General Safety & Health Standards |
|
WAC
296-24-475
Storage and handling of liquefied petroleum gases.
296-24-47501
Definitions
296-24-47503
Scope
296-24-47505
Basic rules.
296-24-47507
Cylinder systems.
296-24-47509
Systems utilizing containers other that DOT containers.
296-24-47511
Liquefied petroleum gas as a motor fuel.
296-24-47513
Storage of containers awaiting use or resale.
296-24-47517
Liquefied petroleum gas service stations.
WAC 296-24-475 Storage
and handling of liquefied petroleum gases.
[Order 73-5, § 296-24-475, filed 5/9/73
and Order 73-4, § 296-24-475, filed 5/7/73.]
WAC 296-24-47501
Definitions.
(1) API-ASME container. A container constructed in accordance
with the requirements of WAC
296-24-47505 (3)(a).
(2) ASME container. A container constructed in accordance with
the requirements of WAC
296-24-47505 (3)(a).
(3) Container assembly. An assembly consisting essentially of
the container and fittings for all container openings, including shutoff
valves, excess flow valves, liquid-level gaging devices, safety relief
devices, and protective housing.
(4) Containers. All vessels, such as tanks, cylinders, or drums,
used for transportation or storing liquefied petroleum gases.
(5) DOT. Department of transportation.
(6) DOT container. A container constructed in accordance with
the applicable requirements of 49 CFR chapter 1.
(7) "Liquefied petroleum gases." "LPG" and "LP-gas." Any material
which is composed predominantly of any of the following hydrocarbons,
or mixtures of them; propane, propylene, butanes (normal butane or iso-butane),
and butylenes.
(8) Movable fuel storage tenders or farm carts. Containers not
in excess of 1,200 gallons water capacity, equipped with wheels to be
towed from one location of usage to another. They are basically nonhighway
vehicles, but may occasionally be moved over public roads or highways.
They are used as a fuel supply for farm tractors, construction machinery
and similar equipment.
(9) P.S.I.G. Pounds per square inch gauge.
(10) P.S.I.A. Pounds per square inch absolute.
(11) Systems. An assembly of equipment consisting essentially
of the container or containers, major devices such as vaporizers, safety
relief valves, excess flow valves, regulators, and piping connecting such
parts.
(12) Vaporizer-burner. An integral vaporizer-burner unit, dependent
upon the heat generated by the burner as the source of heat to vaporize
the liquid used for dehydrators or dryers.
(13) Ventilation, adequate. When specified for the prevention
of fire during normal operation, ventilation shall be considered adequate
when the concentration of the gas in a gas-air mixture does not exceed
25 percent of the lower flammable limit.
(14) Approved. Unless otherwise indicated, listing or approval
by a nationally recognized testing laboratory. Refer to 29 CFR 1910.7
for definition of nationally recognized testing laboratory.
(15) Listed. See "approved" in WAC
296-24-47501(14).
(16) DOT specifications. Regulations of the department of transportation
published in 49 CFR chapter I.
(17) DOT regulations. See WAC 296-24-47501(16).
(18) DOT requirements. See WAC
296-24-47501(16).
(19) DOT cylinders. Cylinders meeting the requirements of 49 CFR
chapter I.
[Statutory Authority: Chapter 49.17 RCW.
88-23-054 (Order 88-25), § 296-24-47501, filed 11/14/88; Order 73-5, §
296-24-47501, filed 5/9/73 and Order 73-4, § 296-24-47501, filed 5/7/73.]
WAC 296-24-47503
Scope.
(1) Application.
(a) WAC
296-24-47505 applies to installations made in accordance
with the requirements of WAC
296-24-47507 through 296-24-47511,
and 296-24-47517,
except as noted in each of those sections.
(b) WAC
296-24-47507 through 296-24-47517
apply as provided in each of those sections.
(2) Inapplicability. These sections do not apply to:
(a) Marine and pipeline terminals, natural gas processing plants, refineries,
or tank farms other than those at industrial sites.
(b) LP-gas refrigerated storage systems;
(c) LP-gas when used with oxygen. The requirements of WAC
296-24-680 through 296-24-722
shall apply to such use;
(d) LP-gas when used in utility gas plants. The National Fire Protection
Association Standard for the Storage and Handling of Liquefied Petroleum
Gases at Utility Gas Plants, NFPA No. 59-1968, shall apply to such use;
(e) Low-pressure (not in excess of one-half pound per square inch or
14 inches water column) LP-gas piping systems, and the installation
and operation of residential and commercial appliances including their
inlet connections, supplied through such systems. For such systems,
the National Fire Protection Association Standard for the Installation
of Gas Appliances and Gas Piping, NFPA 54-1969 shall apply.
(3) Retroactivity. Unless otherwise stated, it is not intended that the
provisions of these sections be retroactive.
(a) Existing plants, appliances, equipment, buildings, structures,
and installations for the storage, handling or use of LP-gas, which
were in compliance with the current provisions of the National Fire
Protection Association Standard for the Storage and Handling of Liquefied
Petroleum Gases NFPA No. 58-1972, 1973 at the time of manufacture or
installation may be continued in use, if such continued use does not
constitute a recognized hazard that is causing or is likely to cause
death or serious physical harm to employees.
(b) Stocks of equipment and appliances on hand in such locations as
manufacturers' storage, distribution warehouses, and dealers' storage
and showrooms, which were in compliance with the current provisions
of the National Fire Protection Association Standard for the Storage
and Handling of Liquefied Petroleum Gases, NFPA No. 58-1972, 1973, at
the time of manufacture, may be placed in service, if such use does
not constitute a recognized hazard that is causing or is likely to cause
death or serious physical harm to employees.
[Statutory Authority: Order 73-5, § 296-24-47503,
filed 5/9/73 and Order 73-4, § 296-24-47503, filed 5/7/73.]
WAC 296-24-47505
Basic rules.
(1) Odorizing gases.
(a) All liquefied petroleum gases shall be effectively odorized by
an approved agent of such character as to indicate positively, by distinct
odor, the presence of gas down to concentration in air of not over one-fifth
the lower limit of flammability. Odorization, however, is not required
if harmful in the use of further processing of the liquefied petroleum
gas, or if odorization will serve no useful purpose as a warning agent
in such use or further processing.
(b) The odorization requirement of (a) of this subsection shall be
considered to be met by the use of 1.0 pounds of ethyl mercaptan, 1.0
pounds of thiophane or 1.4 pounds of amyl mercaptan per ten thousand
gallons of LP-gas. However, this listing of odorants and quantities
shall not exclude the use of other odorants that meet the odorization
requirements of (a) of this subsection.
(2) Approval of equipment and systems.
(a) Each system utilizing DOT containers in accordance with 49 CFR
Part 178 shall have its container valves, connectors, manifold valve
assemblies, and regulators approved.
(b) Each system for domestic or commercial use utilizing containers
of two thousand gallons or less water capacity, other than those constructed
in accordance with 49 CFR Part 178, shall consist of a container assembly
and one or more regulators, and may include other parts. The system
as a unit or the container assembly as a unit, and the regulator or
regulators, shall be individually listed.
(c) In systems utilizing containers of over two thousand gallons water
capacity, each regulator, container, valve, excess flow valve, gaging
device, and relief valve installed on or at the container, shall have
its correctness as to design, construction, and performance determined
by listing by a nationally recognized testing laboratory. Refer to federal
regulation 29 CFR 1910.7 for definition of nationally recognized testing
laboratory.
(d) The provisions of subsection (3)(a) of this section shall not be
construed as prohibiting the continued use or reinstallation of containers
constructed and maintained in accordance with the standard for the Storage
and Handling of Liquefied Petroleum Gases NFPA No. 58 in effect at the
time of fabrication.
(e) Containers used with systems embodied in this section and
WAC
296-24-47509 (3)(c) and 296-24-47513,
shall be constructed, tested, and stamped in accordance with
DOT specifications effective at the date of their manufacture.
(3) Requirements for construction and original test of containers.
(a) Containers used with systems embodied in WAC
296-24-47509, 296-24-47513
through 296-24-47517,
except as provided in WAC
296-24-47511 (3)(c), shall be designed, constructed, and
tested in accordance with the Rules for Construction of Unfired
Pressure Vessels, section VIII, Division 1, American Society
of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code,
1968 edition.
(b) Containers constructed according to the 1949 and earlier editions
of the ASME Code do not have to comply with U-2 through U-10 and U-19
thereof. Containers constructed according to U-70 in the 1949 and earlier
editions do not meet the requirements of this section.
