General Safety & Health Standards |
|
WAC 296-24-33013
Bulk plants.
(1) Storage.
(a) Class I liquids. Class I liquids shall be stored in closed containers,
or in storage tanks above ground outside of buildings, or underground
in accordance with WAC
296-24-33005.
(b) Class II and III liquids. Class II and Class III liquids shall
be stored in containers, or in tanks within buildings or above
ground outside of buildings, or underground in accordance with
WAC
296-24-33005.
(c) Piling containers. Containers of flammable or combustible liquids
when piled one upon the other shall be separated by dunnage sufficient
to provide stability and to prevent excessive stress on container walls.
The height of the pile shall be consistent with the stability and strength
of containers.
(2) Buildings.
(a) Exits. Rooms in which flammable or combustible liquids are stored
or handled by pumps shall have exit facilities arranged to prevent occupants
from being trapped in the event of fire.
(b) Heating. Rooms in which Class I liquids are stored or handled shall
be heated only by means not constituting a source of ignition, such
as steam or hot water. Rooms containing heating appliances involving
sources of ignition shall be located and arranged to prevent entry of
flammable vapors.
(c) Ventilation.
(i) Ventilation shall be provided for all rooms, buildings, or enclosures
in which Class I liquids are pumped or dispensed. Design of ventilation
systems shall take into account the relatively high specific gravity
of the vapors. Ventilation may be provided by adequate openings in
outside walls at floor level unobstructed except by louvers or course
screens. Where natural ventilation is inadequate, mechanical ventilation
shall be provided.
(ii) Class I liquids shall not be stored or handled within a building
having a basement or pit into which flammable vapors may travel, unless
such area is provided with ventilation designed to prevent the accumulation
of flammable vapors therein.
(iii) Containers of Class I liquids shall not be drawn from or filled
within buildings unless provision is made to prevent the accumulation
of flammable vapors in hazardous concentrations. Where mechanical
ventilation is required, it shall be kept in operation while flammable
liquids are being handled.
(3) Loading and unloading facilities.
(a) Separation. Tank vehicle and tank car loading or unloading facilities
shall be separated from aboveground tanks, warehouses, other plant buildings
or nearest line of adjoining property that may be built upon by a distance
of 25 feet for Class I liquids and 15 feet for Class II and Class III
liquids measured from the nearest position of any fill spout. Buildings
for pumps or shelters for personnel may be a part of the facility.
(b) Class restriction. Equipment such as piping, pumps, and meters
used for the transfer of Class I liquids between storage tanks and the
fill stem of the loading rack shall not be used for the transfer of
Class II or Class III liquids.
(c) Valves. Valves used for the final control for filling tank vehicles
shall be of the self-closing type and manually held open except where
automatic means are provided for shutting off the flow when the vehicle
is full or after filling of a preset amount.
(d) Static protection.
(i) Bonding facilities for protection against static sparks during
the loading of tank vehicles through open domes shall be provided:
(A) Where Class I liquids are loaded, or
(B) Where Class II or Class III liquids are loaded into vehicles
which may contain vapors from previous cargoes of Class I liquids.
(ii) Protection as required in (3)(d)(i) of this section shall consist
of a metallic bond wire permanently electrically connected to the
fill stem or to some part of the rack structure in electrical contact
with the fill stem. The free end of such wire shall be provided with
a clamp or equivalent device for convenient attachment to some metallic
part in electrical contact with the cargo tank of the tank vehicle.
(iii) Such bonding connection shall be made fast to the vehicle or
tank before dome covers are raised and shall remain in place until
filling is completed and all dome covers have been closed and secured.
(iv) Bonding as specified in (3)(d)(i), (ii) and (iii) of this section
is not required:
(A) Where vehicles are loaded exclusively with products not having
a static accumulating tendency, such as asphalt, most crude oils,
residual oils, and water soluble liquids;
(B) Where no Class I liquids are handled at the loading facility
and the tank vehicles loaded are used exclusively for Class II and
Class III liquids; and
(C) Where vehicles are loaded or unloaded through closed bottom
or top connections.
(v) Filling through open domes into the tanks of tank vehicles or
tank cars, that contain vapor-air mixtures within the flammable range
or where the liquid being filled can form such a mixture, shall be
by means of a downspout which extends near the bottom of the tank.
This precaution is not required when loading liquids which are nonaccumulators
of static charges.
(e) Stray currents. Tank car loading facilities where Class I liquids
are loaded through open domes shall be protected against stray currents
by bonding the pipe to at least one rail and to the rack structure if
of metal. Multiple lines entering the rack area shall be electrically
bonded together. In addition, in areas where excessive stray currents
are known to exist, all pipe entering the rack area shall be provided
with insulating sections to electrically isolate the rack piping from
the pipelines. No bonding between the tank car and the rack or piping
is required during either loading or unloading of Class II or III liquids.
(f) Container filling facilities. Class I liquids shall not be dispensed
into containers unless the nozzle and container are electrically interconnected.
Where the metallic floorplate on which the container stands while filling
is electrically connected to the fill stem or where the fill stem is
bonded to the container during filling operations by means of a bond
wire, the provisions of these standards shall be deemed to have been
complied with.
(4) Wharves.
(a) Definition, application. The term wharf shall mean any wharf, pier,
bulkhead, or other structure over or contiguous to navigable
water used in conjunction with a bulk plant, the primary function
of which is the transfer of flammable or combustible liquid
cargo in bulk between the bulk plant and any tank vessel, ship,
barge, lighter boat, or other mobile floating craft; and this
subparagraph shall apply to all such installations except marine
service stations as covered in WAC
296-24-33015.
(b) Package cargo. Package cargo of flammable and combustible liquids,
including full and empty drums, bulk fuel, and stores may be handled
over a wharf and at such times and places as may be agreed upon by the
wharf superintendent and the senior deck officer on duty.
(c) Location. Wharves at which flammable or combustible liquid cargoes
are to be transferred in bulk quantities to or from tank vessels shall
be at least 100 feet from any bridge over a navigable waterway, or from
an entrance to or superstructure of any vehicular or railroad tunnel
under a waterway. The termination of the wharf loading or unloading
fixed piping shall be at least 200 feet from a bridge or from an entrance
to or superstructure of a tunnel.
(d) Design and construction. Substructure and deck shall be substantially
designed for the use intended. Deck may employ any material which will
afford the desired combination of flexibility, resistance to shock,
durability, strength, and fire resistance. Heavy timber construction
is acceptable.
(e) Tanks. Tanks used exclusively for ballast water or Class II or
Class III liquids may be installed on suitably designed wharves.
(f) Pumps. Loading pumps capable of building up pressures in excess
of the safe working pressure of cargo hose or loading arms shall be
provided with bypasses, relief valves, or other arrangement to protect
the loading facilities against excessive pressure. Relief devices shall
be tested at not more than yearly intervals to determine that they function
satisfactorily at the pressure at which they are set.
(g) Hoses and couplings. All pressure hoses and couplings shall be
inspected at intervals appropriate to the service. The hose and couplings
shall be tested with the hose extended and using the "inservice maximum
operating pressures." Any hose showing material deteriorations, signs
of leakage, or weakness in its carcass or at the couplings shall be
withdrawn from service and repaired or discarded.
(h) Piping and fittings. Piping, valves, and fittings shall be in accordance
with WAC
296-24-33007 with the following exceptions and additions:
(i) Flexibility of piping shall be assured by appropriate layout
and arrangement of piping supports so that motion of the wharf structure
resulting from wave action, currents, tides, or the mooring of vessels
will not subject the pipe to repeated strain beyond the elastic limit.
(ii) Pipe joints depending upon the friction characteristics of combustible
materials or grooving of pipe ends for mechanical continuity of piping
shall not be used.
(iii) Swivel joints may be used in piping to which hoses are connected,
and for articulated swivel-joint transfer systems, provided that the
design is such that the mechanical strength of joint will not be impaired
if the packing material should fail, as by exposure to fire.
(iv) Piping systems shall contain a sufficient number of valves to
operate the system properly and to control the flow of liquid in normal
operation and in the event of physical damage.
(v) In addition to the requirements of (4)(h)(iv), each line conveying
flammable liquids leading to a wharf shall be provided with a readily
accessible block valve located on shore near the approach to the wharf
and outside of any diked area. Where more than one line is involved,
the valves shall be grouped in one location.
(vi) Means of easy access shall be provided for cargo line valves
located below the wharf deck.
(vii) Pipelines on flammable or combustible liquids wharves shall
be adequately bonded and grounded. If excessive stray currents are
encountered, insulating points shall be installed. Bonding and grounding
connections on all pipelines shall be located on wharfside of hose-riser
insulating flanges, if used, and shall be accessible for inspection.
(viii) Hose or articulated swivel-joint pipe connections used for
cargo transfer shall be capable of accommodating the combined effects
of change in draft and maximum tidal range, and mooring lines shall
be kept adjusted to prevent the surge of the vessel from placing stress
on the cargo transfer system.
(ix) Hose shall be supported so as to avoid kinking and damage from
chafing.
(i) Fire protection. Suitable portable fire extinguishers with a rating
of not less than 12-BC shall be located with 75 feet of those portions
of the facility where fires are likely to occur, such as hose connections,
pumps, and separator tanks.
(i) Where piped water is available, ready-connected fire hose in
size appropriate for the water supply shall be provided so that manifolds
where connections are made and broken can be reached by at least one
hose stream.
