General Safety & Health Standards |
|
Fire
Suppression Equipment
Chapter 296-24 WAC, Part G-3 |
|
WAC
296-24-592
Portable Fire Extinguishers.
296-24-59201
Scope and application.
296-24-59212
Hydrostatic testing.
296-24-59215
Appendix A--Portable fire extinguishers.
296-24-602
Standpipe and hose systems.
296-24-60201
Scope and application.
296-24-60203
Protection of standpipes.
296-24-60205
Equipment.
296-24-60207
Water supply.
296-24-60209
Tests and maintenance.
296-24-60299
Appendix A--Standpipe and hose systems.
296-24-607
Automatic sprinkler systems.
296-24-60701
Scope and application.
296-24-60703
Exemptions.
296-24-60705
General requirements.
296-24-60799
Appendix A--Automatic sprinkler systems.
296-24-617
Fixed extinguishing systems, general.
296-24-61701
Scope and application.
296-24-61703
General requirements.
296-24-61705
Total flooding systems with potential health and safety hazards
to employees.
296-24-61799
Appendix A--Fixed extinguishing systems, general.
296-24-622
Fixed extinguishing systems, dry chemical.
296-24-62201
Scope and application.
296-24-62203
Specific requirements.
296-24-62299
Appendix A--Fixed extinguishing systems, dry chemical.
296-24-623
Fixed extinguishing systems, gaseous agent.
296-24-62301
Scope and application.
296-24-62303
Specific requirements.
296-24-62399
Appendix A--Fixed extinguishing systems, gaseous agent.
296-24-627
Fixed extinguishing systems, water spray and foam.
296-24-62701
Scope and application.
296-24-62703
Specific requirements.
296-24-62799
Appendix A--Fixed extinguishing systems, water spray and foam.
296-24-629
Fire detection systems.
296-24-62901
Scope and application.
296-24-62903
Installation and restoration.
296-24-62905
Maintenance and testing.
296-24-62907
Protection of fire detectors.
296-24-62909
Response time.
296-24-62911
Number, location and spacing of detecting devices.
296-24-62999
Appendix A--Fire detection systems.
296-24-63299
Appendix B--National consensus standards.
296-24-63399
Appendix C--Fire protection references for further information.
296-24-63499
Appendix D--Availability of publications incorporated by references
in
WAC 296-24-58505--Fire brigades.
296-24-63599
Appendix E--Test methods for protective clothing.
WAC
296-24-592 Portable fire extinguishers.
All sections of this chapter which include WAC
296-24-592 in the section number apply to portable fire extinguishers.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-592, filed 12/24/81.]
WAC
296-24-59201 Scope and application.
The requirements of this section apply to the hydrostatic testing
of portable fire extinguishers provided for the use of employees.
[Statutory Authority: RCW 49.17.010,
.040, .050. 01-11-038 (Order 99-36), § 296-24-59201, filed 05/09/01,
effective 09/01/01. Statutory Authority: RCW 49.17.040 and 49.17.050.
82-02-003 (Order 81-32), § 296-24-59201, filed 12/24/81.]
WAC
296-24-59212 Hydrostatic testing.
(1) In addition to an external visual examination, the employer
shall assure that an internal examination of cylinders and shells
to be tested is made prior to the hydrostatic tests.
(2) The employer shall ensure that portable fire extinguishers
are hydrostatically tested whenever they show new evidence of corrosion
or mechanical injury.
(3) The employer shall assure that hydrostatic tests are performed
on extinguisher hose assemblies which are equipped with a shut-off
nozzle at the discharge end of the hose. The test interval shall
be the same as specified for the extinguisher on which the hose
is installed.
(4) The employer shall assure that carbon dioxide hose assemblies
with a shut-off nozzle are hydrostatically tested at 1,250 psi (8,620
kPa).
(5) The employer shall assure that dry chemical and dry powder
hose assemblies with a shut-off nozzle are hydrostatically tested
at 300 psi (2,070 kPa).