(c) Containers designed, constructed, and tested prior to July 1, 1961,
according to the Code for Unfired Pressure Vessels for Petroleum Liquids
and Gases, 1951 edition with 1954 Addenda, of the American Petroleum
Institute and the American Society of Mechanical Engineers shall be
considered in conformance. Containers constructed according to API-ASME
Code do not have to comply with section I or with appendix to section
I. W-601 to W-606 inclusive in the 1943 and earlier editions do not
apply.
(4) Welding of containers.
(a) Welding to the shell, head, or any other part of the container
subject to internal pressure, shall be done in compliance with the code
under which the tank was fabricated. Other welding is permitted only
on saddle plates, lugs, or brackets attached to the container by the
tank manufacturer.
(b) Where repair or modification involving welding of DOT containers
is required, the container shall be returned to a qualified manufacturer
making containers of the same type, and the repair or modification made
in compliance with DOT regulations.
(5) Markings on container.
(a) Each container covered in subsection (3)(a) of this section except
as provided in subsection (2)(d) of this section shall be marked as
specified in the following:
(i) With a marking identifying compliance with, and other markings
required by, the rules of the reference under which the container
is constructed; or with the stamp and other markings required by the
laws, rules or regulations as administered by the state of Washington,
department of labor and industries pertaining to such containers.
(ii) With notation as to whether the container is designed for underground
or aboveground installation or both. If intended for both and different
style hoods are provided, the marking shall indicate the proper hood
for each type of installation.
(iii) With the name and address of the supplier of the container,
or with the trade name of the container.
(iv) With the water capacity of the container in pounds or gallons,
United States standard.
(v) With the pressure in p.s.i.g., for which the container is designed.
(vi) With the wording "This container shall not contain a product
having a vapor pressure in excess of-p.s.i.g. at 100°F," see
WAC
296-24-47509, Table H-31.
(vii) With the tare weight in pounds or other identified unit of
weight for containers with a water capacity of three hundred pounds
or less.
(viii) With marking indicating the maximum level to which the container
may be filled with liquid at temperatures between 20°F and 130°F,
except on containers provided with fixed maximum level indicators
or which are filled by weighing. Markings shall be increments of not
more than 20°F. This marking may be located on the liquid level gaging
device.
(ix) With the outside surface area in square feet.
(b) Markings specified shall be on a metal nameplate attached to the
container and located in such a manner as to remain visible after the
container is installed.
(c) When LP-gas and one or more other gases are stored or used in the
same area, the containers shall be marked to identify their content.
Marking shall be in compliance with American National Standard Z48.1-1954,
"Method of Marking Portable Compressed Gas Containers to Identify the
Material Contained."
(6) Location of containers and regulating equipment.
(a) Containers, and first stage regulating equipment if used, shall
be located outside of buildings, except under one or more of the following:
(i) In buildings used exclusively for container charging, vaporization
pressure reduction, gas mixing, gas manufacturing, or distribution.
(ii) When portable use is necessary and in accordance with WAC
296-24-47507(5).
(iii) LP-gas fueled stationary or portable engines in accordance
with WAC
296-24-47511 (11) or (12).
(iv) LP-gas fueled industrial trucks used in accordance with WAC
296-24-47511(13).
(v) LP-gas fueled vehicles garaged in accordance with WAC
296-24-47511(14).
(vi) Containers awaiting use or resale when stored in accordance
with WAC
296-24-47513.
(b) Each individual container shall be located with respect to the
nearest important building or group of buildings or line of adjoining
property which may be built on in accordance with Table H-23.
TABLE H-23
|
Minimum distances |
| Water
capacity
Per container |
Containers |
Between
above- ground containers |
| |
Under-ground |
Above-ground |
|
| Less
than 125 gals1* |
10
feet |
None |
None |
| 125
to 250 gallons |
10
feet |
10
feet |
None |
| 251
to 500 gallons |
10
feet |
10
feet |
3
feet |
| 501
to 2,000 gallons |
25
feet2* |
25
feet2* |
3
feet |
| 2,001
to 30,000 gallons
30,001
to 70,000 gallons
70,001
to 90,000 gallons |
50
feet
50
feet
50
feet |
50
feet
75
feet
100
feet |
5
feet 1/4 of sum of diameters
of adjacent containers. |
1If the aggregate water capacity of a multicontainer installation
at a consumer site is five hundred one gallons or greater, the minimum
distance shall comply with the appropriate portion of this table, applying
the aggregate capacity rather than the capacity per container. If more
than one installation is made, each installation shall be separated
from another installation by at least twenty-five feet. Do not apply
the MINIMUM DISTANCES BETWEEN ABOVE-GROUND CONTAINERS to such installations.
2Note The above distance requirements
may be reduced to not less than ten feet for a single container of one
thousand two hundred gallons water capacity or less, providing such
a container is at least twenty-five feet from any other LP-gas container
of more than one hundred twenty-five gallons water capacity.
(c) Containers installed for use shall not be stacked one above the
other.
(d) In industrial installations involving containers of one hundred
eighty thousand gallons aggregate water capacity or more, where serious
mutual exposures between the container and adjacent properties prevail,
firewalls or other means of special protection designed and constructed
in accordance with good engineering practices are required.
(e) In the case of buildings devoted exclusively to gas manufacturing
and distributing operations, the distances required by Table H-23
may be reduced provided that in no case shall containers of water
capacity exceeding five hundred gallons be located closer than ten
feet to such gas manufacturing and distributing buildings.
(f) Readily ignitable material such as weeds and long dry grass shall
be removed within ten feet of any container.
(g) The minimum separation between liquefied petroleum gas containers
and flammable liquid tanks shall be twenty feet, and the minimum separation
between a container and the centerline of the dike shall be ten feet.
The foregoing provision shall not apply when LP-gas containers of
one hundred twenty-five gallons or less capacity are installed adjacent
to Class III flammable liquid tanks of two hundred seventy-five gallons
or less capacity.
(h) Suitable means shall be taken to prevent the accumulation of
flammable liquids under adjacent liquefied petroleum gas containers,
such as by diking, diversion curbs, or grading.
(i) When dikes are used with flammable liquid tanks, no liquefied
petroleum gas containers shall be located within the diked area.
(7) Container valves and container accessories.
(a) Valves, fittings, and accessories connected directly to the container
including primary shutoff valves, shall have a rated working pressure
of at least 250 p.s.i.g. and shall be of material and design suitable
for LP-gas service. Cast iron shall not be used for container valves,
fittings, and accessories. This does not prohibit the use of container
valves made of malleable or nodular iron.
(b) Connections to containers, except safety relief connections, liquid
level gaging devices, and plugged openings, shall have shutoff valves
located as close to the container as practicable.
(c) Excess flow valves, where required shall close automatically at
the rated flows of vapor or liquid as specified by the manufacturer.
The connections or line including valves, fittings, etc., being protected
by an excess flow valve shall have a greater capacity than the rated
flow of the excess flow valve.
(d) Liquid level gaging devices which are so constructed that outward
flow of container contents shall not exceed that passed by a No. 54
drill size opening, need not be equipped with excess flow valves.
(e) Openings from container or through fittings attached directly on
container to which pressure gage connection is made, need not be equipped
with shutoff or excess flow valves if such openings are restricted to
not larger than No. 54 drill size opening.
(f) Except as provided in WAC
296-24-47507 (5)(a)(ii), excess flow and back pressure check
valves where required by this section shall be located inside
of the container or at a point outside where the line enters
the container; in the latter case, installation shall be made
in such manner that any undue strain beyond the excess flow
or back pressure check valve will not cause breakage between
the container and such valve.
(g) Excess flow valves shall be designed with a bypass, not to exceed
a No. 60 drill size opening to allow equalization of pressures.
(h) Containers of more than thirty gallons water capacity and less
than two thousand gallons water capacity, filled on a volumetric basis,
and manufactured after December 1, 1963, shall be equipped for filling
into the vapor space.
(8) Piping-Including pipe, tubing, and fittings.
(a) Pipe, except as provided in WAC
296-24-47511 (6)(a) shall be wrought iron or steel (black
or galvanized), brass, copper, or aluminum alloy. Aluminum alloy
pipe shall be at least Schedule 40 in accordance with the specifications
for Aluminum Alloy Pipe, American National Standards Institute
( ANSI) H38.7-1969 (ASTM, B241-1969), except that the use of
alloy 5456 is prohibited and shall be suitably marked at each
end of each length indicating compliance with American National
Standard Institute specifications. Aluminum alloy pipe shall
be protected against external corrosion when it is in contact
with dissimilar metals other than galvanized steel, or its location
is subject to repeated wetting by such liquids as water (except
rain water), detergents, sewage, or leaking from other piping,
or it passes through flooring, plaster, masonry, or insulation.