(ii) Material shall not be placed on wharves in such a manner as
to obstruct access to fire fighting equipment, or important pipeline
control valves.
(iii) Where the wharf is accessible to vehicle traffic, an unobstructed
roadway to the shore end of the wharf shall be maintained for access
of fire fighting apparatus.
(j) Operations control. Loading or discharging shall not commence until
the wharf superintendent and officer in charge of the tank vessel agree
that the tank vessel is properly moored and all connections are properly
made. Mechanical work shall not be performed on the wharf during cargo
transfer, except under special authorization by a delegated person or
the delegated persons authorized representative based on a review of
the area involved, methods to be employed, and precaution necessary.
(5) Electrical equipment.
(a) Application. This subsection shall apply to areas where Class I
liquids are stored or handled. For areas where Class II or Class
III liquids only are stored or handled, the electrical equipment
may be installed according to chapter
296-24 WAC Part L for ordinary locations.
(b) Conformance. All electrical equipment and wiring shall be of a
type specified by and shall be installed according to chapter
296-24 WAC Part L.
(c) Classification. So far as it applies Table H-18 shall be used to
delineate and classify hazardous areas for the purpose of installation
of electrical equipment under normal circumstances. In Table H-18 a
classified area shall not extend beyond an unpierced wall, roof, or
other solid partition. The area classifications listed shall be based
on the premise that the installation meets the applicable requirements
of this section in all respects.
TABLE H-18
ELECTRICAL
EQUIPMENT HAZARDOUS
AREAS--BULK
PLANTS
TABLE
H-18 - PART 1 (pdf)
TABLE
H-18 - PART 2 (pdf)
1When classifying the extent of the area, consideration
shall be given to the fact that tank cars or tank vehicles may be spotted
at varying points. Therefore, the extremities of the loading or unloading
positions shall be used.
(6) Sources of ignition. Class I liquids shall not be handled, drawn,
or dispensed where flammable vapors may reach a source of ignition. Smoking
shall be prohibited except in designated localities. "No smoking" signs
shall be conspicuously posted where hazard from flammable liquid vapors
is normally present.
(7) Drainage and waste disposal. Provision shall be made to prevent flammable
or combustible liquids which may be spilled at loading or unloading points
from entering public sewers and drainage systems, or natural waterways.
Connection to such sewers, drains, or waterways by which flammable or
combustible liquids might enter shall be provided with separator boxes
or other approved means whereby such entry is precluded. Crankcase drainings
and flammable or combustible liquids shall not be dumped into sewers,
but shall be stored in tanks or tight drums outside of any building until
removed from the premises.
(8) Fire control. Suitable fire-control devices, such as small hose or
portable fire extinguishers, shall be available to locations where fires
are likely to occur. Additional fire-control equipment may be required
where a tank of more than 50,000 gallons individual capacity contains
Class I liquids and where an unusual exposure hazard exists from surrounding
property. Such additional fire-control equipment shall be sufficient to
extinguish a fire in the largest tank. The design and amount of such equipment
shall be in accordance with approved engineering standards.
[Statutory Authority: Chapter 49.17 RCW.
94-15-096 (Order 94-07), 296-24-33013, filed 7/20/94, effective 9/20/94;
91-24-017 (Order 91-07), 296-24-33013, filed 11/22/91, effective 12/24/91.
Statutory Authority: RCW 49.17.040 and 49.17.050. 85-10-004 (Order 85-09),
296-24-33013, filed 4/19/85; Order 76-6, 296-24-33013, filed 3/1/76; Order
73-5, 296-24-33013, filed 5/9/73 and Order 73-4, 296-24-33013, filed 5/7/73.]
WAC 296-24-33015
Service stations.
(1) Storage and handling.
(a) General provisions.
(i) Liquids shall be stored in approved closed containers not exceeding
60 gallons capacity, in tanks located underground, in tanks in special
enclosures as described in (b) of this subsection, or in aboveground
tanks as provided for in (3)(b)(i), (ii), (iii) and (iv) of this section.
(ii) Aboveground tanks, located in an adjoining bulk plant, may be
connected by piping to service station underground tanks if, in addition
to valves at aboveground tanks, a valve is also installed within control
of service station personnel.
(iii) Apparatus dispensing Class I liquids into the fuel tanks of
motor vehicles of the public shall not be located at a bulk plant
unless separated by a fence or similar barrier from the area in which
bulk operations are conducted.
(iv) The provisions of subsection (1) of this section shall not prohibit
the dispensing of flammable liquids in the open from a tank vehicle
to a motor vehicle. Such dispensing shall be permitted provided:
(A) The tank vehicle complies with the requirements covered in
the Standard on Tank Vehicles for Flammable Liquids, NFPA 385-1966.
(B) The dispensing is done on premises not open to the public.
(C) The dispensing hose does not exceed 50 feet in length.
(D) The dispensing nozzle is a listed automatic-closing type without
a latch-open device.
(vi) Class I liquids shall not be stored or handled within a building
having a basement or pit into which flammable vapors may travel, unless
such area is provided with ventilation designed to prevent the accumulation
of flammable vapors therein.
(vii) Accurate inventory records shall be maintained and reconciled
on all Class I liquid storage tanks for possible indication of leakage
from tanks or piping.
(b) Special enclosures.
(i) When installation of tanks in accordance with WAC
296-24-33005(3) is impractical because of property or
building limitations, tanks for flammable or combustible liquids
may be installed in buildings if properly enclosed.
(ii) The enclosure shall be substantially liquid and vaportight without
backfill. Sides, top, and bottom of the enclosure shall be of reinforced
concrete at least 6 inches thick, with openings for inspection through
the top only. Tank connections shall be so piped or closed that neither
vapors nor liquid can escape into the enclosed space. Means shall
be provided whereby portable equipment may be employed to discharge
to the outside any liquid or vapors which might accumulate should
leakage occur.
(iii) At automotive service stations provided in connection with
tenant or customer parking facilities at or below grade level in large
buildings of commercial, mercantile, or residential occupancy, tanks
containing Class I liquids, installed of necessity in accordance with
subsection (1)(b)(ii) of this section, shall not exceed 6,000 gallons
individual or 18,000 gallons aggregate capacity.
(c) Inside buildings.
(i) Except where stored in tanks as provided in subsection (1)(b)
of this section, no Class I liquids shall be stored within any service
station building except in closed containers of aggregate capacity
not exceeding 60 gallons. One container not exceeding 60 gallons capacity
equipped with an approved pump is permitted.
(ii) Class I liquids may be transferred from one container to another
in lubrication or service rooms of a service station building provided
the electrical installation complies with Table H-19 and provided
that any heating equipment complies with subsection (5) of this section.
(iii) Class II and Class III liquids may be stored and dispensed
inside service station buildings from tanks of not more than 120 gallons
capacity each.
(d) Labeling. No sale or purchase of any Class I, II, or III liquids
shall be made in containers unless such containers are clearly marked
with the name of the product contained therein.
(e) Dispensing into portable containers. No delivery of any Class I
liquids shall be made into portable containers unless the container
is constructed of metal, has a tight closure with screwed or spring
cover, and is fitted with a spout or so designed that the contents can
be poured without spilling.
(2) Dispensing systems.
(a) Location. Dispensing devices at automotive service stations shall
be so located that all parts of the vehicle being served will be on
the premises of the service station.
(b) Inside location. Approved dispensing units may be located inside
of buildings. The dispensing area shall be separated from other areas
in an approved manner. The dispensing unit and its piping shall be mounted
either on a concrete island or protected against collision damage by
suitable means and shall be located in a position where it cannot be
struck by a vehicle descending a ramp or other slope out of control.
The dispensing area shall be provided with an approved mechanical or
gravity ventilation system. When dispensing units are located below
grade, only approved mechanical ventilation shall be used and the entire
dispensing area shall be protected by an approved automatic sprinkler
system. Ventilating systems shall be electrically interlocked with gasoline
dispensing units so that the dispensing units cannot be operated unless
the ventilating fan motors are energized.
(c) Emergency power cutoff. A clearly identified and easily accessible
switch(es) or a circuit breaker(s) shall be provided at a location remote
from dispensing devices, including remote pumping systems, to shut off
the power to all dispensing devices in the event of an emergency.
(d) Dispensing units.
(i) Class I liquids shall be transferred from tanks by means of fixed
pumps so designed and equipped as to allow control of the flow and
to prevent leakage or accidental discharge.
(ii) Only listed devices may be used for dispensing Class I liquids.
No such device may be used if it shows evidence of having been dismantled.
(iii) Every dispensing device for Class I liquids installed after
December 31, 1978, shall contain evidence of listing so placed that
any attempt to dismantle the device will result in damage to such
evidence, visible without disassembly or dismounting of the nozzle.
(iv) Class I liquids shall not be dispensed by pressure from drums,
barrels, and similar containers. Approved pumps taking suction through
the top of the container or approved self-closing faucets shall be
used.
(v) The dispensing units, except those attached to containers, shall
be mounted either on a concrete island or protected against collision
damage by suitable means.
(e) Remote pumping systems.
(i) This subdivision shall apply to systems for dispensing Class
I liquids where such liquids are transferred from storage to individual
or multiple dispensing units by pumps located elsewhere than at the
dispensing units.
(ii) Pumps shall be designed or equipped so that no part of the system
will be subjected to pressures above its allowable working pressure.
Pumps installed above grade, outside of buildings, shall be located
not less than 10 feet from lines of adjoining property which is/or
may be built upon, and not less than 5 feet from any building opening.