(6) Hose assemblies passing a hydrostatic test do not require any
type of recording or stamping.
(7) The employer shall assure that hose assemblies for carbon dioxide
extinguishers that require a hydrostatic test are tested within
a protective cage device.
(8) The employer shall assure that carbon dioxide extinguishers
and nitrogen or carbon dioxide cylinders used with wheeled extinguishers
are tested every five years at 5/3 of the service pressure as stamped
into the cylinder. Nitrogen cylinders which comply with 29 CFR 173.34(e)(15)
may be hydrostatically tested every ten years.
(9) The employer shall assure that all stored pressure and Halon
1211 types of extinguishers are hydrostatically tested at the factory
test pressure not to exceed two times the service pressure.
(10) The employer shall assure that acceptable self-generating
type soda acid and foam extinguishers are tested at 350 psi (2,410
kPa).
(11) Air or gas pressure may not be used for hydrostatic testing.
(12) Extinguisher shells, cylinders, or cartridges which fail a
hydrostatic pressure test, or which are not fit for testing shall
be removed from service and from the workplace.
(13) (a) The equipment for testing compressed gas type cylinders
shall be of the water-jacket type. The equipment shall be provided
with an expansion indicator which operates with an accuracy within
one percent of the total expansion or 0.1 cc (.1mL) of liquid.
(b) The equipment for testing noncompressed gas type cylinders
shall consist of the following:
(i) A hydrostatic test pump, hand or power operated, capable
of producing not less than one hundred fifty percent of the
test pressure, which shall include appropriate check valves
and fittings;
(ii) A flexible connection for attachment to fittings to test
through the extinguisher nozzle, test bonnet, or hose outlet,
as is applicable; and
(iii) A protective cage or barrier for personal protection
of the tester, designed to provide visual observation of the
extinguisher under test.
[Statutory Authority: RCW 49.17.010,
.040, .050. 01-11-038 (Order 99-36), § 296-24-59212, filed 05/09/01,
effective 09/01/01.]
WAC
296-24-59215 Appendix A-Portable fire extinguishers.
(1) Scope and application. The scope and application of this section
is written to apply to three basic types of workplaces. First,
there are those workplaces where the employer has chosen to evacuate
all employees from the workplace at the time of a fire emergency.
Second, there are those workplaces where the employer has chosen
to permit certain employees to fight fires and to evacuate all
other nonessential employees at the time of a fire emergency.
Third, there are those workplaces where the employer has chosen
to permit all employees in the workplace to use portable fire
extinguishers to fight fires.
The section also addresses two kinds of work areas. The entire
workplace can be divided into outside (exterior) work areas and
inside (interior) work areas. This division of the workplace into
two areas is done in recognition of the different types of hazards
employees may be exposed to during fire fighting operations. Fires
in interior workplaces, pose a greater hazard to employees; they
can produce greater exposure to quantities of smoke, toxic gases,
and heat because of the capability of a building or structure
to contain or entrap these products of combustion until the building
can be ventilated. Exterior work areas, normally open to the environment,
are somewhat less hazardous, because the products of combustion
are generally carried away by the thermal column of the fire.
Employees also have a greater selection of evacuation routes if
it is necessary to abandon fire fighting efforts.
In recognition of the degree of hazard present in the two types
of work areas, the standards for exterior work areas are somewhat
less restrictive in regards to extinguisher distribution. WAC
296-800-300 explains this by specifying which sections apply.
(2) Portable fire extinguisher exemptions. In recognition of the
three options given to employers in regard to the amount of employee
evacuation to be carried out, the standards permit certain exemptions
based on the number of employees expected to use fire extinguishers.
Where the employer has chosen to totally evacuate the workplace
at the time of a fire emergency and when fire extinguishers are
not provided, the requirements of this section do not apply to that
workplace.
Where the employer has chosen to partially evacuate the workplace
or the effected area at the time of a fire emergency and has permitted
certain designated employees to remain behind to operate critical
plant operations or to fight fires with extinguishers, then the
employer is exempt from the distribution requirements of this section.
