|
170 |
|
1,500 |
|
390 |
|
2,950 |
|
1,600 |
|
9,380 |
|
50 |
|
547 |
|
175 |
|
1,530 |
|
400 |
|
3,010 |
|
1,650 |
|
9,620 |
|
| 55 |
|
310 |
|
180 |
|
1,570 |
|
450 |
|
3,320 |
|
1,700 |
|
9,860 |
|
60 |
|
360 |
|
185 |
|
1,600 |
|
500 |
|
3,620 |
|
1,750 |
|
10,090 |
|
| 65 |
|
408 |
|
190 |
|
1,640 |
|
550 |
|
3,910 |
|
1,800 |
|
10,330 |
|
70 |
|
455 |
|
195 |
|
1,670 |
|
600 |
|
4,200 |
|
1,850 |
|
10,560 |
|
| 75 |
|
762 |
|
200 |
|
1,710 |
|
650 |
|
4,480 |
|
1,900 |
|
10,800 |
|
80 |
|
804 |
|
210 |
|
1,780 |
|
700 |
|
4,760 |
|
1,950 |
|
11,030 |
|
| 85 |
|
845 |
|
220 |
|
1,850 |
|
750 |
|
5,040 |
|
2,000 |
|
11,260 |
|
90 |
|
885 |
|
230 |
|
1,920 |
|
800 |
|
5,300 |
|
2,050 |
|
11,490 |
|
| 95 |
|
925 |
|
240 |
|
1,980 |
|
850 |
|
5,590 |
|
2,100 |
|
11,720 |
|
100 |
|
965 |
|
250 |
|
2,050 |
|
900 |
|
5,850 |
|
2,150 |
|
11,950 |
|
| 105 |
|
1,010 |
|
260 |
|
2,120 |
|
950 |
|
6,120 |
|
2,200 |
|
12,180 |
|
110 |
|
1,050 |
|
270 |
|
2,180 |
|
1,000 |
|
6,380 |
|
2,250 |
|
12,400 |
|
| 115 |
|
1,090 |
|
280 |
|
2,250 |
|
1,050 |
|
6,640 |
|
2,300 |
|
12,630 |
|
120 |
|
1,120 |
|
290 |
|
2,320 |
|
1,100 |
|
6,900 |
|
2,350 |
|
12,850 |
|
| 125 |
|
1,160 |
|
300 |
|
2,380 |
|
1,150 |
|
7,160 |
|
2,400 |
|
13,080 |
|
130 |
|
1,200 |
|
310 |
|
2,450 |
|
1,200 |
|
7,410 |
|
2,450 |
|
13,300 |
|
| 135 |
|
1,240 |
|
320 |
|
2,510 |
|
1,250 |
|
7,660 |
|
2,500 |
|
13,520 |
|
140 |
|
1,280 |
|
330 |
|
2,570 |
|
1,300 |
|
7,910 |
|
|
|
|
|
- Table instructions:
- -The surface area = the total outside surface area of the container in square feet.
- -When the surface area isn't stamped on the name plate or the marking isn't legible, calculate the area by using the Table 8, Surface Area
If you have |
Then calculate as follows |
Cylindrical container with hemispherical heads |
Area = overall length in feet times the outside diameter in feet times 3.1416 |
| Cylindrical container with other than hemispherical heads |
Area = (overall length in feet plus 0.3 outside diameter in feet) times outside diameter in feet times 3.1416 |
Spherical container |
Area = outside diameter in feet squared times 3.1416 |
- Flow rate--CFM air = cubic feet per minute of air required at standard conditions, 60°F and atmospheric pressure (14.7 psia).
- The rate of discharge may be altered for intermediate values of surface area.
- For containers with total outside surface area greater than 2,500 sq. ft., the required flow rate can be calculated using the formula, flow rate CFM air .= 22.11 A0.82 where A .=outside surface area of the container in square feet.
Nonrefrigerated stationary containers
IMPORTANT:
In addition to this section, you need to follow the Appurtenances requirements for all systems, WAC 296-826-50005.
You must
- Make sure all containers are equipped with
all of the following:
- -An approved vapor return valve
- -A fixed maximum liquid level gauge
- -A pressure gauge that is both:
- Graduated from zero to 400 psig
and - Designed for use in ammonia service
- Graduated from zero to 400 psig
- Provide one or more spring-loaded safety relief valves, or an equivalent type, on all containers.