When an outside pump location is impractical, pumps may be installed
inside of buildings, as provided for dispensers in (b) of this subsection,
or in pits as provided in (e)(iii) of this subsection. Pumps shall
be substantially anchored and protected against physical damage by
vehicles.
(iii) Pits for subsurface pumps or piping manifolds of submersible
pumps shall withstand the external forces to which they may be subjected
without damage to the pump, tank, or piping. The pit shall be no larger
than necessary for inspection and maintenance and shall be provided
with a fitted cover.
(iv) A control shall be provided that will permit the pump to operate
only when a dispensing nozzle is removed from its bracket on the dispensing
unit and the switch on this dispensing unit is manually actuated.
This control shall also stop the pump when all nozzles have been returned
to their brackets.
(v) An approved impact valve, incorporating a fusible link, designed
to close automatically in the event of severe impact or fire exposure
shall be properly installed in the dispensing supply line at the base
of each individual dispensing device.
(vi) Testing. After the completion of the installation, including
any paving, that section of the pressure piping system between the
pump discharge and the connection for the dispensing facility shall
be tested for at least 30 minutes at the maximum operating pressure
of the system. Such tests shall be repeated at 5-year intervals thereafter.
(f) Delivery nozzles.
(i) A listed manual or automatic-closing type hose nozzle valve shall
be provided on dispensers used for the dispensing of Class I liquids.
(ii) Manual-closing type valves shall be held open manually during
dispensing. Automatic-closing type valves may be used in conjunction
with an approved latch-open device.
(g) Special type dispensers.
(i) Emergency controls shall be installed at an acceptable location,
but controls shall not be more than 100 feet from dispensers.
(ii) Instructions for the operation of dispensers shall be conspicuously
posted.
(3) Marine service stations.
(a) Dispensing.
(i) The dispensing area shall be located away from other structures
so as to provide room for safe ingress and egress of craft to be fueled.
Dispensing units shall in all cases be at least 20 feet from any activity
involving fixed sources of ignition.
(ii) Dispensing shall be by approved dispensing units with or without
integral pumps and may be located on open piers, wharves, or floating
docks or on shore or on piers of the solid fill type.
(iii) Dispensing nozzles shall be automatic-closing without a hold-open
latch.
(b) Tanks and pumps.
(i) Tanks, and pumps not integral with the dispensing unit, shall
be on shore or on a pier of the solid fill type, except as provided
below.
(ii) Where shore location would require excessively long supply lines
to dispensers, tanks may be installed on a pier provided that
applicable portions of WAC
296-24-33005 relative to spacing, diking, and piping are
complied with and the quantity so stored does not exceed 1,100
gallons aggregate capacity.
(iii) Shore tanks supplying marine service stations may be located
above ground, where rock ledges or high water table make underground
tanks impractical.
(iv) Where tanks are at an elevation which would produce gravity
head on the dispensing unit, the tank outlet shall be equipped
with a pressure control valve positioned adjacent to and outside
the tank block valve specified in WAC
296-24-33005 (2)(h)(ii), so adjusted that liquid cannot
flow by gravity from the tank in case of piping or hose failure.
(c) Piping.
(i) Piping between shore tanks and dispensing units shall be as described
in WAC
296-24-33007, except that, where dispensing is from a
floating structure, suitable lengths of oil-resistant flexible
hose may be employed between the shore piping and the piping
on the floating structure as made necessary by change in water
level or shoreline.
(ii) A readily accessible valve to shut off the supply from shore
shall be provided in each pipeline at or near the approach to the
pier and at the shore end of each pipeline adjacent to the point where
flexible hose is attached.
(iii) Piping shall be located so as to be protected from physical
damage.
(iv) Piping handling Class I liquids shall be grounded to control
stray currents.
(4) Electrical equipment.
(a) Application. This subsection shall apply to areas where Class I
liquids are stored or handled. For areas where Class II or Class
III liquids are stored or handled the electrical equipment may
be installed according to the provisions of chapter
296-24 WAC Part L for ordinary locations.
(b) All electrical equipment and wiring shall be of a type
specified by and shall be installed according to chapter
296-24 WAC Part L.
(c) So far as it applies, Table H-19 shall be used to delineate and
classify hazardous areas for the purpose of installation of electrical
equipment under normal circumstances. A classified area shall not extend
beyond an unpierced wall, roof, or other solid partition.
(d) The area classifications listed shall be based on the assumption
that the installation meets the applicable requirements of this section
in all respects.
TABLE
H-19 (pdf)
ELECTRICAL
EQUIPMENT HAZARDOUS
AREAS--SERVICE
STATIONS
(5) Heating equipment.
(a) Conformance. Heating equipment shall be installed as provided in
(b) through (e) of this subsection.
(b) Application. Heating equipment may be installed in the conventional
manner in an area except as provided in (c), (d) or (e) of this subsection.
(c) Special room. Heating equipment may be installed in a special room
separated from an area classified by Table H-19 by walls having a fire
resistance rating of at least 1 hour and without any openings in the
walls within 8 feet of the floor into an area classified in Table H-19.This
room shall not be used for combustible storage and all air for combustion
purposes shall come from outside the building.
(d) Work areas. Heating equipment using gas or oil fuel may be installed
in the lubrication, sales, or service room where there is no dispensing
or transferring of Class I liquids provided the bottom of the combustion
chamber is at least 18 inches above the floor and the heating equipment
is protected from physical damage by vehicles. Heating equipment using
gas or oil fuel listed for use in garages may be installed in the lubrication
or service room where Class I liquids are dispensed provided the equipment
is installed at least 8 feet above the floor.
(e) Electric heat. Electrical heating equipment shall conform to subsection
(4) of this section.
(6) Drainage and waste disposal. Provision shall be made in the area
where Class I liquids are dispensed to prevent spilled liquids from flowing
into the interior of service station buildings. Such provision may be
by grading driveways, raising door sills, or other equally effective means.
Crankcase drainings and flammable or combustible liquids shall not be
dumped into sewers but shall be stored in tanks or drums outside of any
building until removed from the premises.
(7) Sources of ignition. In addition to the previous restrictions of
this section, the following shall apply: There shall be no smoking or
open flames in the areas used for fueling, servicing fuel systems for
internal combustion engines, receiving or dispensing of flammable or combustible
liquids. Conspicuous and legible signs prohibiting smoking shall be posted
within sight of the customer being served. The motors of all equipment
being fueled shall be shut off during the fueling operation.
(8) Fire control. Each service station shall be provided with at least
one fire extinguisher having a minimum approved classification of 6 B,
C located so that an extinguisher will be within 75 feet of each pump,
dispenser, underground fill pipe opening, and lubrication or service room.
Note: For additional requirements relating to portable fire extinguishers
see WAC 296-800-300.
[Statutory Authority: Chapter 49.17 RCW.
91-24-017 (Order 91-07), 296-24-33015, filed 11/22/91, effective 12/24/91.
Statutory Authority: RCW 49.17.040 and 49.17.050. 85-10-004 (Order 85-09),
296-24-33015, filed 4/19/85; 83-24-013 (Order 83-34), 296-24-33015, filed
11/30/83; Order 76-6, 296-24-33015, filed 3/1/76; Order 73-5, 296-24-33015,
filed 5/9/73 and Order 73-4, 296-24-33015, filed 5/7/73.]
WAC 296-24-33017
Processing plants.
(1) Scope. This section shall apply to those plants or buildings which
contain chemical operations such as oxidation, reduction, halogenation,
hydrogenation, alkylation, polymerization, and other chemical processes
but shall not apply to chemical plants, refineries or distilleries.
(2) Location.
(a) Classification. The location of each processing vessel shall be
based upon its flammable or combustible liquid capacity. Processing
vessels shall be located, with respect to distances to lines of adjoining
property which may be built upon, in accordance with Table H-20, except
when the processing plant is designed in accordance with (2)(b) of this
section.
TABLE H-20
| Processing
vessels with emergency relief venting to permit pressure |
Stable liquids |
Unstable
liquids |
| Not in excess
of 2.5 p.s.i.g. |
Table H-9 |
2 1/2 times
Table H-9 |
| Over 2.5 p.s.i.g. |
1 1/2 times
Table H-9 |
4 times Table
H-9 |
(b) Exception. The distances required in (2)(a) of this section may
be waived when the vessels are housed within a building and the exterior
wall facing the line of adjoining property which may be built upon is
a blank wall having a fire-resistance rating of not less than 4 hours.
When Class IA or unstable liquids are handled, the blank wall shall
have explosion resistance in accordance with good engineering practice,
see (3)(d) of this section.
(3) Processing building.
(a) Construction.
(i) Processing buildings shall be of fire-resistance or noncombustible
construction, except heavy timber construction with load-bearing walls
may be permitted for plants utilizing only stable Class II or Class
III liquids. Except as provided in (2)(b) of this section or in the
case of explosion resistant walls used in conjunction with explosion
relieving facilities, see (3)(d) of this section, loadbearing walls
are prohibited. Buildings shall be without basements or covered pits.
(ii) Areas shall have adequate exit facilities arranged to prevent
occupants from being trapped in the event of fire. Exits shall not
be exposed by the drainage facilities described in (3)(b) of this
section.
(b) Drainage.
(i) Emergency drainage systems shall be provided to direct flammable
or combustible liquid leakage and fire protection water to
a safe location. This may require curbs, scuppers, or special
drainage systems to control the spread of fire, see WAC
296-24-33005 (2)(g)(ii).