Employees who will be remaining behind to perform incipient fire
fighting or members of a fire brigade must be trained in their duties.
The training must result in the employees becoming familiar with
the locations of fire extinguishers. Therefore, the employer must
locate the extinguishers in convenient locations where the employees
know they can be found. For example, they could be mounted in the
fire truck or cart that the fire brigade uses when it responds to
a fire emergency. They can also be distributed as set forth in the
National Fire Protection Association's Standard No. 10, "Portable
Fire Extinguishers."
Where the employer has decided to permit all employees in the workplace
to use fire extinguishers, then the entire WISHA standard applies.
(3) Portable fire extinguisher mounting. Previous standards for
mounting fire extinguishers have been criticized for requiring specific
mounting locations. In recognition of this criticism, the standard
has been rewritten to permit as much flexibility in extinguisher
mounting as is acceptable to assure that fire extinguishers are
available when needed and that employees are not subjected to injury
hazards when they try to obtain an extinguisher.
It is the intent of WISHA to permit the mounting of extinguishers
in any location that is accessible to employees without the use
of portable devices such as a ladder. This limitation is necessary
because portable devices can be moved or taken from the place where
they are needed and, therefore, might not be available at the time
of an emergency.
Employers are given as much flexibility as possible to assure that
employees can obtain extinguishers as fast as possible. For example,
an acceptable method of mounting extinguishers in areas where fork
lift trucks or tow-motors are used is to mount the units on retractable
board which, by means of counterweighting, can be raised above the
level where they could be struck by vehicular traffic. When needed,
they can be lowered quickly for use. This method of mounting can
also reduce vandalism and unauthorized use of extinguishers. The
extinguishers may also be mounted as outlined in the National Fire
Protection Association's Standard No. 10, "Portable Fire Extinguishers."
(4) Selection and distribution. The employer is responsible for
the proper selection and distribution of fire extinguishers and
the determination of the necessary degree of protection. The selection
and distribution of fire extinguishers must reflect the type and
class of fire hazards associated with a particular workplace.
Extinguishers for protecting Class A hazards may be selected from
the following types: Water, foam, loaded stream, or multipurpose
dry chemical. Extinguishers for protecting Class B hazards may be
selected from the following types: Halon 1301, Halon 1211, carbon
dioxide, dry chemicals, foam, or loaded stream. Extinguishers for
Class C hazards may be selected from the following types: Halon
1301, Halon 1211, carbon dioxide, or dry chemical.
Combustible metal (Class D hazards) fires pose a different type
of fire problem in the workplace. Extinguishers using water, gas,
or certain dry chemicals cannot extinguish or control this type
of fire. Therefore, certain metals have specific dry powder extinguishing
agents which can extinguish or control this type of fire. Those
agents which have been specifically approved for use on certain
metal fires provide the best protection; however, there are also
some "universal" type agents which can be used effectively on a
variety of combustible metal fires if necessary. The "universal"
type agents include: Foundry flux, Lith-X powder, TMB liquid, pyromet
powder, TEC powder, dry talc, dry graphite powder, dry sand, dry
sodium chloride, dry soda ash, lithium chloride, zirconium silicate,
and dry dolomite.
Water is not generally accepted as an effective extinguishing agent
for metal fires. When applied to hot burning metal, water will break
down into its basic atoms of oxygen and hydrogen. This chemical
breakdown contributes to the combustion of the metal. However, water
is also a good universal coolant and can be used on some combustible
metals, but only under proper conditions and application, to reduce
the temperature of the burning metal below the ignition point. For
example, automatic deluge systems in magnesium plants can discharge
such large quantities of water on burning magnesium that the fire
will be extinguished. The National Fire Protection Association has
specific standards for this type of automatic sprinkler system.
Further information on the control of metal fires with water can
be found in the National Fire Protection Association's Fire Protection
Handbook.