Galvanized sheet steel or pipe, galvanized inside and out, may
be considered suitable protection. The maximum nominal pipe
size for aluminum pipe shall be three-fourths inch and shall
not be used for pressures exceeding 20 p.s.i.g. Aluminum alloy
pipe shall not be installed within six inches of the ground.
(i) Vapor piping with operating pressures not exceeding 125 p.s.i.g.
shall be suitable for a working pressure of at least 125 p.s.i.g.
Pipe shall be at least Schedule 40 ASTM A-53-69, Grade B Electric
Resistance Welded and Electric Flash Welded Pipe or equal.
(ii) Vapor piping with operating pressures over 125 p.s.i.g. and
all liquid piping shall be suitable for a working pressure of at least
250 p.s.i.g. Pipe shall be at least Schedule 80 if joints are threaded
or threaded and back welded. At least Schedule 40 (ASTM A-53-1969
Grade B Electric Resistance Welded and Electric Flash Welded Pipe
or equal) shall be used if joints are welded, or welded and flanged.
(b) Tubing shall be seamless and of copper, brass, steel, or aluminum
alloy. Copper tubing shall be of Type K or L or equivalent as covered
in the Specification for Seamless Copper Water Tube, ANSI H23.1-1970
(ASTM B88-1969). Aluminum alloy tubing shall be of Type A or B or equivalent
as covered in Specification ASTM B210-1968 and shall be suitably marked
every eighteen inches indicating compliance with ASTM specifications.
The minimum nominal wall thickness of copper tubing and aluminum alloy
tubing shall be as specified in Table H-24 and Table H-25.
TABLE H-24
WALL THICKNESS
OF COPPER TUBING1
Note: The standard size
by which tube is designated is one-eighth-inch smaller than its nominal
outside diameter.
| Standard
size (inches) |
Nominal
O.D. (inches) |
Nominal
wall thickness (inches) |
| |
|
Type
K |
Type
L |
| 1/4 |
0.375 |
0.035 |
0.030 |
| 3/8 |
0.500 |
0.049 |
0.035 |
| 1/2 |
0.625 |
0.049 |
0.040 |
| 5/8 |
0.750 |
0.049 |
0.042 |
| 3/4 |
0.875 |
0.065 |
0.045 |
| 1 |
1.125 |
0.065 |
0.050 |
| 1
1/4 |
1.375 |
0.065 |
0.055 |
| 1
1/2 |
1.625 |
0.072 |
0.060 |
| 2 |
2.125 |
0.083 |
0.070 |
1Based on data in Specification for Seamless Copper Water
Tubing, ANSI H23.1-1970 (ASTM B-88-69).
TABLE H-25
WALL THICKNESS
OF ALUMINUM ALLOY TUBING1
| Outside
diameter (inches) |
Nominal wall thickness (inches) |
| |
Type
A |
Type
B |
| 3/8 |
0.035 |
0.049 |
| 1/2 |
0.035 |
0.049 |
| 5/8 |
0.042 |
0.049 |
| 3/4 |
0.049 |
0.058 |
1Based on data in Standard Specification for Alluminum-Alloy
Drawn Seamless Coiled Tubes for Special Purpose Applications, ASTM B210-68.
Aluminum alloy tubing shall be protected against external corrosion
when it is in contact with dissimilar metals other than galvanized steel,
or its location is subject to repeated wetting by liquids such as water
(except rainwater), detergents, sewage, or leakage from other piping,
or it passes through flooring, plaster, masonry, or insulation. Galvanized
sheet steel or pipe, galvanized inside and out, may be considered suitable
protection. The maximum outside diameter for aluminum alloy tubing shall
be three-fourths inch and shall not be used for pressures exceeding
20 p.s.i.g. Aluminum alloy tubing shall not be installed within six
inches of the ground.
(c) In systems where the gas in liquid form without pressure reduction
enters the building, only heavy walled seamless brass or copper tubing
with an internal diameter not greater than three thirty-seconds inch,
and a wall thickness of not less than three sixty-fourths inch shall
be used. This requirement shall not apply to research and experimental
laboratories, buildings, or separate fire divisions of buildings used
exclusively for housing internal combustion engines, and to commercial
gas plants or bulk stations where containers are charged, nor to industrial
vaporizer buildings, nor to buildings, structures, or equipment under
construction or undergoing major renovation.
(d) Pipe joints may be screwed, flanged, welded, soldered, or brazed
with a material having a melting point exceeding 1,000°F. Joints on
seamless copper, brass, steel, or aluminum alloy gas tubing shall be
made by means of approved gas tubing fittings, or soldered or brazed
with a material having a melting point exceeding 1,000°F.
(e) For operating pressures of 125 p.s.i.g. or less, fittings shall
be designed for a pressure of at least 125 p.s.i.g. For operating pressures
above 125 p.s.i.g., fittings shall be designed for a minimum of 250
p.s.i.g.
(f) The use of threaded cast iron pipe fittings such as ells, tees,
crosses, couplings, and unions is prohibited. Aluminum alloy fittings
shall be used with aluminum alloy pipe and tubing. Insulated fittings
shall be used where aluminum alloy pipe or tubing connects with a dissimilar
metal.
(g) Strainers, regulators, meters, compressors, pumps, etc., are not
to be considered as pipe fittings. This does not prohibit the use of
malleable, nodular, or higher strength gray iron for such equipment.
(h) All materials such as valve seats, packing, gaskets, diaphragms,
etc., shall be of such quality as to be resistant to the action of liquefied
petroleum gas under the service conditions to which they are subjected.
(i) All piping, tubing, or hose shall be tested after assembly and
proved free from leaks at not less than normal operating pressures.
After installation, piping and tubing of all domestic and commercial
systems shall be tested and proved free of leaks using a manometer or
equivalent device that will indicate a drop in pressure. Test shall
not be made with a flame.
(j) Provision shall be made to compensate for expansion, contraction,
jarring, and vibration, and for settling. This may be accomplished by
flexible connections.
(k) Piping outside buildings may be buried, above ground, or both,
but shall be well supported and protected against physical damage. Where
soil conditions warrant, all piping shall be protected against corrosion.
Where condensation may occur, the piping shall be pitched back to the
container, or suitable means shall be provided for revaporization of
the condensate.
(9) Hose specifications.
(a) Hose shall be fabricated of materials that are resistant to the
action of LP-gas in the liquid and vapor phases. If wire braid is used
for reinforcing the hose, it shall be of corrosion-resistant material
such as stainless steel.
(b) Hose subject to container pressure shall be marked "LP-gas" or
"LPG" at not greater than ten-foot intervals.
(c) Hose subject to container pressure shall be designed for a bursting
pressure of not less than 1,250 p.s.i.g.
(d) Hose subject to container pressure shall have its correctness as
to design construction and performance determined by being listed
(see WAC
296-24-47501(15)).
(e) Hose connections subject to container pressure shall be capable
of withstanding, without leakage, a test pressure of not less than 500
p.s.i.g.
(f) Hose and hose connections on the low-pressure side of the regulator
or reducing valve shall be designed for a bursting pressure of not less
than 125 p.s.i.g. or five times the set pressure of the relief devices
protecting that portion of the system, whichever is higher.
(g) Hose may be used on the low-pressure side of regulators to connect
to other than domestic and commercial gas appliances under the following
conditions:
(i) The appliances connected with hose shall be portable and need
a flexible connection.
(ii) For use inside buildings the hose shall be of minimum practical
length, but shall not exceed six feet except as provided in
WAC
296-24-47507 (5)(a)(vii) and shall not extend from one
room to another, nor pass through any walls, partitions, ceilings,
or floors. Such hose shall not be concealed from view or used
in a concealed location. For use outside of buildings, the
hose may exceed this length but shall be kept as short as
practical.
(iii) The hose shall be approved and shall not be used where it is
likely to be subjected to temperatures above 125°F. The hose shall
be securely connected to the appliance and the use of rubber slip
ends shall not be permitted.
(iv) The shutoff valve for an appliance connected by hose shall be
in the metal pipe or tubing and not at the appliance end of the hose.
When shutoff valves are installed close to each other, precautions
shall be taken to prevent operation of the wrong valve.
(v) Hose used for connecting to wall outlets shall be protected from
physical damage.
(10) Safety devices.
(a) Every container except those constructed in accordance with DOT
specifications and every vaporizer (except motor fuel vaporizers
and except vaporizers described in subsection (11)(b)(iii) of
this section and
WAC 296-24-47509 (4)(e)(i)) whether heated by artificial
means or not, shall be provided with one or more safety relief
valves of spring-loaded or equivalent type. These valves shall
be arranged to afford free vent to the outer air with discharge
not less than five feet horizontally away from any opening into
the building which is below such discharge. The rate of discharge
shall be in accordance with the requirements of (b) or (d) of
this subsection in the case of vaporizers.