(ii) Emergency drainage systems, if connected to public sewers or
discharged into public waterways, shall be equipped with traps or
separators.
(iii) The processing plant shall be designed and operated to prevent
the normal discharge of flammable or combustible liquids to public
waterways, public sewers, or adjoining property.
(c) Ventilation.
(i) Enclosed processing buildings shall be ventilated at a rate of
not less than 1 cubic foot per minute per square foot of solid floor
area. This shall be accomplished by natural or mechanical ventilation
with discharge or exhaust to a safe location outside of the building.
Provision shall be made for introduction of makeup air in such a manner
as not to short circuit the ventilation. Ventilation shall be arranged
to include all floor areas or pits where flammable vapors may collect.
(ii) Equipment used in a building and the ventilation of the building
shall be designed so as to limit flammable vapor-air mixtures under
normal operating conditions to the interior of equipment, and to not
more than 5 feet from equipment which exposes Class I liquids to the
air. Examples of such equipment are dispensing stations, open centrifuges,
plate and frame filters, open vacuum filters, and surfaces of open
equipment.
(d) Explosion relief. Areas where Class IA or unstable liquids are
processed shall have explosion venting through one or more of the following
methods:
(i) Open air construction.
(ii) Lightweight walls and roof.
(iii) Lightweight wall panels and roof hatches.
(iv) Windows of explosion venting type.
(4) Liquid handling.
(a) Storage.
(i) The storage of flammable or combustible liquids in tanks shall
be in accordance with the applicable provisions of WAC
296-24-33005.
(ii) If the storage of flammable or combustible liquids in outside
aboveground or underground tanks is not practical because
of temperature or production considerations, tanks may be
permitted inside of buildings or structures in accordance
with the applicable provisions of WAC
296-24-33005.
(iii) Storage tanks inside of buildings shall be permitted only in
areas at or above grade which have adequate drainage and are separated
from the processing area by construction having a fire resistance
rating of at least 2 hours.
(iv) The storage of flammable or combustible liquids in containers
shall be in accordance with the applicable provisions of WAC
296-24-33009.
(b) Piping, valves, and fittings.
(i) Piping, valves, and fittings shall be in accordance with WAC
296-24-33007.
(ii) Approved flexible connectors may be used where vibration exists
or where frequent movement is necessary. Approved hose may be used
at transfer stations.
(iii) Piping containing flammable or combustible liquids shall be
identified.
(c) Transfer.
(i) The transfer of large quantities of flammable or combustible
liquids shall be through piping by means of pumps or water displacement.
Except as required in process equipment, gravity flow shall not be
used. The use of compressed air as a transferring medium is prohibited.
(ii) Positive displacement pumps shall be provided with pressure
relief discharging back to the tank or to pump suction.
(d) Equipment.
(i) Equipment shall be designed and arranged to prevent the unintentional
escape of liquids and vapors and to minimize the quantity escaping
in the event of accidental release.
(ii) Where the vapor space of equipment is usually within the flammable
range, the probability of explosion damage to the equipment can be
limited by inerting, by providing an explosion suppression system,
or by designing the equipment to contain the peak explosion pressure
which may be modified by explosion relief. Where the special hazards
of operation, sources of ignition, or exposures indicate a need, consideration
shall be given to providing protection by one or more of the above
means.
(5) Tank vehicle and tank car loading and unloading. Tank vehicle and
tank car loading or unloading facilities shall be separated from
aboveground tanks, warehouses, other plant buildings, or nearest
line of adjoining property which may be built upon by a distance
of 25 feet for Class I liquids and 15 feet for Class II and Class
III liquids measured from the nearest position of any fill stem.
Buildings for pumps or shelters for personnel may be a part of
the facility. Operations of the facility shall comply with the
appropriate portions of WAC
296-24-33013(3).
(6) Fire control.
(a) Portable extinguishers. Approved portable fire extinguishers of
appropriate size, type and number shall be provided.
(b) Other controls. Where the special hazards of operation or exposure
indicate a need, the following fire control provision shall be provided.
(i) A reliable water supply shall be available in pressure and quantity
adequate to meet the probable fire demands.
(ii) Hydrants shall be provided in accordance with accepted good
practice.
(iii) Hose connected to a source of water shall be installed so that
all vessels, pumps, and other equipment containing flammable or combustible
liquids can be reached with at least one hose stream. Nozzles that
are capable of discharging a water spray shall be provided.
(iv) Processing plants shall be protected by an approved automatic
sprinkler system or equivalent extinguishing system. If special extinguishing
systems including but not limited to those employing foam, carbon
dioxide, or dry chemical are provided, approved equipment shall be
used and installed in an approved manner.
(c) Alarm systems. An approved means for prompt notification of fire
to those within the plant and any public fire department available shall
be provided. It may be advisable to connect the plant system with the
public system where public fire alarm system is available.
(d) Maintenance. All plant fire protection facilities shall be adequately
maintained and periodically inspected and tested to make sure they are
always in satisfactory operating condition and that they will serve
their purpose in time of emergency.
(7) Sources of ignition.
(a) General.
(i) Precautions shall be taken to prevent the ignition of flammable
vapors. Sources of ignition include but are not limited to open flames;
lightning; smoking; cutting and welding; hot surfaces; frictional
heat; static, electrical, any mechanical sparks; spontaneous ignition,
including heat-producing chemical reactions; and radiant heat.
(ii) Class I liquids shall not be dispensed into containers unless
the nozzle and container are electrically interconnected. Where the
metallic floorplate on which the container stands while filling is
electrically connected to the fill stem or where the fill stem is
bonded to the container during filling operations by means of a bond
wire, the provisions of this section shall be deemed to have been
complied with.
(b) Maintenance and repair.
(i) When necessary to do maintenance work in a flammable or combustible
liquid processing area, the work shall be authorized by a responsible
representative of the employer.
(ii) Hot work such as welding or cutting operations, use of spark-producing
power tools, and chipping operations shall be permitted only under
supervision of an individual in responsible charge who shall make
an inspection of the area to be sure that it is safe for the work
to be done and that safe procedures will be followed for the work
specified.
(c) Electrical.
(i) All electrical wiring and equipment within storage or processing
areas shall be installed according to chapter
296-24 WAC Part L.
(ii) Locations where flammable vapor-air mixtures may exist under
normal operations shall be classified Class I, Division 1
according to the requirements of chapter
296-24 WAC Part L. For those pieces of equipment installed
in accordance with (3)(c)(ii) of this section, the Division
1 area shall extend 5 feet in all directions from all points
of vapor liberation. All areas within pits shall be classified
Division 1 if any part of the pit is within a Division 1 or
2 classified area, unless the pit is provided with mechanical
ventilation.
(iii) Locations where flammable vapor-air mixtures may exist under
abnormal conditions and for a distance beyond Division 1 locations
shall be classified Division 2 according to the requirements
of chapter
296-24 WAC Part L. These locations include an area within
20 feet horizontally, 3 feet vertically beyond a Division
1 area, and up to 3 feet above floor or grade level within
25 feet, if indoors, or 10 feet if outdoors, from any pump,
bleeder, withdrawal fittings, meter, or similar device handling
Class I liquids. Pits provided with adequate mechanical ventilation
within a Division 1 or 2 area shall be classified Division
2. If Class II or Class III liquids only are handled, then
ordinary electrical equipment is satisfactory though care
shall be used in locating electrical apparatus to prevent
hot metal from falling into open equipment.
(iv) Where the provisions of (7)(c)(i), (ii), and (iii) of this section
require the installation of explosion-proof equipment, ordinary electrical
equipment including switchgear may be used if installed in a room
or enclosure which is maintained under positive pressure with respect
to the hazardous area. Ventilation makeup air shall be uncontaminated
by flammable vapors.
(8) Housekeeping.
(a) General. Maintenance and operating practices shall be in accordance
with established procedures which will tend to control leakage and prevent
the accidental escape of flammable or combustible liquids. Spills shall
be cleaned up promptly.
(b) Access. Adequate aisles shall be maintained for unobstructed movement
of personnel and so that fire protection equipment can be brought to
bear on any part of the processing equipment.
(c) Waste and residues. Combustible waste material and residues in
a building or operating area shall be kept to a minimum, stored in closed
metal waste cans, and disposed of daily.
(d) Clear zone. Ground area around buildings and operating areas shall
be kept free of tall grass, weeds, trash, or other combustible materials.
[Statutory Authority: Chapter 49.17 RCW.
91-24-017 (Order 91-07), 296-24-33017, filed 11/22/91, effective 12/24/91.
Statutory Authority: RCW 49.17.040 and 49.17.050. 85-10-004 (Order 85-09),
296-24-33017, filed 4/19/85; Order 76-6, 296-24-33017, filed 3/1/76; Order
73-5, 296-24-33017, filed 5/9/73 and Order 73-4, 296-24-33017, filed 5/7/73.]
WAC 296-24-33019 Refineries, chemical
plants, and distilleries.
(1) Storage tanks. Flammable or combustible liquids shall be
stored in tanks, in containers, or in portable tanks. Tanks shall
be installed in accordance with WAC
296-24-33005. Tanks for the storage of flammable or combustible
liquids in tank farms and in locations other than process areas
shall be located in accordance with WAC
296-24-33005 (2)(a) and (b).