An excellent source of selection and distribution criteria is found
in the National Fire Protection Association's Standard No. 10. Other
sources of information include the National Safety Council and the
employer's fire insurance carrier.
(5) Substitution of standpipe systems for portable fire extinguishers.
The employer is permitted to substitute acceptable standpipe systems
for portable fire extinguishers under certain circumstances. It
is necessary to assure that any substitution will provide the same
coverage that portable units provide. This means that fire hoses,
because of their limited portability, must be spaced throughout
the protected area so that they can reach around obstructions such
as columns, machinery, etc., and so that they can reach into closets
and other enclosed areas.
(6) Inspection, maintenance and testing. The ultimate responsibility
for the inspection, maintenance and testing of portable fire extinguishers
lies with the employer. The actual inspection, maintenance, and
testing may, however, be conducted by outside contractors with whom
the employer has arranged to do the work. When contracting for such
work, the employer should assure that the contractor is capable
of performing the work that is needed to comply with this standard.
If the employer should elect to perform the inspection, maintenance,
and testing requirements of this section in-house, then the employer
must make sure that those persons doing the work have been trained
to do the work and to recognize problem areas which could cause
an extinguisher to be inoperable. The National Fire Protection Association
provides excellent guidelines in its standard for portable fire
extinguishers. The employer may also check with the manufacturer
of the unit that has been purchased and obtain guidelines on inspection,
maintenance, and testing. Hydrostatic testing is a process that
should be left to contractors or individuals using suitable facilities
and having the training necessary to perform the work.
Any time the employer has removed an extinguisher from service
to be checked or repaired, alternate equivalent protection must
be provided. Alternate equivalent protection could include replacing
the extinguisher with one or more units having equivalent or equal
ratings, posting a fire watch, restricting the unprotected area
from employee exposure, or providing a hose system ready to operate.
(7) Hydrostatic testing. As stated before, the employer may contract
for hydrostatic testing. However, if the employer wishes to provide
the testing service, certain equipment and facilities must be available.
Employees should be made aware of the hazards associated with hydrostatic
testing and the importance of using proper guards and water pressures.
Severe injury can result if extinguisher shells fail violently under
hydrostatic pressure.
Employers are encouraged to use contractors who can perform adequate
and reliable service. Firms which have been certified by the Materials
Transportation Board (MTB) of the United States Department of Transportation
(DOT), or state licensed extinguisher servicing firms, or recognized
by the National Association of Fire Equipment Distributors in Chicago,
Illinois, are generally acceptable for performing this service.
(8) Training and education. This part of the standard is of the
utmost importance to employers and employees if the risk of injury
or death due to extinguisher use is to be reduced. If an employer
is going to permit an employee to fight a workplace fire of any
size, the employer must make sure that the employee knows everything
necessary to assure the employee's safety.
Training and education can be obtained through many channels. Often,
local fire departments in larger cities have fire prevention bureaus
or similar organizations which can provide basic fire prevention
training programs. Fire insurance companies will have data and information
available. The National Fire Protection Association and the National
Safety Council will provide, at a small cost, publications that
can be used in a fire prevention program.
Actual fire fighting training can be obtained from various sources
in the country. The Texas A and M University, the University of
Maryland's Fire and Rescue Institute, West Virginia University's
Fire Service Extension, Iowa State University's Fire Service Extension
and other state training schools and land grant colleges have fire
fighting programs directed to industrial applications. Some manufacturers
of extinguishers, such as the Ansul Company and Safety First, conduct
fire schools for customers in the proper use of extinguishers. Several
large corporations have taken time to develop their own on-site
training programs which expose employees to the actual "feeling"
of fire fighting. Simulated fires for training of employees in the
proper use of extinguishers are also an acceptable part of a training
program.
In meeting the requirements of this section, the employer may also
provide educational materials, without classroom instruction, through
the use of employee notice campaigns using instruction sheets or
flyers or similar types of informal programs. The employer must
make sure that employees are trained and educated to recognize not
only what type of fire is being fought and how to fight it, but
also when it is time to get away from it and leave fire suppression
to more experienced fire fighters.