- Make sure safety relief valves do all of the
following:
- -Discharge in the following ways:
- Away from the container in an upward, unobstructed manner into the atmosphere
- Not in or beneath a building
- -Have raincaps that allow free discharge of the vapor and prevent the entrance of water
- -Have a method for draining accumulated condensation
- -Have a start to discharge, related to the design pressure of the container, according to Table 6, Safety Valve Start to Discharge Rate
- -Are arranged to minimize the possibility of tampering
- -Are provided, when the pressure setting adjustment is external, with a means of sealing the adjustment
- -Have direct communication with the vapor space of the container
- -Discharge in the following ways:
|
|
Note:
|
You must
- Protect container appurtenances against physical damage and during transit of containers intended for underground installation.
- Make sure shut off valves aren't installed between the safety relief valve and the container or system. A shut off valve may be used if arranged so that the required capacity flow is maintained.
|
You must
- Make sure vapor and liquid connections have
either of the following:
- -An approved excess flow valve
or - -An approved quick-closing internal valve that remains closed except during operation.
- -An approved excess flow valve
|
You must
- Follow additional requirements found in Table 9, Appurtenances for Nonrefrigerated Stationary Containers
Refrigerated tanks
IMPORTANT:
In addition to this section, you need to follow the Appurtenances requirements for all systems, WAC 296-826-50005.
You must
- Protect container appurtenances against the
following:
- -Physical damage during transit of containers intended for underground installation
- -Damage from vehicles.
- Make sure safety relief devices have a total
relieving capacity larger than either of the following:
- -A possible refrigeration system upset such as a cooling water failure, power failure, instrument air or instrument failure, mechanical failure of any equipment, excessive pumping rates or changing atmospheric pressure
- or
- -The amount based on using either one of the following fire exposure formulas (see note below for codes):
- Valve manufacturers who use weight of vapors to be relieved as the classifying basis, use this formula:
W = |
34,500 F A (0.82) ____________________ L |
|
|
|
or
- Valve manufacturers that classify valves based on air flows, use this formula:
Q (a)=
|
633,000
F A (0.32) LC
|
|
- Make sure safety relief devices meet the following
additional requirements:
- -Are set to start-to-discharge at a pressure not in excess of the design pressure of the tank
- -Have a total relieving capacity sufficient to prevent a maximum pressure in a tank of more than 120 percent of the design pressure.
- Provide shut off valves for all connections
including plugs, safety valves, and thermometer wells:
- -Locate them as close to the tank as is practical.
|
Shut off valves don't need to be provided on connections with a No. 54 drill size restriction |
|
|
Note:
|
You must
- Follow requirements found in Table 10, Refrigerated Tank Appurtenances
|
Table 10 |
||
|
If you have |
Then make sure they |
|
|
Shut off valves used as a means of lock out for inspection or repair |
|
|
|
Discharge line and header |
|
|
|
Vacuum breakers |
Are provided with atmospheric storage |
|
|
Stacks |
|
|
You must
- Make sure appurtenances meet all of the requirements
found in the following:
- -ANSI CGA C-7 2004
- -ANSI CGA G2.1 1999
- -API Standard 620 4th Edition, 2002
- -ASHRAE 15 2004
- -ASME 2001, Section VIII, Division 1
- -ANSI B95.1 1977
Systems mounted on trucks, semi-trailers and trailers
IMPORTANT:
In addition to this section, you need to follow the Appurtenances requirements for all systems, WAC 296-826-50005.
You must
- Make sure each container has all of the following:
- -Fixed maximum liquid level gauging devices
- -Pressure-indicator gauges with a dial graduated from zero to 400 psig
- -Either of the following:
- Equipped for spray-loading, which
fills in vapor space
or - Has an approved vapor return valve of adequate capacity.
- Equipped for spray-loading, which
fills in vapor space
- Provide one or more spring-loaded safety relief
valves, or an equivalent type, on all containers, that do all
of the following:
- -Discharges in the following ways:
- Away from the container in an upward, unobstructed manner into the atmosphere
- Not in or beneath a building.
- -Has raincaps that allow free discharge of the vapor and prevent the entrance of water
- -Has a method for draining accumulated condensation
- -Has a start to discharge, related to the design pressure of the container, according to Table 6, Safety Valve Start to Discharge Rate
- -Are arranged to minimize the possibility of tampering
- -Provided, when the pressure setting adjustment is external, with a means of sealing the adjustment
- -Has direct communication with the vapor space of the container
- -Discharges in the following ways:
- Make sure shut off valves aren't installed between the safety relief valve and the container or system. A shut off valve may be used if arranged so that the required capacity flow is maintained.
|
| If you have |
Then make sure they |
|
All container connections |
|
|
| Filling connections |
|
|
Nonrecessed container fittings and appurtenances |
|
|
| Columnar-type gauges |
|
|
Hydrostatic relief valves |
Are installed between each pair of valves in the liquid ammonia piping or hose. |
|
Systems mounted on farm trucks or trailers for transportation of ammonia
IMPORTANT:
- This section applies to containers of 3,000 gallons capacity or less and pertinent equipment mounted on farm trucks or trailers used for the transportation of ammonia.