(b) Minimum
required rate of discharge in cubic feet per minute of air at one hundred
twenty percent of the maximum permitted start to discharge pressure
for safety relief valves to be used on containers other than those constructed
in accordance with DOT specification shall be as follows:
|
Surface
area
(sq.
ft.) |
Flow
rate
CFM
air |
| 20 or less |
626 |
| 25 |
751 |
| 30 |
872 |
| 35 |
990 |
| 40 |
1,100 |
| 45 |
1,220 |
| 50 |
1,330 |
| 55 |
1,430 |
| 60 |
1,540 |
| 65 |
1,640 |
| 70 |
1,750 |
| 75 |
1,850 |
| 80 |
1,950 |
| 85 |
2,050 |
| 90 |
2,150 |
| 95 |
2,240 |
| 100 |
2,340 |
| 105 |
2,440 |
| 110 |
2,530 |
| 115 |
2,630 |
| 120 |
2,720 |
| 125 |
2,810 |
| 130 |
2,900 |
| 135 |
2,990 |
| 140 |
3,080 |
| 145 |
3,170 |
| 150 |
3,260 |
| 155 |
3,350 |
| 160 |
3,440 |
| 165 |
3,530 |
| 170 |
3,620 |
| 175 |
3,700 |
| 180 |
3,790 |
| 185 |
3,880 |
| 190 |
3,960 |
| 195 |
4,050 |
| 200 |
4,130 |
| 210 |
4,300 |
| 220 |
4,470 |
| 230 |
4,630 |
| 240 |
4,800 |
| 250 |
4,960 |
| 260 |
5,130 |
| 270 |
5,290 |
| 280 |
5,450 |
| 290 |
5,610 |
| 300 |
5,760 |
| 310 |
5,920 |
| 320 |
6,080 |
| 330 |
6,230 |
| 340 |
6,390 |
| 350 |
6,540 |
| 360 |
6,690 |
| 370 |
6,840 |
| 380 |
7,000 |
| 390 |
7,150 |
| 400 |
7,300 |
| 450 |
8,040 |
| 500 |
8,760 |
| 550 |
9,470 |
| 600 |
10,170 |
| 650 |
10,860 |
| 700 |
11,550 |
| 750 |
12,220 |
| 800 |
12,880 |
| 850 |
13,540 |
| 900 |
14,190 |
| 950 |
14,830 |
| 1,000 |
15,470 |
| 1,050 |
16,100 |
| 1,100 |
16,720 |
| 1,150 |
17,350 |
| 1,200 |
17,960 |
| 1,250 |
18,570 |
| 1,300 |
19,180 |
| 1,350 |
19,780 |
| 1,400 |
20,380 |
| 1,450 |
20,980 |
| 1,500 |
21,570 |
| 1,550 |
22,160 |
| 1,600 |
22,740 |
| 1,650 |
23,320 |
| 1,700 |
23,900 |
| 1,750 |
24,470 |
| 1,800 |
25,050 |
| 1,850 |
25,620 |
| 1,900 |
26,180 |
| 1,950 |
26,750 |
| 2,000 |
27,310 |
Surface area = total outside surface area of container in square
feet.
(c) When the surface area is
not stamped on the nameplate or when the marking is not legible, the
area can be calculated by using one of the following formulas:
(i) Cylindrical container with
hemispherical heads:
Area = Overall length x outside diameter x 3.1416.
(ii) Cylindrical container
with other than hemispherical heads:
Area = (Overall length + 0.3 outside diameter) x outside diameter
x 3.1416.
Note:
This formula is not exact, but will give results within the limits
of practical accuracy for the sole purpose of sizing relief valves.
(iii) Spherical container:
Area = Outside diameter squared x 3.1416.
Flow rate-CFM air = Required
flow capacity in cubic feet per minute of air at standard conditions,
60°F and atmospheric pressure (14.7 p.s.i.a.).
The rate of discharge may be
interpolated for intermediate values of surface area. For containers
with total outside surface area greater than two thousand square feet,
the required flow rate can be calculated using the formula, flow rate-CFM
air = 53.632 A0.82.
A = Total outside surface area
of the container in square feet.
Valves not marked "air" have
flow rate marking in cubic feet per minute of liquefied petroleum
gas. These can be converted to ratings in cubic feet per minute of
air by multiplying the liquefied petroleum gas ratings by factors
listed below. Air flow ratings can be converted to ratings in cubic
feet per minute of liquefied petroleum gas by dividing the air ratings
by the factors listed below.
AIR
CONVERSION FACTORS
| Container
type |
100
|
125
|
150
|
175
|
200
|
| Air
conversion factor |
1.162 |
1.142 |
1.113 |
1.078 |
1.010 |
(d) Minimum required rate of
discharge for safety relief valves for liquefied petroleum gas vaporizers
(steam heated, water heated, and direct fired).
The minimum required rate of
discharge for safety relief valves shall be determined as follows:
(i) Obtain the total surface area by adding the surface area of vaporizer
shell in square feet directly in contact with LPgas and the heat exchanged
surface area in square feet directly in contact with LP-gas.
(ii) Obtain the minimum required rate of discharge in cubic feet
of air per minute, at 60°F and 14.7 p.s.i.a. from (b) of this subsection,
for this total surface area.
(e) Container and vaporizer safety relief valves shall be set to start-to-discharge,
with relation to the design pressure of the container, in accordance
with Table H-26.
TABLE H-26
| Containers |
Minimum
(percent) |
Maximum
(percent) |
| ASME Code;
Par. U-68, U-69-1949
and earlier editions |
110 |
1125 |
| ASME Code;
Par. U-200,
U-201--1949 edition |
88 |
1100 |
| ASME Code-1950,
1952, 1956,
1959, 1962, 1965 and
1968 (Division I) editions |
88 |
1100 |
| API-ASME
Code-all editions |
88 |
1100 |
| DOT--As
prescribed in
49 CFR Chapter I |
______________ |
______________ |
1Manufacturers of safety relief valves are allowed a plus
tolerance not exceeding ten percent of the set pressure marked on the
valve.
(f) Safety relief devices used with systems employing containers other
than those constructed according to DOT specifications shall be so constructed
as to discharge at not less than the rates shown in (b) of this subsection,
before the pressure is in excess of one hundred twenty percent of the
maximum (not including the ten percent referred to in (e) of this subsection)
permitted start to discharge pressure setting of the device.
(g) In certain locations sufficiently sustained high temperatures prevail
which require the use of a lower vapor pressure product to be stored
or the use of a higher designed pressure vessel in order to prevent
the safety valves opening as the result of these temperatures. As an
alternative the tanks may be protected by cooling devices such as by
spraying, by shading, or other effective means.
(h) Safety relief valves shall be arranged so that the possibility
of tampering will be minimized. If pressure setting or adjustment is
external, the relief valves shall be provided with approved means for
sealing adjustment.
(i) Shutoff valves shall not be installed between the safety relief
devices and the container, or the equipment or piping to which the safety
relief device is connected except that a shutoff valve may be used where
the arrangement of this valve is such that full required capacity flow
through the safety relief device is always afforded.
(j) Safety relief valves shall have direct communication with the vapor
space of the container at all times.
(k) Each container safety relief valve used with systems covered
by WAC
296-24-47509, 296-24-47511,
and 296-24-47517,
except as provided in WAC
296-24-47511 (3)(c) shall be plainly and permanently marked
with the following: "Container type" of the pressure vessel
on which the valve is designed to be installed; the pressure
in p.s.i.g. at which the valve is set to discharge; the actual
rate of discharge of the valve in cubic feet per minute of air
at 60°F and 14.7 p.s.i.a.; and the manufacturer's name and catalog
number, for example: T200-250-4050 AIR-indicating that the valve
is suitable for use on a Type 200 container, that it is set
to start to discharge at 250 p.s.i.g.; and that its rate of
discharge is four thousand fifty cubic feet per minute of air
as determined in (b) of this subsection.
(l) Safety relief valve assemblies, including their connections, shall
be of sufficient size so as to provide the rate of flow required for
the container on which they are installed.
(m) A hydrostatic relief valve shall be installed between each pair
of shutoff valves on liquefied petroleum gas liquid piping so as to
relieve into a safe atmosphere. The start-to-discharge pressure setting
of such relief valves shall not be in excess of 500 p.s.i.g. The minimum
setting on relief valves installed in piping connected to other than
DOT containers shall not be lower than one hundred forty percent of
the container relief valve setting and in piping connected to DOT containers
not lower than 400 p.s.i.g. Such a relief valve should not be installed
in the pump discharge piping if the same protection can be provided
by installing the relief valve in the suction piping. The start-to-discharge
pressure setting of such a relief valve, if installed on the discharge
side of a pump, shall be greater than the maximum pressure permitted
by the recirculation device in the system.