[Statutory Authority: RCW 49.17.010,
.040, .050. 01-11-038 (Order 99-36), § 296-24-59215, filed 05/09/01,
effective 09/01/01. Statutory Authority: Chapter 49.17 RCW. 94-15-096
(Order 94-07), § 296-24-59215, filed 7/20/94, effective 9/20/94.
Statutory Authority: RCW 49.17.040 and 49.17.050. 82-02-003 (Order
81-32), § 296-24-59215, filed 12/24/81.]
WAC
296-24-602 Standpipe and hose systems.
This section establishes design and installation criteria for
standpipe systems.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-602, filed 12/24/81.]
WAC
296-24-60201 Scope and application.
(1) Scope. This section applies to all small hose, Class II and
Class III standpipe systems installed to meet the requirements of
a particular WISHA standard.
(2) Exception. This section does not apply to Class I standpipe
systems.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-60201, filed 12/24/81.]
WAC
296-24-60203 Protection of standpipes.
The employer shall assure that standpipes are located or otherwise
protected against mechanical damage. Damaged standpipes shall be
repaired promptly.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-60203, filed 12/24/81.]
WAC
296-24-60205 Equipment.
(1) Reels and cabinets. Where reels or cabinets are provided to
contain fire hose, the employer shall assure that they are designed
to facilitate prompt use of the hose valves, the hose, and other
equipment at the time of a fire or other emergency. The employer
shall assure that the reels and cabinets are conspicuously identified
and used only for fire equipment.
(2) Hose outlets and connections.
(a) The employer shall assure that hose outlets and connections
are located high enough above the floor to avoid being obstructed
and to be accessible to employees.
(b) The employer shall standardize screw threads or provide appropriate
adapters throughout the system and assure that the hose connections
are compatible with those used on the supporting fire equipment.
(3) Hose.
(a) The employer shall assure that every one and one-half inch
(3.8 cm) or smaller hose outlet used to meet this standard is
equipped with hose connected and ready for use. In extremely cold
climates where such installation may result in damaged equipment,
the hose may be stored in another location provided it is readily
available and can be connected when needed.
(b) Standpipe systems installed after July 1, 1982, for use by
employees, shall be equipped with lined hose. Unlined hose may
remain in use on existing systems. However, after the effective
date of this standard, unlined hose which becomes unserviceable
shall be replaced with lined hose.
(c) Employers must provide hose of sufficient length so that
friction, resulting from water flowing through the hose, does
not decrease the pressure at the nozzle below 30 psi (210 kPa).
The dynamic pressure at the nozzle must be within the range of
30 psi (210 kPa) to 125 psi (860 kPa).
(4) Nozzles. Employers must make sure that standpipe hoses are
equipped with shut-off type nozzles.
[Statutory Authority: RCW
49.17.010, .040, .050. 02-12-098 (Order 00-20), § 296-24-60205,
filed 06/05/02, effective 08/01/02. Statutory Authority: RCW
49.17.040 and 49.17.050. 82-02-003 (Order 81-32), § 296-24-60205,
filed 12/24/81.]
WAC
296-24-60207 Water supply.
The minimum water supply for standpipe and hose systems, which
are provided for the use of employees, shall be sufficient to provide
100 gallons per minute (6.3 l/s) for a period of at least thirty
minutes.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-60207, filed 12/24/81.]
WAC
296-24-60209 Tests and maintenance.
(1) Acceptance tests.
(a) The employer shall assure that the piping of Class II and
Class III systems installed after July 1, 1982, including yard
piping, is hydrostatically tested for a period of at least two
hours at not less than 200 psi (1,380 kPa), or at least 50 psi
(340 kPa) in excess of normal pressure when such pressure is greater
than 150 psi (1,030 kPa).