(2) Wharves. Wharves handling flammable or combustible liquids shall
be in accordance with WAC
296-24-33013(4).
(3) Fired and unfired pressure vessels.
(a) Fired vessels. Fired pressure vessels shall be constructed in accordance
with the Code for Fired Pressure Vessels, section I of the ASME Boiler
and Pressure Vessel Code--1968.
(b) Unfired vessels shall be constructed in accordance with the Code
for Unfired Pressure Vessels, section VIII of the ASME Boiler and Pressure
Vessel Code--1968.
(4) Location of process units. Process units shall be located so that
they are accessible from at least one side for the purpose of fire control.
Where topographical conditions are such that flammable or combustible
liquids may flow from a processing area so as to constitute a fire hazard
to property of others, provision shall be made to divert or impound the
flow by curbs, drains, or other suitable means.
(5) Fire control.
(a) Portable equipment. Portable fire extinguishment and control equipment
shall be provided in such quantities and types as are needed for the
special hazards of operation and storage.
(b) Water supply. Water shall be available in volume and at adequate
pressure to supply water hose streams, foam producing equipment, automatic
sprinklers, or water spray systems as the need is indicated by the special
hazards of operation and storage.
(c) Special equipment. Special extinguishing equipment such as that
utilizing foam, inert gas, or dry chemical shall be provided as the
need is indicated by the special hazards of operation and storage.
[Order 73-5, 296-24-33019, filed 5/9/73
and Order 73-4, 296-24-33019, filed 5/7/73.]
WAC 296-24-370 Spray
finishing using flammable and combustible materials.
[Order 73-5, 296-24-370, filed 5/9/73
and Order 73-4, 296-24-370, filed 5/7/73.]
WAC 296-24-37001
Definitions.
(1) Aerated solid powders. Aerated powders shall mean any powdered
material used as a coating material which shall be fluidized within a
container by passing air uniformly from below. It is common practice to
fluidize such materials to form a fluidized powder bed and then dip the
part to be coated into the bed in a manner similar to that used in liquid
dipping. Such beds are also used as sources for powder spray operations.
(2) Spraying area. Any area in which dangerous quantities of
flammable vapors or mists, or combustible residues, dusts, or deposits
are present due to the operation of spraying processes.
(3) Spray booth. A power-ventilated structure provided to enclose
or accommodate a spraying operation to confine and limit the escape of
spray, vapor, and residue, and to safely conduct or direct them to an
exhaust system.
(4) Waterwash spray booth. A spray booth equipped with a water
washing system designed to minimize dusts or residues entering exhaust
ducts and to permit the recovery of overspray finishing material.
(5) Dry spray booth. A spray booth not equipped with a water
washing system as described in subsection (4) of this section. A dry spray
booth may be equipped with (a) distribution or baffle plates to promote
an even flow of air through the booth or cause the deposit of overspray
before it enters the exhaust duct; or (b) overspray dry filters to minimize
dusts; or (c) overspray dry filters to minimize dusts or residues entering
exhaust ducts; or (d) overspray dry filter rolls designed to minimize
dusts or residues entering exhaust ducts; or (e) where dry powders are
being sprayed, with powder collection systems so arranged in the exhaust
to capture oversprayed material.
(6) Fluidized bed. A container holding powder coating material
which is aerated from below so as to form an air-supported expanded cloud
of such material through which the preheated object to be coated is immersed
and transported.
(7) Electrostatic fluidized bed. A container holding powder coating
material which is aerated from below so as to form an air-supported expanded
cloud of such material which is electrically charged with a charge opposite
to the charge of the object to be coated; such object is transported through
the container immediately above the charged and aerated materials in order
to be coated.
(8) Approved. Shall mean approved and listed by a nationally recognized
testing laboratory. Refer to federal regulation 29 CRF 1910.7 for definition
of nationally recognized testing laboratory.
(9) Listed. See "approved" in subsection (8) of this section.
[Statutory Authority: Chapter 49.17 RCW.
88-23-054 (Order 88-25), 296-24-37001, filed 11/14/88; Order 76-6, 296-24-37001,
filed 3/1/76; Order 73-5, 296-24-37001, filed 5/9/73 and Order 73-4, 296-24-37001,
filed 5/7/73.]
WAC 296-24-37003
Spray booths.
(1) Construction. Spray booths shall be substantially constructed of
steel, securely and rigidly supported, or of concrete or masonry except
that aluminum or other substantial noncombustible material may be used
for intermittent or low volume spraying. Spray booths shall be designed
to sweep air currents toward the exhaust outlet.
(2) Interiors. The interior surfaces of spray booths shall be smooth
and continuous without edges and otherwise designed to prevent pocketing
of residues and facilitate cleaning and washing without injury.
(3) Floors. The floor surface of a spray booth and operator's working
area, if combustible, shall be covered with noncombustible material of
such character as to facilitate the safe cleaning and removal of residues.
(4) Distribution or baffle plates. Distribution or baffle plates, if
installed to promote an even flow of air through the booth or cause the
deposit of overspray before it enters the exhaust duct, shall be of noncombustible
material and readily removable or accessible on both sides for cleaning.
Such plates shall not be located in exhaust ducts.
(5) Dry type overspray collectors--(Exhaust air filters). In conventional
dry type spray booths, overspray dry filters or filter rolls, if installed,
shall conform to the following:
(a) The spraying operations except electrostatic spraying operations
shall be so designed, installed and maintained that the average air
velocity over the open face of the booth (or booth cross section during
spraying operations) shall be not less than 100 linear feet per minute.
Electrostatic spraying operations may be conducted with an air velocity
over the open face of the booth of not less than 60 linear feet per
minute, or more, depending on the volume of the finishing material being
applied and its flammability and explosion characteristics. Visible
gauges or audible alarm or pressure activated devices shall be installed
to indicate or insure that the required air velocity is maintained.
Dry spray booths equipped with a filter roll which is automatically
advanced when the air velocity is reduced to that specified in this
section should be arranged to cause shutdown of spraying operations
if the filter roll fails to advance automatically. Maintenance procedures
should be established to assure replacing filter pads before excessive
restriction to airflow occurs. Filter pads should be inspected after
each period of use and clogged filter pads discarded and replaced. Filter
rolls shall be inspected to insure proper replacement of filter media.
(b) All discarded filter pads and filter rolls shall be immediately
removed to a safe, well-detached location or placed in a water-filled
metal container and disposed of at the close of the day's operation
unless maintained completely in water.
(c) The location of filters in a spray booth shall be so as to not
reduce the effective booth enclosure of the articles being sprayed.
(d) Space within the spray booth on the downstream and upstream sides
of filters shall be protected with an approved automatic sprinkler system
meeting one of the following requirements:
(i) An automatic sprinkler system as defined in WAC
296-24-607; or
(ii) A fixed dry chemical extinguishing system as defined in WAC
296-24-622; or
(iii) A fixed carbon dioxide gaseous agent system as defined in WAC
296-24-623.
(e) Filters or filter rolls shall not be used when applying a spray
material known to be highly susceptible to spontaneous heating and ignition.
(f) Clean filters or filter rolls shall be noncombustible or of a type
having a combustibility not in excess of Class 2 filters as
listed by Underwriters' Laboratories, Inc. Filters and filter
rolls shall not be alternately used for different types of coating
materials, where the combination of materials may be conducive
to spontaneous ignition. See also WAC
296-24-37013(6).
(6) Frontal area. Each spray booth having a frontal area larger than
9 square feet shall have a metal deflector or curtain not less than 2
1/2 inches deep installed at the upper outer edge of the booth over the
opening.
(7) Conveyors. Where conveyors are arranged to carry work into or out
of spray booths, the openings therefor shall be as small as practical.
(8) Separation of operations. Each spray booth shall be separated from
other operations by not less than 3 feet, or by a greater distance,
or by such partition or wall as to reduce the danger from juxtaposition
of hazardous operations. See also WAC
296-24-37005(1).
(9) Cleaning. Spray booths shall be so installed that all portions are
readily accessible for cleaning. A clear space of not less than 3 feet
on all sides shall be kept free from storage or combustible construction.
(10) Illumination. When spraying areas are illuminated through glass
panels or other transparent materials, only fixed lighting units shall
be used as a source of illumination. Panels shall effectively isolate
the spraying area from the area in which the lighting unit is located,
and shall be of a noncombustible material of such a nature or so protected
that breakage will be unlikely. Panels shall be so arranged that normal
accumulations of residue on the exposed surface of the panel will not
be raised to a dangerous temperature by radiation or conduction from the
source of illumination.
[Statutory Authority: Chapter 49.17 RCW.
89-11-035 (Order 89-03), 296-24-37003, filed 5/15/89, effective 6/30/89;
Order 76-6, 296-24-37003, filed 3/1/76; Order 73-5, 296-24-37003, filed
5/9/73 and Order 73-4, 296-24-37003, filed 5/7/73.]
WAC 296-24-37005
Electrical and other sources of ignition.
(1) Conformance. All electrical equipment, open flames and other sources
of ignition shall conform to the requirements of this section, except
as follows:
(a) Electrostatic apparatus shall conform to the requirements
of WAC
296-24-37015 and 296-24-37017.
(b) Drying, curing, and fusion apparatus shall conform to the requirements
of WAC
296-24-37019.
(c) Automobile undercoating spray operations in garages shall conform
to the requirements of WAC
296-24-37021.
(d) Powder coating equipment shall conform to the requirements of WAC
296-24-37023.