(n) The discharge from any safety relief device shall not terminate
in or beneath any building, except relief devices covered by
subsection (6)(a)(i) through (vi) of this section, or WAC
296-24-47507 (4)(a) or (5).
(o) Container safety relief devices and regulator relief vents shall
be located not less than five feet in any direction from air openings
into sealed combustion system appliances or mechanical ventilation air
intakes.
(11) Vaporizer and housing.
(a) Indirect fired vaporizers utilizing steam, water, or other heating
medium shall be constructed and installed as follows:
(i) Vaporizers shall be constructed in accordance with the requirements
of subsection (3)(a) through (c) of this section and shall be permanently
marked as follows:
(A) With the code marking signifying the specifications to which
the vaporizer is constructed.
(B) With the allowable working pressure and temperature for which
the vaporizer is designed.
(C) With the sum of the outside surface area and the inside heat
exchange surface area expressed in square feet.
(D) With the name or symbol of the manufacturer.
(ii) Vaporizers having an inside diameter of six inches or less exempted
by the ASME Unfired Pressure Vessel Code, Section VIII of the ASME
Boiler and Pressure Vessel Code-1968 shall have a design pressure
not less than 250 p.s.i.g. and need not be permanently marked.
(iii) Heating or cooling coils shall not be installed inside a storage
container.
(iv) Vaporizers may be installed in buildings, rooms, sheds, or lean-tos
used exclusively for gas manufacturing or distribution, or in other
structures of light, noncombustible construction or equivalent, well
ventilated near the floor line and roof.
When vaporizing and/or mixing equipment is located in a structure
or building not used exclusively for gas manufacturing or distribution,
either attached to or within such a building, such structure or room
shall be separated from the remainder of the building by a wall designed
to withstand a static pressure of at least one hundred pounds per
square foot. This wall shall have no openings or pipe or conduit passing
through it. Such structure or room shall be provided with adequate
ventilation and shall have a roof or at least one exterior wall of
lightweight construction.
(v) Vaporizers shall have, at or near the discharge, a safety relief
valve providing an effective rate of discharge in accordance
with subsection (10)(d) of this section, except as provided
in WAC
296-24-47509 (4)(e)(i).
(vi) The heating medium lines into and leaving the vaporizer shall
be provided with suitable means for preventing the flow of gas into
the heat systems in the event of tube rupture in the vaporizer. Vaporizers
shall be provided with suitable automatic means to prevent liquid
passing through the vaporizers to the gas discharge piping.
(vii) The device that supplies the necessary heat for producing steam,
hot water, or other heating medium may be installed in a building,
compartment, room, or lean-to which shall be ventilated near the floorline
and roof to the outside. The device location shall be separated from
all compartments or rooms containing liquefied petroleum gas vaporizers,
pumps, and central gas mixing devices by a wall designed to withstand
a static pressure of at least one hundred pounds per square foot.
This wall shall have no openings or pipes or conduit passing through
it. This requirement does not apply to the domestic water heaters
which may supply heat for a vaporizer in a domestic system.
(viii) Gas-fired heating systems supplying heat exclusively for vaporization
purposes shall be equipped with automatic safety devices to shut off
the flow of gas to main burners, if the pilot light should fail.
(ix) Vaporizers may be an integral part of a fuel storage container
directly connected to the liquid section or gas section or both.
(x) Vaporizers shall not be equipped with fusible plugs.
(xi) Vaporizer houses shall not have unprotected drains to sewers
or sump pits.
(b) Atmospheric vaporizers employing heat from the ground or surrounding
air shall be installed as follows:
(i) Buried underground, or
(ii) Located inside the building close to a point at which pipe enters
the building provided the capacity of the unit does not exceed one
quart.
(iii) Vaporizers of less than one quart capacity heated by the ground
or surrounding air, need not be equipped with safety relief valves
provided that adequate tests demonstrate that the assembly is safe
without safety relief valves.
(c) Direct gas-fired vaporizers shall be constructed, marked, and installed
as follows:
(i) In accordance with the requirements of the American Society of
Mechanical Engineers Boiler and Pressure Vessel Code-1968 that are
applicable to the maximum working conditions for which the vaporizer
is designed.
(ii) With the name of the manufacturer; rated BTU input to the burner;
the area of the heat exchange surface in square feet; the outside
surface of the vaporizer in square feet; and the maximum vaporizing
capacity in gallons per hour.
(iii) Vaporizers may be connected to the liquid section or the gas
section of the storage container, or both; but in any case there shall
be at the container a manually operated valve in each connection to
permit completely shutting off when desired, of all flow of gas or
liquid from container to vaporizer.
(iv) Vaporizers with capacity not exceeding thirty-five gallons per
hour shall be located at least five feet from container shutoff valves.
Vaporizers having capacity of more than thirty-five gallons but not
exceeding one hundred gallons per hour shall be located at least ten
feet from the container shutoff valves. Vaporizers having a capacity
greater than one hundred gallons per hour shall be located at least
fifteen feet from container shutoff valves.
(v) Vaporizers may be installed in buildings, rooms, housings, sheds,
or lean-tos used exclusively for vaporizing or mixing of liquefied
petroleum gas. Vaporizing housing structures shall be of noncombustible
construction, well ventilated near the floorline and the highest point
of the roof. When vaporizer and/or mixing equipment is located in
a structure or room attached to or within a building, such structure
or room shall be separated from the remainder of the building by a
wall designed to withstand a static pressure of at least one hundred
pounds per square foot. This wall shall have no openings or pipes
or conduit passing through it. Such structure or room shall be provided
with adequate ventilation, and shall have a roof or at least one exterior
wall of lightweight construction.
(vi) Vaporizers shall have at or near the discharge, a safety relief
valve providing an effective rate of discharge in accordance with
subsection (10)(d) of this section. The relief valve shall be so located
as not to be subjected to temperatures in excess of 140°F.
(vii) Vaporizers shall be provided with suitable automatic means
to prevent liquid passing from the vaporizer to the gas discharge
piping of the vaporizer.
(viii) Vaporizers shall be provided with means for manually turning
off the gas to the main burner and pilot.
(ix) Vaporizers shall be equipped with automatic safety devices to
shut off the flow of gas to main burners if the pilot light should
fail. When the flow through the pilot exceeds 2,000 B.T.U. per hour,
the pilot also shall be equipped with an automatic safety device to
shut off the flow of gas to the pilot should the pilot flame be extinguished.
(x) Pressure regulating and pressure reducing equipment if located
within ten feet of a direct fired vaporizer shall be separated from
the open flame by a substantially airtight noncombustible partition
or partitions.
(xi) Except as provided in (c)(v) of this subsection, the following
minimum distances shall be maintained between direct fired vaporizers
and the nearest important building or group of buildings or line of
adjoining property which may be built upon:
(A) Ten feet for vaporizers having a capacity of fifteen gallons
per hour or less vaporizing capacity.
(B) Twenty-five feet for vaporizers having a vaporizing capacity
of sixteen to one hundred gallons per hour.
(C) Fifty feet for vaporizers having a vaporizing capacity exceeding
one hundred gallons per hour.
(xii) Direct fired vaporizers shall not raise the product pressure
above the design pressure of the vaporizer equipment nor shall
they raise the product pressure within the storage container
above the pressure shown in the second column of Table H-31.(See
WAC
296-24-47509.)
(xiii) Vaporizers shall not be provided with fusible plugs.
(xiv) Vaporizers shall not have unprotected drains to sewers or sump
pits.
(d) Direct gas-fired tank heaters, shall be constructed and installed
as follows:
(i) Direct gas-fired tank heaters, and tanks to which they are applied,
shall only be installed above ground.
(ii) Tank heaters shall be permanently marked with the name of the
manufacturer, the rated B.T.U. input to the burner, and the maximum
vaporizing capacity in gallons per hour.
Note: Tank heaters may be an integral part of a fuel storage container
directly connected to the container liquid section, or vapor section,
or both.
(iii) Tank heaters shall be provided with a means for manually turning
off the gas to the main burner and pilot.
(iv) Tank heaters shall be equipped with an automatic safety device
to shut off the flow of gas to main burners, if the pilot light should
fail. When flow through pilot exceeds 2,000 B.T.U. per hour, the pilot
also shall be equipped with an automatic safety device to shut off
the flow of gas to the pilot should the pilot flame be extinguished.