(b) The employer shall assure that hose on all standpipe systems
installed after July 1, 1982, is hydrostatically tested with couplings
in place, at a pressure of not less than 200 psi (1,380 kPa),
before it is placed in service. This pressure shall be maintained
for at least fifteen seconds and not more than one minute during
which time the hose shall not leak nor shall any jacket thread
break during the test.
(2) Maintenance.
(a) The employer shall assure that water supply tanks are kept
filled to the proper level except during repairs. When pressure
tanks are used, the employer shall assure that proper pressure
is maintained at all times except during repairs.
(b) The employer shall assure that valves in the main piping
connections to the automatic sources of water supply are kept
fully open at all times except during repair.
(c) The employer shall assure that hose systems are inspected
at least annually and after each use to assure that all of the
equipment and hose are in place, available for use, and in serviceable
condition.
(d) When the system or any portion thereof is found not to be
serviceable, the employer shall remove it from service immediately
and replace it with equivalent protection such as extinguishers
and fire watches.
(e) The employer shall assure that hemp or linen hose on existing
systems is unracked, physically inspected for deterioration,
and reracked using a different fold pattern at least annually.
The employer shall assure that defective hose is replaced in
accordance with
WAC 296-24-60205 (3)(b).
(f) The employer shall designate trained persons to conduct all
inspections required under this section.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-60209, filed 12/24/81.]
WAC
296-24-60299 Appendix A-Standpipe and hose systems.
(1) Scope and application. This section has been written to provide
adequate coverage of those standpipe and hose systems that an
employer may install in the workplace to meet the requirements
of a particular WISHA standard. For example, WISHA permits the
substitution of hose systems for portable fire extinguishers in
WAC
296-24-592. If an employer chooses to provide hose systems
instead of portable Class A fire extinguishers, then those hose
systems used for substitution would have to meet the applicable
requirements of WAC
296-24-592. All other standpipe and hose systems not used
as a substitute would be exempt from these requirements.
The section specifically exempts Class I large hose systems. By
large hose systems, WISHA means those two and one-half inch hose
lines that are usually associated with fire departments of the size
that provide their own water supply through fire apparatus. When
the fire gets to the size that outside protection of that degree
is necessary, WISHA believes that in most industries employees will
have been evacuated from the fire area and the "professional" fire
fighters will take control.
(2) Protection of standpipes. Employers must make sure that standpipes
are protected so that they can be relied upon during a fire emergency.
This means protecting the pipes from mechanical and physical damage.
There are various means for protecting the equipment such as, but
not limited to, enclosing the supply piping in the construction
of the building, locating the standpipe in an area which is inaccessible
to vehicles, or locating the standpipe in a stairwell.
(3) Hose covers and cabinets. The employer should keep fire protection
hose equipment in cabinets or inside protective covers which will
protect it from the weather elements, dirt or other damaging sources.
The use of protective covers must be easily removed or opened to
assure that hose and nozzle are accessible. When the employer places
hose in a cabinet, the employer must make sure that the hose and
nozzle are accessible to employees without subjecting them to injury.
In order to make sure that the equipment is readily accessible,
the employer must also make sure that the cabinets used to store
equipment are kept free of obstructions and other equipment which
may interfere with the fast distribution of the fire hose stored
in the cabinet.
(4) Hose outlets and connections. The employer must assure that
employees who use standpipe and hose systems can reach the hose
rack and hose valve without the use of portable equipment such as
ladders. Hose reels are encouraged for use because one employee
can retrieve the hose, charge it, and place it into service without
much difficulty.
(5) Hose. When the employer elects to provide small hose in lieu
of portable fire extinguishers, those hose stations being used for
the substitution must have hose attached and ready for service.
However, if more than the necessary amount of small hose outlets
are provided, hose does not have to be attached to those outlets
that would provide redundant coverage. Further, where the installation
of hose on outlets may expose the hose to extremely cold climates,
the employer may store the hose in houses or similar protective
areas and connect it to the outlet when needed.
There is approved lined hose available that can be used to replace
unlined hose which is stored on racks in cabinets. The lined hose
is constructed so that it can be folded and placed in cabinets in
the same manner as unlined hose.