(2) Minimum separation. There shall be no open flame or spark producing
equipment in any spraying area nor within 20 feet thereof, unless separated
by a partition.
(3) Hot surfaces. Space-heating appliances, steampipes, or hot surfaces
shall not be located in a spraying area where deposits of combustible
residues may readily accumulate.
(4) Wiring conformance. Electrical wiring and equipment shall conform
to the provisions of this section and chapter
296-24 WAC Part L.
(5) Combustible residues, areas. Unless specifically approved for locations
containing both deposits of readily ignitable residue and explosive vapors,
there shall be no electrical equipment in any spraying area, whereon deposits
of combustible residues may readily accumulate, except wiring in rigid
conduit or in boxes or fittings containing no taps, splices, or terminal
connections.
(6) Wiring type approved. Electrical wiring and equipment not
subject to deposits of combustible residues but located in a spraying
area as herein defined shall be of explosion-proof type approved
for Class I, Group D locations and conform to the provisions of
chapter
296-24 WAC Part L, for Class I, Division 1, hazardous locations.
Electrical wiring, motors, and other equipment outside of but
within twenty feet of any spraying area, and not separated therefrom
by partitions, shall not produce sparks under normal operating
conditions and conform to the provisions of chapter
296-24 WAC Part L for Class I, Division 2, hazardous locations.
(7) Lamps. Electric lamps outside of, but within twenty feet of any spraying
area, and not separated therefrom by a partition, shall be totally enclosed
to prevent the falling of hot particles and shall be protected from mechanical
injury by suitable guards or by location.
(8) Portable lamps. Portable electric lamps shall not be used in any
spraying area during spraying operations. Portable electric lamps, if
used during cleaning or repairing operations, shall be of the type approved
for hazardous Class I locations.
(9) Grounding.
(a) All metal parts of spray booths, exhaust ducts, and piping systems
conveying flammable or combustible liquids or aerated solids shall be
properly electrically grounded in an effective and permanent manner.
(b) "Airless" high-fluid pressure spray guns and any conductive object
being sprayed should be properly electrically grounded.
[Statutory Authority: Chapter 49.17 RCW.
91-24-017 (Order 91-07), 296-24-37005, filed 11/22/91, effective 12/24/91.
Statutory Authority: RCW 49.17.040 and 49.17.050. 85-10-004 (Order 85-09),
296-24-37005, filed 4/19/85; Order 76-6, 296-24-37005, filed 3/1/76; Order
73-5, 296-24-37005, filed 5/9/73 and Order 73-4, 296-24-37005, filed 5/7/73.]
WAC 296-24-37007
Ventilation.
(1) Conformance. Ventilating and exhaust systems shall be in accordance
with the Standard for Blower and Exhaust Systems for Vapor Removal, NFPA
No. 91-1961, where applicable and shall also conform to the provisions
of this section.
(2) General. All spraying areas shall be provided with mechanical ventilation
adequate to remove flammable vapors, mists or powders to a safe location
and to confine and control combustible residues so that life is not endangered.
Mechanical ventilation shall be kept in operation at all times while spraying
operations are being conducted and for a sufficient time thereafter to
allow vapors from drying coated articles and drying finishing material
residue to be exhausted.
(3) Independent exhaust. Each spray booth shall have an independent exhaust
duct system discharging to the exterior of the building, except that multiple
cabinet spray booths in which identical spray finishing material is used
with a combined frontal area of not more than 18 square feet may have
a common exhaust. If more than one fan serves one booth, all fans shall
be so interconnected that one fan cannot operate without all fans being
operated.
(4) Fan-rotating element. The fan-rotating element shall be nonferrous
or nonsparking or the casing shall consist of or be lined with such material.
There shall be ample clearance between the fan-rotating element and the
fan casing to avoid a fire by friction, necessary allowance being made
for ordinary expansion and loading to prevent contact between moving parts
and the duct or fan housing. Fan blades shall be mounted on a shaft sufficiently
heavy to maintain perfect alignment even when the blades of the fan are
heavily loaded, the shaft preferably to have bearings outside the duct
and booth. All bearings shall be of the self-lubricating type, or lubricated
from the outside duct.
(5) Electric motors. Electric motors driving exhaust fans shall not be
placed inside booths or ducts. See also WAC
296-24-37005.
(6) Belts.Belts shall not enter the duct or booth unless the belt and
pulley within the duct or booth are thoroughly enclosed.
(7) Exhaust ducts. Exhaust ducts shall be constructed of steel and shall
be substantially supported. Exhaust ducts without dampers are preferred;
however, if dampers are installed, they shall be maintained so that they
will be in a full open position at all times the ventilating system is
in operation.
(a) Exhaust ducts shall be protected against mechanical damage and
have a clearance from unprotected combustible construction or other
combustible material of not less than 18 inches.
(b) If combustible construction is provided with the following protection
applied to all surfaces within 18 inches, clearances may be reduced
to the distances indicated:
(i) 8-gage sheet metal on 1/4-inch 12 inches.
asbestos mill board.
(ii) 28-gage sheet metal on 1/8-inch 9 inches.
asbestos mill board spaced out 1 inch on noncombustible spacers.
(iii) 22-gage sheet metal on 1-inch 3 inches.
rockwool batts reinforced with wire mesh or the equivalent.
(iv) Where ducts are protected with an approved automatic sprinkler
system, properly maintained, the clearance required in (7)(a) of this
section may be reduced to 6 inches.
(8) Discharge clearance. Unless the spray booth exhaust duct terminal
is from a water-wash spray booth, the terminal discharge point shall be
not less than 6 feet from any combustible exterior wall or roof nor discharge
in the direction of any combustible construction or unprotected opening
in any noncombustible exterior wall within 25 feet.
(9) Air exhaust. Air exhaust from spray operations shall not be directed
so that it will contaminate makeup air being introduced into the spraying
area or other ventilating intakes, nor directed so as to create a nuisance.
Air exhausted from spray operations shall not be recirculated.
(10) Access doors. When necessary to facilitate cleaning, exhaust ducts
shall be provided with an ample number of access doors.
(11) Room intakes. Air intake openings to rooms containing spray finishing
operations shall be adequate for the efficient operation of exhaust fans
and shall be so located as to minimize the creation of dead air pockets.
(12) Drying spaces. Freshly sprayed articles shall be dried only in spaces
provided with adequate ventilation to prevent the formation of
explosive vapors. In the event adequate and reliable ventilation
is not provided such drying spaces shall be considered a spraying
area. (See also WAC
296-24-37019.)
[Order 76-6, 296-24-37007, filed 3/1/76;
Order 73-5, 296-24-37007, filed 5/9/73 and Order 73-4, 296-24-37007, filed
5/7/73.]
WAC 296-24-37009
Flammable and combustible liquids--Storage and handling.
(1) Conformance. The storage of flammable or combustible liquids in connection
with spraying operations shall conform to the requirements of
WAC
296-24-330, where applicable.
(2) Quantity. The quantity of flammable or combustible liquids kept in
the vicinity of spraying operations shall be the minimum required for
operations and should ordinarily not exceed a supply for 1 day or one
shift. Bulk storage of portable containers of flammable or combustible
liquids shall be in a separate, constructed building detached from other
important buildings or cut off in a standard manner.
(3) Containers. Original closed containers, approved portable tanks,
approved safety cans or a properly arranged system of piping shall be
used for bringing flammable or combustible liquids into spray finishing
room. Open or glass containers shall not be used.
(4) Transferring liquids. Except as provided in (5) of this section,
the withdrawal of flammable and combustible liquids from containers having
a capacity of greater than 60 gallons shall be by approved pumps. The
withdrawal of flammable or combustible liquids from containers and the
filling of containers, including portable mixing tanks, shall be done
only in a suitable mixing room or in a spraying area when the ventilating
system is in operation. Adequate precautions shall be taken to protect
against liquid spillage and sources of ignition.
(5) Spraying containers. Containers supplying spray nozzles shall be
of closed type or provided with metal covers kept closed. Containers not
resting on floors shall be on metal supports or suspended by wire cables.
Containers supplying spray nozzles by gravity flow shall not exceed 10
gallons capacity. Original shipping containers shall not be subject to
air pressure for supplying spray nozzles. Containers under air pressure
supplying spray nozzles shall be of limited capacity, not exceeding that
necessary for 1 day's operation; shall be designed and approved for such
use; shall be provided with a visible pressure gage; and shall be provided
with a relief valve set to operate in conformance with the requirements
of the Code for Unfired Pressure Vessels, Section VIII of the ASME Boiler
and Pressure Vessel Code--1968. Containers under air pressure supplying
spray nozzles, air-storage tanks and coolers shall conform to the standards
of the Code for Unfired Pressure Vessels, Section VIII of the ASME Boiler
and Pressure Vessel Code--1968 for construction, tests, and maintenance.
(6) Pipes and hoses.
(a) All containers or piping to which is attached a hose or flexible
connection shall be provided with a shutoff valve at the connection.
Such valves shall be kept shut when spraying operations are not being
conducted.
(b) When a pump is used to deliver products, automatic means shall
be provided to prevent pressure in excess of the design working pressure
of accessories, piping, and hose.
(c) All pressure hose and couplings shall be inspected at regular intervals
appropriate to this service. The hose and couplings shall be tested
with the hose extended, and using the "inservice maximum operating pressures."
Any hose showing material deteriorations, signs of leakage, or weakness
in its carcass or at the couplings, shall be withdrawn from service
and repaired or discarded.