- In addition to this section, you need to follow the Appurtenances requirements for all systems, WAC 296-826-50005.
You must
- Make sure all containers are equipped with a fixed maximum liquid level gauge.
- Make sure vapor and liquid connections have
either of the following:
- -An approved excess flow valve
or - -An approved quick-closing internal valve that remains closed except during operation.
- -An approved excess flow valve
|
- Provide one or more spring-loaded safety relief
valves, or an equivalent type, on all containers, that do all
of the following:
- -Discharges in the following ways:
- Away from the container in an upward, unobstructed manner into the atmosphere
- -Has raincaps that allow free discharge of the vapor and prevent the entrance of water
- -Has a method for draining accumulated condensation
- -Has a start to discharge, related to the design pressure of the container, according to Table 6, Safety Valve Start to Discharge Rate
- -Are arranged to minimize the possibility of tampering
- -Provided, when the pressure setting adjustment is external, with a means of sealing the adjustment
- -Has direct communication with the vapor space of the container
- -Discharges in the following ways:
- Make sure shut off valves aren't installed between the safety relief valve and the container or system. A shut off valve may be used if arranged so that the required capacity flow is maintained.
|
You must
- Secure both ends of the hose while in transit
- Make sure all containers with a capacity exceeding
250 gallons are equipped with both of the following:
- -A pressure gauge with a dial graduated
from 0-400 psig
and - -A method for spray loading or with an approved vapor return valve
- -A pressure gauge with a dial graduated
from 0-400 psig
- Follow additional requirements found in Table 12, Appurtenances for Systems Mounted on Farm Trucks or Trailers
| If you have |
Then make sure they |
|
| Filling connections |
|
|
| A fully enclosed guard |
|
|
Fittings |
|
|
| Liquid withdrawal lines installed in the bottom of the container |
Have connections, including the hose, that aren't lower than the lowest horizontal edge of the truck axle |
|
Columnar-type gauges |
|
|
| Hydrostatic relief valves |
Are installed between each pair of valves in the liquid ammonia piping or hose. |
|
Systems mounted on farm equipment for ammonia application
IMPORTANT:
- This section applies to systems mounted on farm equipment and used for the filed application of ammonia.
- In addition to this section, you need to follow the Appurtenances requirements for all systems, WAC 296-826-50005.
You must
- Make sure each container has a fixed maximum liquid-level gauge.
- Provide one or more spring-loaded safety relief
valves, or an equivalent type, on all containers, that do all
of the following:
- -Discharges in the following ways:
- Away from the container in an upward, unobstructed manner into the atmosphere
- Not in or beneath a building.
- -Has raincaps that allow free discharge of the vapor and prevent the entrance of water
- -Has a method for draining accumulated condensation
- -Has a start to discharge, related to the design pressure of the container, according to Table 6, Safety Valve Start to Discharge Rate
- -Are arranged to minimize the possibility of tampering
- -Provided, when the pressure setting adjustment is external, with a means of sealing the adjustment
- -Has direct communication with the vapor space of the container
- -Discharges in the following ways:
You must
- Make sure shut off valves aren't installed between the safety relief valve and the container or system. A shut off valve may be used if arranged so that the required capacity flow is maintained.
|
- Follow additional requirements found in Table 13, Appurtenances for Systems Mounted on Farm Equipment for Ammonia Application
Portable DOT containers
IMPORTANT:
- This section applies to systems that use cylinders, portable tanks (DOT-51), or ton containers (DOT-106A, DOT-110A).
- In addition to this section, you need to follow the Appurtenances requirements for all systems, WAC 296-826-50005.
You must
- Make sure safety relief devices meet DOT specifications.
- Provide the following protection:
- -To valves and pressure regulating equipment from tampering once installed for use
- -To containers:
- From heat sources such as radiant flame and steam pipes. Don't apply heat directly to containers to raise the pressure
- From moving vehicles or external damage while being stored
- From ignitable debris and to prevent external corrosion while being stored. Storage can be indoors or outdoors.
- Protect container valves while in transit,
in storage, and while being moved into final use by doing either
of the following:
- -Setting them into the recess of the container
or - -By fastening a ventilated cap or collar to the container that can withstand a blow from any direction equivalent to a 30-pound weight being dropped 4 feet
- -Setting them into the recess of the container
- Construction should be such that a blow won't be transmitted to the valves or other connections.
- Keep outlet valves tightly closed when containers aren't connected for service on all empty or loaded containers
- Secure the valve protection cap, if the container is designed for one, when the container isn't in service.