(v) Pressure regulating and pressure reducing equipment if located
within ten feet of a direct fired tank heater shall be separated from
the open flame by a substantially airtight noncombustible partition.
(vi) The following minimum distances shall be maintained between
a storage tank heated by a direct fired tank heater and the nearest
important building or group of buildings or line of adjoining property
which may be built upon:
(A) Ten feet for storage containers of less than five hundred gallons
water capacity.
(B) Twenty-five feet for storage containers of five hundred to
one thousand two hundred gallons water capacity.
(C) Fifty feet for storage containers of over one thousand two
hundred gallons water capacity.
(vii) No direct fired tank heater shall raise the product pressure
within the storage container over seventy-five percent of
the pressure set out in the second column of Table H-31.(See
WAC
296-24-47509.)
(e) The vaporizer section of vaporizer-burners used for dehydrators
or dryers shall be located outside of buildings; they shall be constructed
and installed as follows:
(i) Vaporizer-burners shall have a minimum design pressure of 250
p.s.i.g. with a factor of safety of five.
(ii) Manually operated positive shutoff valves shall be located at
the containers to shut off all flow to the vaporizer-burners.
(iii) Minimum distances between storage containers and vaporizer-burners
shall be as follows:
| Water
capacity per container (gallons) |
Minimum
distances (feet) |
| Less than
501 |
10 |
| 501 to
2,000 |
25 |
| Over 2,000 |
50 |
(iv) The vaporizer section of vaporizer-burners shall be protected
by a hydrostatic relief valve. The relief valve shall be located so
as not to be subjected to temperatures in excess of 140°F. The start-to-discharge
pressure setting shall be such as to protect the components involved,
but not less than 250 p.s.i.g. The discharge shall be directed upward
and away from component parts of the equipment and away from operating
personnel.
(v) Vaporizer-burners shall be provided with means for manually turning
off the gas to the main burner and pilot.
(vi) Vaporizer-burners shall be equipped with automatic safety devices
to shut off the flow of gas to the main burner and pilot in the event
the pilot is extinguished.
(vii) Pressure regulating and control equipment shall be located
or protected so that the temperatures surrounding this equipment shall
not exceed 140°F except that equipment components may be used at higher
temperatures if designed to withstand such temperatures.
(viii) Pressure regulating and control equipment when located downstream
of the vaporizer shall be designed to withstand the maximum discharge
temperature of the vapor.
(ix) The vaporizer section of vaporizer-burners shall not be provided
with fusible plugs.
(x) Vaporizer coils or jackets shall be made of ferrous metal or
high temperature alloys.
(xi) Equipment utilizing vaporizer-burners shall be equipped with
automatic shutoff devices upstream and downstream of the vaporizer
section connected so as to operate in the event of excessive temperature,
flame failure, and, if applicable, insufficient airflow.
(12) Filling densities.
(a) The "filling density" is defined as the percent ratio of the weight
of the gas in a container to the weight of water the container will
hold at 60°F. All containers shall be filled according to the filling
densities shown in Table H-27.
TABLE H-27
MAXIMUM PERMITTED
FILLING DENSITY
Above ground
containers
| Specific
gravity at 60°F (15.6°C) |
0 to
1,200 U.S. gals. (1,000 imp. Gals. 4,550 (liters) total water
cap. |
Over
1,200 U.S. gals. (1,000 imp. gals. 4,550 (liters) total water
cap. |
Underground
containers, All capacities |
| |
Percent |
Percent |
Percent |
| 0.496-0.503 |
41 |
44 |
45 |
| .504-.510 |
42 |
45 |
46 |
| .511-.519 |
43 |
46 |
47 |
| .520-.527 |
44 |
47 |
48 |
| .528-.536 |
45 |
48 |
49 |
| .537-.544 |
46 |
49 |
50 |
| .545-.552 |
47 |
50 |
51 |
| .553-.560 |
48 |
51 |
52 |
| .561-.568 |
49 |
52 |
53 |
| .569-.576 |
50 |
53 |
54 |
| .577-.584 |
51 |
54 |
55 |
| .585-.592 |
52 |
55 |
56 |
| .593-.600 |
53 |
56 |
57 |
(b) Except as provided in (c) of this subsection, any container including
mobile cargo tanks and portable tank containers regardless of size or
construction, shipped under DOT jurisdiction or constructed in accordance
with 49 CFR Chapter I specifications shall be charged according to 49
CFR Chapter I requirements.
(c) Portable containers not subject to DOT jurisdiction (such as, but
not limited to, motor fuel containers on industrial and lift trucks,
and farm tractors covered in subsection (5) of this section, or containers
recharged at the installation) may be filled either by weight, or by
volume using a fixed length dip tube gaging device.
(13) LP-gas in buildings.
(a) Vapor shall be piped into buildings at pressures in excess of 20
p.s.i.g. only if the buildings or separate areas thereof,
(i) Are constructed in accordance with this section;
(ii) Are used exclusively to house equipment for vaporization, pressure
reduction, gas mixing, gas manufacturing, or distribution, or to house
internal combustion engines, industrial processes, research and experimental
laboratories, or equipment and processes using such gas and having
similar hazard;
(iii) Buildings, structures, or equipment under construction or undergoing
major renovation.
(b) Liquid may be permitted in buildings as follows:
(i) Buildings, or separate areas of buildings, used exclusively to
house equipment for vaporization, pressure reduction, gas mixing,
gas manufacturing, or distribution, or to house internal combustion
engines, industrial processes, research and experimental laboratories,
or equipment and processes using such gas and having similar hazard;
and when such buildings, or separate areas thereof are constructed
in accordance with this section.
(ii) Buildings, structures, or equipment under construction or undergoing
major renovation provided the temporary piping meets the following
conditions:
(A) Liquid piping inside the building shall conform to the requirements
of subsection (8) of this section, and shall not exceed
three-fourths iron pipe size. Copper tubing with an outside
diameter of three-fourths inch or less may be used provided
it conforms to Type K of Specifications for Seamless Water
Tube, ANSI H23.1-1970 (ASTM B88-1969) (see WAC
296-24-47505 Table H-24).All such piping shall be protected
against construction hazards. Liquid piping inside buildings
shall be kept to a minimum. Such piping shall be securely
fastened to walls or other surfaces so as to provide adequate
protection from breakage and so located as to subject the
liquid line to lowest ambient temperatures.
(B) A shutoff valve shall be installed in each intermediate branch
line where it takes off the main line and shall be readily accessible.
A shutoff valve shall also be placed at the appliance end of the
intermediate branch line. Such shutoff valve shall be upstream of
any flexible connector used with the appliance.
(C) Suitable excess flow valves shall be installed in the container
outlet line supplying liquid LP-gas to the building. A suitable
excess flow valve shall be installed immediately downstream of each
shutoff valve. Suitable excess flow valves shall be installed where
piping size is reduced and shall be sized for the reduced size piping.
(D) Hydrostatic relief valves shall be installed in accordance
with subsection (10)(m) of this section.
(E) The use of hose to carry liquid between the container and the
building or at any point in the liquid line, except at the appliance
connector, shall be prohibited.
(F) Where flexible connectors are necessary for appliance installation,
such connectors shall be as short as practicable and shall comply
with subsection (8)(b) or (9) of this section.
(G) Release of fuel when any section of piping or appliances is
disconnected shall be minimized by either of the following
methods:
(I) Using an approved automatic quick-closing coupling (a type
closing in both directions when coupled in the fuel line), or
(II) Closing the valve nearest to the appliance and allowing
the appliance to operate until the fuel in the line is consumed.
(III) Portable containers shall not be taken into buildings except
as provided in subsection (6)(a) of this section.
(14) Transfer of liquids. The employer shall assure that:
(a) At least one attendant shall remain close to the transfer connection
from the time the connections are first made until they are finally
disconnected, during the transfer of the product.
(b) Containers shall be filled or used only upon authorization of the
owner.
(c) Containers manufactured in accordance with specifications of 49
CFR Part 178 and authorized by 49 CFR Chapter 1 as a "single trip" or
"nonrefillable container" shall not be refilled or reused in LP-gas
service.
(d) Gas or liquid shall not be vented to the atmosphere to assist in
transferring contents of one container to another, except as
provided in WAC
296-24-47511 (5)(d) and except that this shall not preclude
the use of listed pump utilizing LP-gas in the vapor phase as
a source of energy and venting such gas to the atmosphere at
a rate not to exceed that from a No. 31 drill size opening and
provided that such venting and liquid transfer shall be located
not less than fifty feet from the nearest important building.