(d) Piping systems conveying flammable or combustible liquids shall
be of steel or other material having comparable properties of resistance
to heat and physical damage. Piping systems shall be properly bonded
and grounded.
(7) Spray liquid heaters. Electrically powered spray liquid heaters
shall be approved and listed for the specific location in which
used (see WAC
296-24-37005). Heaters shall not be located in spray booths
nor other locations subject to the accumulation of deposits or
combustible residue. Agitators, if used, should preferably be
driven by compressed air, water, or low-pressure steam. If an
electric motor is used, (see WAC
296-24-37005).
(8) Pump relief. If flammable or combustible liquids are supplied to
spray nozzles by positive displacement pumps, the pump discharge line
shall be provided with an approved relief valve discharging to a pump
suction or a safe detached location, or a device provided to stop the
prime mover if the discharge pressure exceeds the safe operating pressure
of the system.
(9) Grounding. Whenever flammable or combustible liquids are transferred
from one container to another, both containers shall be effectively bonded
and grounded to prevent discharge sparks of static electricity.
[Order 73-5, 296-24-37009, filed 5/9/73
and Order 73-4, 296-24-37009, filed 5/7/73.]
WAC 296-24-37011
Protection.
(1) Conformance. In sprinklered buildings, the automatic sprinkler system
in rooms containing spray finishing operations shall conform to
the requirements of WAC
296-24-607. In unsprinklered buildings where sprinklers are
installed only to protect spraying areas, the installation shall
conform to such standards insofar as they are applicable. Sprinkler
heads shall be located so as to provide water distribution throughout
the entire booth.
(2) Valve access. Automatic sprinklers protecting each spray booth (together
with its connecting exhaust) shall be under an accessibly located separate
outside stem and yoke (OS&Y) subcontrol valve.
(3) Cleaning of heads. Sprinklers protecting spraying areas shall be
kept as free from deposits as practical by cleaning daily if necessary.
(See also WAC
296-24-37013.)
(4) Portable extinguishers. An adequate supply of suitable portable fire
extinguishers shall be installed near all spraying areas.
[Statutory Authority: RCW 49.17.040 and
49.17.050. 82-02-003 (Order 81-32), 296-24-37011, filed 12/24/81; Order
73-5, 296-24-37011, filed 5/9/73 and Order 73-4, 296-24-37011, filed 5/7/73.]
WAC 296-24-37013
Operations and maintenance.
(1) Spraying. Spraying shall not be conducted outside of predetermined
spraying areas.
(2) Cleaning. All spraying areas shall be kept as free from the accumulation
of deposits of combustible residues as practical, with cleaning conducted
daily if necessary. Scrapers, spuds, or other such tools used for cleaning
purposes shall be of nonsparking material.
(3) Residue disposal. Residue scrapings and debris contaminated with
residue shall be immediately removed from the premises and properly disposed
of. Approved metal waste cans shall be provided wherever rags or waste
are impregnated with finishing material and all such rags or waste deposited
therein immediately after use. The contents of waste cans shall be properly
disposed of at least once daily or at the end of each shift.
(4) Clothing storage. Spray finishing employees' clothing shall not be
left on the premises overnight unless kept in metal lockers.
(5) Cleaning solvents. The use of solvents for cleaning operations shall
be restricted to those having flashpoints not less than 100°F; however,
for cleaning spray nozzles and auxiliary equipment, solvents having flashpoints
not less than those normally used in spray operations may be used. Such
cleaning shall be conducted inside spray booths and ventilating equipment
operated during cleaning.
(6) Hazardous materials combinations. Spray booths shall not be alternately
used for different types of coating materials, where the combination of
the materials may be conducive to spontaneous ignition, unless all deposits
of the first used material are removed from the booth and exhaust ducts
prior to spraying with the second used material.
(7) "No smoking" signs. "No smoking" signs in large letters on
contrasting color background shall be conspicuously posted at
all spraying areas and paint storage rooms.
[Order 73-5, 296-24-37013, filed 5/9/73
and Order 73-4, 296-24-37013, filed 5/7/73.]
WAC 296-24-37015
Fixed electrostatic apparatus.
(1) Conformance. Where installation and use of electrostatic
spraying equipment is used, such installation and use shall conform
to all other requirements contained in WAC 296-24-370
through 296-24-37027.
(2) Type approval. Electrostatic apparatus and devices used in connection
with coating operations shall be of approved types.
(3) Location. Transformers, power packs, control apparatus, and all other
electrical portions of the equipment, with the exception of high-voltage
grids, electrodes, and electrostatic atomizing heads and their
connections, shall be located outside of the spraying area, or
shall otherwise conform to the requirements of WAC
296-24-37005.
(4) Support. Electrodes and electrostatic atomizing heads shall be adequately
supported in permanent locations and shall be effectively insulated from
the ground. Electrodes and electrostatic atomizing heads which are permanently
attached to their bases, supports, or reciprocators, shall be deemed to
comply with this section. Insulators shall be nonporous and noncombustible.
(5) Insulators, grounding. High-voltage leads to electrodes shall be
properly insulated and protected from mechanical injury or exposure to
destructive chemicals. Electrostatic atomizing heads shall be effectively
and permanently supported on suitable insulators and shall be effectively
guarded against accidental contact or grounding. An automatic means shall
be provided for grounding the electrode system when it is electrically
deenergized for any reason. All insulators shall be kept clean and dry.
(6) Safe distance. A safe distance shall be maintained between goods
being painted and electrodes or electrostatic atomizing heads or conductors
of at least twice the sparking distance. A suitable sign indicating this
safe distance shall be conspicuously posted near the assembly.
(7) Conveyors required. Goods being painted using this process are to
be supported on conveyors. The conveyors shall be so arranged as to maintain
safe distances between the goods and the electrodes or electrostatic atomizing
heads at all times. Any irregularly shaped or other goods subject to possible
swinging or movement shall be rigidly supported to prevent such swinging
or movement which would reduce the clearance to less than that specified
in (6) of this section.
(8) Prohibition. This process is not acceptable where goods being coated
are manipulated by hand. When finishing materials are applied
by electrostatic equipment which is manipulated by hand, see WAC
296-24-37017 for applicable requirements. (Rev. 1-23-76)
(9) Fail-safe controls. Electrostatic apparatus shall be equipped with
automatic controls which will operate without time delay to disconnect
the power supply to the high voltage transformer and to signal the operator
under any of the following conditions:
(a) Stoppage of ventilating fans or failure of ventilating equipment
from any cause.
(b) Stoppage of the conveyor carrying goods through the high voltage
field.
(c) Occurrence of a ground or of an imminent ground at any point on
the high voltage system.
(d) Reduction of clearance below that specified in (6) of this section.
(10) Guarding. Adequate booths, fencing, railings, or guards shall be
so placed about the equipment that they, either by their location or character
or both, assure that a safe isolation of the process is maintained from
plant storage or personnel. Such railings, fencing, and guards shall be
of conducting material, adequately grounded.
(11) Ventilation. Where electrostatic atomization is used the spraying
area shall be so ventilated as to insure safe conditions from a fire and
health standpoint.
(12) Fire protection. All areas used for spraying, including the interior
of the booth, shall be protected by automatic sprinklers where this protection
is available. Where this protection is not available, other approved automatic
extinguishing equipment shall be provided.
[Order 76-6, 296-24-37015, filed 3/1/76;
Order 73-5, 296-24-37015, filed 5/9/73 and Order 73-4, 296-24-37015, filed
5/7/73.]
WAC 296-24-37017 Electrostatic hand
spraying equipment.
(1) Application. This section shall apply to any equipment using electrostatically
charged elements for the atomization and/or, precipitation of materials
for coatings on articles, or for other similar purposes in which the atomizing
device is hand held and manipulated during the spraying operation.
(2) Conformance. Electrostatic hand spraying equipment shall
conform with the other provisions of WAC
296-24-370 through
296-24-37027.
(3) Equipment approval and specifications. Electrostatic hand spray apparatus
and devices used in connection with coating operations shall be of approved
types. The equipment should be so designed that the maximum surface temperature
of the equipment in the spraying area shall not exceed 150°F under any
condition. The high voltage circuits shall be designed so as to not produce
a spark of sufficient intensity to ignite any vapor-air mixtures nor result
in appreciable shock hazard upon coming in contact with a grounded object
under all normal operating conditions. The electrostatically charged exposed
elements of the handgun shall be capable of being energized only by a
switch which also controls the coating material supply.
(4) Electrical support equipment. Transformers, powerpacks, control apparatus,
and all other electrical portions of the equipment, with the exception
of the handgun itself and its connections to the powder supply
shall be located outside of the spraying area or shall otherwise
conform to the requirements of WAC
296-24-37005.
(5) Spray gun ground. The handle of the spraying gun shall be electrically
connected to ground by a metallic connection and to be so constructed
that the operator in normal operating position is in intimate electrical
contact with the grounded handle.
(6) Grounding--General. All electrically conductive objects in the spraying
area shall be adequately grounded. This requirement shall apply to paint
containers, wash cans, and any other objects or devices in the area. The
equipment shall carry a prominent permanently installed warning regarding
the necessity for this grounding feature.
(7) Maintenance of grounds. Objects being painted or coated shall be
maintained in metallic contact with the conveyor or other grounded support.
Hooks shall be regularly cleaned to insure this contact and areas of contact
shall be sharp points or knife edges where possible. Points of support
of the object shall be concealed from random spray where feasible and
where the objects being sprayed are supported from a conveyor, the point
of attachment to the conveyor shall be so located as to not collect spray
material during normal operation.
(8) Interlocks. The electrical equipment shall be so interlocked with
the ventilation of the spraying area that the equipment cannot be operated
unless the ventilation fans are in operation.
(9) Ventilation. The spraying operation shall take place within a spray
area which is adequately ventilated to remove solvent vapors released
from the operation.
[Order 73-5, 296-24-37017, filed 5/9/73
and Order 73-4, 296-24-37017, filed 5/7/73.]
WAC 296-24-37019
Drying, curing, or fusion apparatus.
(1) Conformance. Drying, curing, or fusion apparatus in connection with
spray application of flammable and combustible finishes shall conform
to the Standard for Ovens and Furnaces, NFPA 86A-1969, where applicable
and shall also conform with the following requirements of this section.
(2) Alternate use prohibited. Spray booths, rooms, or other enclosures
used for spraying operations shall not alternately be used for the purpose
of drying by any arrangement which will cause a material increase in the
surface temperature of the spray booth, room, or enclosure.
(3) Adjacent system interlocked. Except as specifically provided in (4)
of this section, drying, curing, or fusion units utilizing a heating system
having open flames or which may produce sparks shall not be installed
in a spraying area, but may be installed adjacent thereto when equipped
with an interlocked ventilating system arranged to:
(a) Thoroughly ventilate the drying space before the heating system
can be started;
(b) Maintain a safe atmosphere at any source of ignition;
(c) Automatically shut down the heating system in the event of failure
of the ventilating system.
(4) Alternate use permitted. Automobile refinishing spray booths or enclosures,
otherwise installed and maintained in full conformity with this section,
may alternately be used for drying with portable electrical infrared drying
apparatus when conforming with the following:
(a) Interior (especially floors) of spray enclosures shall be kept
free of overspray deposits.
(b) During spray operations, the drying apparatus and electrical connections
and wiring thereto shall not be located within spray enclosure nor in
any other location where spray residues may be deposited thereon.
(c) The spraying apparatus, the drying apparatus, and the ventilating
system of the spray enclosure shall be equipped with suitable interlocks
so arranged that:
(i) The spraying apparatus cannot be operated while the drying apparatus
is inside the spray enclosure.
(ii) The spray enclosure will be purged of spray vapors for a period
of not less than 3 minutes before the drying apparatus can be energized.
(iii) The ventilating system will maintain a safe atmosphere within
the enclosure during the drying process and the drying process apparatus
will automatically shut off in the event of failure of the ventilating
system.
(d) All electrical wiring and equipment of the drying apparatus shall
conform with the applicable sections of chapter
296-24 WAC Part L. Only equipment of a type approved for
Class I, Division 2 hazardous locations shall be located within
18 inches of floor level. All metallic parts of the drying apparatus
shall be properly electrically bonded and grounded.
(e) The drying apparatus shall contain a prominently located, permanently
attached warning sign indicating that ventilation should be maintained
during the drying period and that spraying should not be conducted in
the vicinity that spray will deposit on apparatus.
[Statutory Authority: Chapter 49.17 RCW.
91-24-017 (Order 91-07), 296-24-37019, filed 11/22/91, effective 12/24/91.
Statutory Authority: RCW 49.17.040 and 49.17.050. 85-10-004 (Order 85-09),
296-24-37019, filed 4/19/85; Order 76-6, 296-24-37019, filed 3/1/76; Order
73-5, 296-24-37019, filed 5/9/73 and Order 73-4, 296-24-37019, filed 5/7/73.]
WAC 296-24-37021
Automobile undercoating in garages.
Automobile undercoating spray operations in garages, conducted
in areas having adequate natural or mechanical ventilation, are
exempt from the requirements pertaining to spray finishing operations,
when using undercoating materials not more hazardous than kerosene
(as listed by Underwriters' Laboratories in respect to fire hazard
rating 30-40) or undercoating materials using only solvents listed
as having a flash point in excess of 100°F. Undercoating spray
operations not conforming to these provisions are subject to all
requirements of WAC
296-24-370 through 296-24-37027,
pertaining to spray finishing operations.
[Order 73-5, 296-24-37021, filed 5/9/73
and Order 73-4, 296-24-37021, filed 5/7/73.]
WAC 296-24-37023
Powder coating.
(1) Electrical and other sources of ignition. Electrical equipment
and other sources of ignition shall conform to the requirements
of WAC
296-24-37005 and chapter
296-24 WAC Part L.
(2) Ventilation.
(a) In addition to the provisions of WAC
296-24-37007, where applicable, exhaust ventilation shall
be sufficient to maintain the atmosphere below the lowest explosive
limits for the materials being applied. All nondeposited air-suspended
powders shall be safely removed via exhaust ducts to the powder
recovery cyclone or receptacle. Each installation shall be designed
and operated to meet the foregoing performance specification.
(b) Powders shall not be released to the outside atmosphere.
(3) Drying, curing, or fusion equipment. The provisions of the Standard
for Ovens and Furnaces, NFPA No. 86A-1969 shall apply where applicable.
(4) Operation and maintenance.
(a) All areas shall be kept free of the accumulation of powder coating
dusts, particularly such horizontal surfaces as ledges, beams, pipes,
hoods, booths, and floors.
(b) Surfaces shall be cleaned in such manner as to avoid scattering
dust to other places or creating dust clouds.
(c) "No smoking" signs in large letters on contrasting color background
shall be conspicuously posted at all powder coating areas and powder
storage rooms.
(5) Fixed electrostatic spraying equipment. The provisions of WAC
296-24-37015 and other subsections of this section shall apply
to fixed electrostatic equipment, except that electrical equipment
not covered therein shall conform to (1) of this section.
(6) Electrostatic hand spraying equipment. The provisions of WAC
296-24-37017 and other subsections of this section, shall
apply to electrostatic handguns when used in powder coating, except
that electrical equipment not covered therein shall conform to
(1) of this section.
(7) Electrostatic fluidized beds.
(a) Electrostatic fluidized beds and associated equipment shall be
of approved types. The maximum surface temperature of this equipment
in the coating area shall not exceed 150°F. The high voltage circuits
shall be so designed as to not produce a spark of sufficient intensity
to ignite any powder-air mixtures nor result in appreciable shock hazard
upon coming in contact with a grounded object under normal operating
conditions.
(b) Transformers, powerpacks, control apparatus, and all other electrical
portions of the equipment, with the exception of the charging electrodes
and their connections to the power supply shall be located outside of
the powder coating area or shall otherwise conform to the requirements
of (1) of this section.
(c) All electrically conductive objects within the charging influence
of the electrodes shall be adequately grounded. The powder coating equipment
shall carry a prominent, permanently installed warning regarding the
necessity for grounding these objects.
(d) Objects being coated shall be maintained in contact with the conveyor
or other support in order to insure proper grounding. Hangers shall
be regularly cleaned to insure effective contact and areas of contact
shall be sharp points or knife edges where possible.
(e) The electrical equipment shall be so interlocked with the ventilation
system that the equipment cannot be operated unless the ventilation
fans are in operation.
[Statutory Authority: Chapter 49.17 RCW.
91-24-017 (Order 91-07), 296-24-37023, filed 11/22/91, effective 12/24/91.
Statutory Authority: RCW 49.17.040 and 49.17.050. 85-10-004 (Order 85-09),
296-24-37023, filed 4/19/85; Order 76-6, 296-24-37023, filed 3/1/76; Order
73-5, 296-24-37023, filed 5/9/73 and Order 73-4, 296-24-37023, filed 5/7/73.]
WAC 296-24-37025
Organic peroxides and dual component coatings.
(1) Conformance. All spraying operations involving the use of organic
peroxides and other dual component coatings shall be conducted in approved
sprinklered spray booths meeting the requirements of this section.
(2) Smoking. Smoking shall be prohibited and "no smoking" signs shall
be prominently displayed and only nonsparking tools shall be used in any
area where organic peroxides are stored, mixed or applied.
[Order 73-5, 296-24-37025, filed 5/9/73
and Order 73-4, 296-24-37025, filed 5/7/73.]
WAC 296-24-37027
Scope.
This section applies to flammable and combustible finishing materials
when applied as a spray by compressed air, "airless" or "hydraulic atomization,"
steam, electrostatic methods, or by any other means in continuous or intermittent
processes. The section also covers the application of combustible powders
by powder spray guns, electrostatic powder spray guns, fluidized beds,
or electrostatic fluidized beds. The section does not apply to outdoor
spray application of buildings, tanks or other similar structures, nor
to small portable spraying apparatus not used repeatedly in the same location.
[Order 73-5, 296-24-37027, filed 5/9/73
and Order 73-4, 296-24-37027, filed 5/7/73.]
WAC 296-24-405 Dip Tanks.
Note: Dip Tank requirements have been moved to WAC 296-835, Dipping and Coating Operations "Dip Tanks."
WAC 296-24-450 Chlorine
cylinders used in chlorinator systems.
Ventilation, storage of tanks and use of tanks shall meet specifications
of The Chlorine Manual, The Chlorine Institute, Inc., fifth edition, 1986.
[Statutory Authority: Chapter 49.17 RCW.
91-03-044 (Order 90-18), 296-24-450, filed 1/10/91, effective 2/12/91;
Order 74-27, 296-24-450, filed 5/7/74.]
|