(e) Filling of fuel containers for industrial trucks or motor vehicles
from industrial bulk storage containers shall be performed not less
than ten feet from the nearest important masonry-walled building or
not less than twenty-five feet from the nearest important building or
other construction and, in any event, not less than twenty-five feet
from any building opening.
(f) Filling of portable containers, containers mounted on skids, fuel
containers on farm tractors, or similar applications, from storage containers
used in domestic or commercial service, shall be performed not less
than fifty feet from the nearest important building.
(g) The filling connection and the vent from the liquid level gages
in containers, filled at point of installation, shall not be less than
ten feet in any direction from air openings into sealed combustion system
appliances or mechanical ventilation air intakes.
(h) Fuel supply containers shall be gaged and charged only in the open
air or in buildings especially provided for that purpose.
(i) The maximum vapor pressure of the product at 100°F which
may be transferred into a container shall be in accordance with
WAC
296-24-47509(2) and 296-24-47511(3).
(For DOT containers use DOT requirements.)
(j) Marketers and users shall exercise precaution to assure that only
those gases for which the system is designed, examined, and listed,
are employed in its operation, particularly with regard to pressures.
(k) Pumps or compressors shall be designed for use with LP-gas. When
compressors are used they shall normally take suction from the vapor
space of the container being filled and discharge to the vapor space
of the container being emptied.
(l) Pumping systems, when equipped with a positive displacement pump,
shall include a recirculating device which shall limit the differential
pressure on the pump under normal operating conditions to the maximum
differential pressure rating of the pump. The discharge of the pumping
system shall be protected so that pressure does not exceed 350 p.s.i.g.
If a recirculation system discharges into the supply tank and contains
a manual shutoff valve, an adequate secondary safety recirculation system
shall be incorporated which shall have no means of rendering it inoperative.
Manual shutoff valves in recirculation systems shall be kept open except
during an emergency or when repairs are being made to the system.
(m) When necessary, unloading piping or hoses shall be provided with
suitable bleeder valves for relieving pressure before disconnection.
(n) Agricultural air moving equipment, including crop dryers, shall
be shut down when supply containers are being filled unless the air
intakes and sources of ignition on the equipment are located fifty feet
or more from the container.
(o) Agricultural equipment employing open flames or equipment with
integral containers, such as flame cultivators, weed burners, and, in
addition, tractors, shall be shut down during refueling.
(15) Tank car or transport truck loading or unloading points and operations.
(a) The track of tank car siding shall be relatively level.
(b) A "tank car connected" sign, as covered by DOT rules, shall be
installed at the active end or ends of the siding while the tank car
is connected.
(c) While cars are on side track for loading or unloading, the wheels
at both ends shall be blocked on the rails.
(d) The employer shall insure that an employee is in attendance at
all times while the tank car, cars, or trucks are being loaded or unloaded.
(e) A backflow check valve, excess-flow valve, or a shutoff valve with
means of remote closing, to protect against uncontrolled discharge of
LP-gas from storage tank piping shall be installed close to the point
where the liquid piping and hose or swing joint pipe is connected.
(f) Where practical, the distance of the unloading or loading point
shall conform to the distances in subsection (6)(b) of this section.
(16) Instructions. Personnel performing installation, removal, operation,
and maintenance work shall be properly trained in such function.
(17) Electrical equipment and other sources of ignition.
(a) Electrical equipment and wiring shall be of a type specified by
and shall be installed according to chapter
296-24 WAC Part L, for ordinary locations except that fixed
electrical equipment in classified areas shall comply with subsection
(18) of this section.
(b) Open flames or other sources of ignition shall not be permitted
in vaporizer rooms (except those housing direct-fired vaporizers), pumphouses,
container charging rooms or other similar locations. Direct-fired vaporizers
shall not be permitted in pumphouses or container charging rooms.
Note: Liquefied petroleum gas storage containers
do not require lightning protection. Since liquefied petroleum gas is
contained in a closed system of piping and equipment, the system need
not be electrically conductive or electrically bonded for protection
against static electricity (see NFPA No. 77-1972-1973, Recommended Practice
for Static Electricity).
(c) Open flames (except as provided for in (b) of this subsection),
cutting or welding, portable electric tools, and extension lights capable
of igniting LP-gas, shall not be permitted within classified areas specified
in Table H-28 of this section unless the LP-gas facilities have been
freed of all liquid and vapor, or special precautions observed under
carefully controlled conditions.
(18) Fixed electrical equipment in classified areas. Fixed electrical
equipment and wiring installed within classified areas shall comply
with Table H-28 of this section and shall be installed according
to
chapter 296-24 WAC Part L. This provision does not apply to
fixed electrical equipment at residential or commercial installations
of LP-gas systems or to systems covered by WAC
296-24-47511.
(19) Liquid-level gaging device.
(a) Each container manufactured after December 31, 1965, and filled
on a volumetric basis shall be equipped with a fixed liquid-level gage
to indicate the maximum permitted filling level as provided in (e) of
this subsection. Each container manufactured after December 31, 1969,
shall have permanently attached to the container adjacent to the fixed
level gage a marking showing the percentage full that will be shown
by that gage. When a variable liquid-level gage is also provided, the
fixed liquid-level gage will also serve as a means for checking the
variable gage. These gages shall be used in charging containers as required
in subsection (12) of this section.
(b) All variable gaging devices shall be arranged so that the maximum
liquid level for butane, for a fifty-fifty mixture of butane and propane,
and for propane, to which the container may be charged is readily determinable.
The markings indicating the various liquid levels from empty to full
shall be on the system nameplate or gaging device or part may be on
the system nameplate and part on the gaging device. Dials of magnetic
or rotary gages shall show whether they are for cylindrical or spherical
containers and whether for aboveground or underground service. The dials
of gages intended for use only on aboveground containers of over one
thousand two hundred gallons water capacity shall be so marked.
(c) Gaging devices that require bleeding of the product to the atmosphere,
such as the rotary tube, fixed tube, and slip tube, shall be designed
so that the bleed valve maximum opening is not larger than a No. 54
drill size, unless provided with excess flow valve.
(d) Gaging devices shall have a design working pressure of at least
250 p.s.i.g.
(e) Length of tube or position of fixed liquid-level gage shall be
designed to indicate the maximum level to which the container may be
filled for the product contained. This level shall be based on the volume
of the product at 40°F at its maximum permitted filling density for
aboveground containers and at 50°F for underground containers. The employer
shall calculate the filling point for which the fixed liquid level gage
shall be designed according to the method in this subsection.
TABLE H-28-1
|
Part |
Location |
Extent of classified area1 |
Equipment shall be
suitable for
Class I Group D2 |
|
A |
Storage containers other than DOT cylinders |
Within 15 feet in all directions from connections, except connections
otherwise covered in Table H-28 |
Division 2 |
|
B |
Tank vehicle and tank car loading and unloading3 |
Within 5 feet in all directions from connections regularly
made or disconnected for product transfer |
Division 2 |
| |
|
Beyond 5 feet but within 15 feet in all directions from a point
where connections are regularly made or disconnected and within
the cylindrical volume between the horizontal equator of the
sphere and grade. (See Figure H-1) |
Division 2 |
|
C |
Gage vent openings other than those on DOT cylinders. |
Within 5 feet in all directions from point of discharge |
Division 1 |
| |
|
Within 5 feet but within 15 feet in all directions from point
of discharge |
Division 2 |
|
D |
Relief valve discharge other than those on DOT cylinders |
Within direct path of discharge |
Division 1. NOTE--Fixed electrical equipment should preferably
not be installed. |
| |
|
Within 5 feet in all directions from point of discharge |
Division 1 |
| |
|
Beyond 5 feet but within 15 feet in all directions from point
of discharge except within the direct path of discharge. |
Division 2 |
|
E |
Pumps, compressors, gas-air mixers and vaporizers other than
direct fired |
_____________________ |
_____________________ |
|
Indoor without ventilation |
Entire room and any adjacent room not separated by a gastight
partition |
Division 1 |
|
|
Within 15 feet of the exterior side of any exterior wall or
roof that is not vaportight or within 15 feet of any exterior
opening |
Division 2 |
|
Indoor with adequate ventilation4 |
Entire room and any adjacent room not separated by a gastight
partition |
Division 2 |
|
Outdoors in open air at or above grade |
Within 15 feet in all directions from this equipment and within
the cylindrical volume between the horizontal equator of the
sphere and grade. (See Figure H-1.) |
Division 2 |
|
F |
Service station dispensing units |
Entire space within dispenser enclosure, and 18 inches horizontally
from enclosure exterior up to an elevation 4 ft. above dispenser
base. Entire pit or open space beneath dispenser. |
Division 1 |
|
|
Up to 18 inches above grade within 20 ft. horizontally from
any edge of enclosure. |
Division 2 |
|
|
Note: For pits within this area, see Part F of this table. |
|
|
G |
Pits or trenches containing or located beneath LP-gas valves,
pumps, compressors, regulators, an similar equipment |
_____________________ |
_____________________ |
|
Without mechanical ventilation |
Entire pit or trench |
Division 1 |
| |
|
Entire room and any adjacent room not separated by a gastight
partition |
Division 2 |
| |
|
Within 15 feet in all directions from pit or trench when located
outdoors |
Division 2 |
| |
With adequate mechanical ventilation |
Entire pit or trench |
Division 1 |
| |
|
Entire room and any adjacent room not separated by a gastight
partition |
Division 2 |
| |
|
Within 15 feet in all directions from pit or trench when located
outdoors |
Division 2 |
|
H |
Special buildings or rooms for storage of portable containers |
Entire room |
Division 2 |
|
I |
Pipelines and connections containing operational bleeds, drips,.
Vents or drains |
Within 5 ft. in all directions from point of discharge |
Division 1 |
| |
|
Beyond 5 ft from point of discharge, same as Part E of this
table |
|
|
J |
Container filling: Indoors without ventilation |
Entire room |
Division 1 |
| |
Indoors with adequate ventilation.4 regularly made of disconnected
for product transfer. |
Within 5 feet in all directions from connections |
Division 1 |
| |
|
Beyond 5 feet and entire room |
Division 2 |
| |
Outdoors in open air from connections regularly made or disconnected
for product transfer |
Within 5 feet in all directions |
Division 1 |
| |
|
Beyond 5 feet but within 15 feet in all directions from a point
where connections are regularly made or disconnected and within
the cylindrical volume between the horizontal equator of the
sphere and grade. (See Figure H-1). |
Division 2 |
1 The classified area shall not extend beyond
an unpierced wall, roof, or solid vaportight partition.
2 See chapter
296-45 WAC, and chapter
296-24 WAC Part L.
3 When classifying extent of hazardous area,
consideration shall be given to possible variations in the spotting
of tank cars and tank vehicles at the unloading points and the effect
these variations of actual spotting point may have on the point of connection.
4 Ventilation, either natural or mechanical,
is considered adequate when the concentration of the gas in a gas-air
mixture does not exceed twenty-five percent of the lower flammable limit
under normal operating conditions.

Figure H-1
Note: It is impossible to set out in a table
the length of a fixed dip tube for various capacity tanks because
of the varying tank diameters and lengths and because the tank may
be installed either in a vertical or horizontal position. Knowing
the maximum permitted filling volume in gallons, however, the length
of the fixed tube can be determined by the use of a strapping table
obtained from the container manufacturer. The length of the fixed
tube should be such that when its lower end touches the surface of
the liquid in the container, the contents of the container will be
the maximum permitted volume as determined by the following formula:
Water capacity (gals.)
of container* x filling
density**
Maximum
__________________
= volume
Specific gravity of
of LP-gas
LP-gas* volume
correction factor***
x 100
* Measure at 60°F.
** From subsection (12)(a) of this section "filling densities."
*** For aboveground containers the liquid temperature is assumed
to be 40°F and for underground containers the liquid temperature
is assumed to be 50°F. To correct the liquid volumes at these temperatures
to 60°F the following factors shall be used.
(i) Formula for determining maximum volume of liquefied petroleum
gas for which a fixed length of dip tube shall be set:
TABLE H-29
VOLUME CORRECTION
FACTORS
| Specific
gravity |
Aboveground |
Underground |
| 0.500
.510
.520
.530
.540
.550
.560
.570
.580
.590 |
1.033
1.031
1.029
1.028
1.026
1.025
1.024
1.023
1.021
1.020 |
1.017
1.016
1.015
1.014
1.013
1.013
1.012
1.011
1.011
1.010 |
(ii) The maximum volume of LP-gas which can be placed in a container
when determining the length of the dip tube expressed as a percentage
of total water content of the container is calculated by the following
formula.
(iii) The maximum weight of LP-gas which may be placed in a container
for determining the length of a fixed dip tube is determined by multiplying
the maximum volume of liquefied petroleum gas obtained by the formula
in (e)(i) of this subsection by the pounds of liquefied petroleum
gas in a gallon at 40°F for aboveground and at 50°F for underground
containers. For example, typical pounds per gallon are specified below:
Example: Assume a one hundred-gallon total water capacity tank for
aboveground storage of propane having a specific gravity of 0.510 of
60°F.
100 (gals.) x 42 (filling
density
from (12)(a) of this
subsection) 4200
___________________________
=
0.510 x 1.031 (correction
factor
52.6
from Table H-29) x
100
79.8
gallons propane, the maximum
4200
amount permitted to be placed in a
100-gallon total water capacity
52.6
aboveground container equipped
with a fixed dip tube.
Maximum volume of
LP-gas (from formula
in (e)(I) of
this subsection) x 100
Maximum
_________________ =
percent
Total water content
of container in
gallons.
| |
Aboveground,
pounds per gallon |
Underground,
pounds per gallon |
| Propane
N Butane |
4.37
4.97 |
4.31
4.92 |
(f) Fixed liquid-level gages used on containers other than DOT containers
shall be stamped on the exterior of the gage with the letters "DT" followed
by the vertical distance (expressed in inches and carried out to one
decimal place) from the top of container to the end of the dip tube
or to the centerline of the gage when it is located at the maximum permitted
filling level. For portable containers that may be filled in the horizontal
and/or vertical position the letters "DT" shall be followed by "V" with
the vertical distance from the top of the container to the end of the
dip tube for vertical filling and with "H" followed by the proper distance
for horizontal filling. For DOT containers the stamping shall be placed
both on the exterior of the gage and on the container. On aboveground
or cargo containers where the gages are positioned at specific levels,
the marking may be specified in percent of total tank contents and the
marking shall be stamped on the container.
(g) Gage glasses of the columnar type shall be restricted to charging
plants where the fuel is withdrawn in the liquid phase only. They shall
be equipped with valves having metallic handwheels, with excess flow
valves, and with extra-heavy glass adequately protected with a metal
housing applied by the gage manufacturer. They shall be shielded against
the direct rays of the sun. Gage glasses of the columnar type are prohibited
on tank trucks, and on motor fuel tanks, and on containers used in domestic,
commercial, and industrial installations.
(h) Gaging devices of the float, or equivalent type which do not require
flow for their operation and having connections extending to a point
outside the container do not have to be equipped with excess flow valves
provided the piping and fittings are adequately designed to withstand
the container pressure and are properly protected against physical damage
and breakage.
(20) Requirements for appliances.
(a) Except as provided in (b) of this subsection, new commercial and
industrial gas consuming appliances shall be approved.
(b) Any appliance that was originally manufactured for operation with
a gaseous fuel other than LP-gas and is in good condition may be used
with LP-gas only after it is properly converted, adapted, and tested
for performance with LP-gas before the appliance is placed in use.
(c) Unattended heaters used inside buildings for the purpose of animal
or poultry production or care shall be equipped with an approved automatic
device designed to shut off the flow of gas to the main burners, and
pilot if used, in the event of flame extinguishment.
(d) All commercial, industrial, and agricultural appliances or equipment
shall be installed in accordance with the requirements of these standards
and in accordance with the following:
(i) Domestic and commercial appliances-NFPA 54-1969, Standard for
the Installation of Gas Appliances and Gas Piping.
(ii) Industrial appliances-NFPA 54A-1969, Standard for the Installation
of Gas Piping and Gas Equipment on Industrial Premises and Certain
Other Premises.
(iii) Standard for the Installation and Use of Stationary Combustion
Engines and Gas Turbines-NFPA 37-1970.
(iv) Standard for the Installation of Equipment for the Removal of
Smoke and Grease-Laden Vapors from Commercial Cooking Equipment, NFPA
96-1970.
[Statutory Authority RCW 49.17.010, .040,
.050. 99-17-094 (Order 99-01), § 296-24-47505, filed 08/17/99, effective
12/01/99. Statutory Authority: Chapter 49.17 RCW. 91-24-017 (Order 91-07),
§ 296-24-47505, filed 11/22/91, effective 12/24/91; 88-23-054 (Order 88-25),
§ 296-24-47505, filed 11/14/88. Statutory Authority: RCW 49.17.040 and
49.17.050. 85-10-004 (Order 85-09), § 296-24-47505, filed 4/19/85; Order
76-6, § 296-24-47505, filed 3/1/76; Order 73-5, § 296-24-47505, filed
5/9/73 and Order 73-4, § 296-24-47505, filed 5/7/73.]
WAC
296-24 Part F-1 Continued
|