Hose is considered to be unserviceable when it deteriorates to
the extent that it can no longer carry water at the required pressure
and flow rates. Dry rotted linen or hemp hose, cross threaded couplings,
and punctured hose are examples of unserviceable hose.
(6) Nozzles. Variable stream nozzles can provide useful variations
in water flow and spray patterns during fire fighting operations
and they are recommended for employee use. It is recommended that
100 psi nozzle pressure be used to provide good flow patterns for
variable stream nozzles. The most desirable attribute for nozzles
is the ability of the nozzle person to shut off the water flow at
the nozzle when it is necessary. This can be accomplished in many
ways. For example, a shut-off nozzle with a lever or rotation of
the nozzle to stop flow would be effective, but in other cases a
simple globe valve placed between a straight stream nozzle and the
hose could serve the same purpose. For straight stream nozzles,
50 psi nozzle pressure is recommended. The intent of the standard
is to protect the employee from "run-away" hoses if it becomes necessary
to drop a pressurized hose line and retreat from the fire front
and other related hazards.
(7) Design and installation. Standpipe and hose systems designed
and installed in accordance with NFPA Standard No. 14-1976, "Standpipe
and Hose Systems," are considered to be in compliance with this
standard.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-60299, filed 12/24/81.]
WAC
296-24-607 Automatic sprinkler systems.
The design and installation criteria for automatic sprinkler systems
is contained in this section.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-607, filed 12/24/81.]
WAC
296-24-60701 Scope and application.
(1) The requirements of this section apply to all automatic sprinkler
systems installed to meet a particular WISHA standard.
(2) For automatic sprinkler systems used to meet WISHA requirements
and installed prior to the effective date of this standard, compliance
with the National Fire Protection Association (NFPA) or the National
Board of Fire Underwriters (NBFU) standard in effect at the time
of the system's installation will be acceptable as compliance with
this section.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-60701, filed 12/24/81.]
WAC
296-24-60703 Exemptions.
Automatic sprinkler systems installed in workplaces, but not required
by WISHA are exempt from the requirements of this section.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-60703, filed 12/24/81.]
WAC
296-24-60705 General requirements.
(1) Design.
(a) All automatic sprinkler designs used to comply with this
standard shall provide the necessary discharge patterns, densities,
and water flow characteristics for complete coverage in a particular
workplace or zoned subdivision of the workplace.
(b) The employer shall assure that only approved equipment and
devices are used in the design and installation of automatic sprinkler
systems used to comply with this standard.
(2) Maintenance. The employer shall properly maintain an automatic
sprinkler system installed to comply with this section. The employer
shall assure that a main drain flow test is performed on each system
annually. The inspector's test valve shall be opened at least every
two years to assure that the sprinkler system operates properly.
(3) Acceptance tests. The employer shall conduct proper acceptance
tests on sprinkler systems installed for employee protection after
July 1, 1982, and record the dates of such tests. Proper acceptance
tests include the following:
(a) Flushing of underground connections;
(b) Hydrostatic tests of piping in system;
(c) Air tests in dry-pipe systems;
(d) Dry-pipe valve operation; and
(e) Test of drainage facilities.
(4) Water supplies. The employer shall assure that every automatic
sprinkler system is provided with at least one automatic water supply
capable of providing design water flow for at least thirty minutes.
An auxiliary water supply or equivalent protection shall be provided
when the automatic water supply is out of service, except for systems
of twenty or fewer sprinklers.
(5) Hose connections for fire fighting use. The employer may attach
hose connections for fire fighting use to wet pipe sprinkler systems
provided that the water supply satisfies the combined design demand
for sprinklers and standpipes.
(6) Protection of piping. The employer shall assure that automatic
sprinkler system piping is protected against freezing and exterior
surface corrosions.
(7) Drainage. The employer shall assure that all dry sprinkler
pipes and fittings are installed so that the systems may be totally
drained.
(8) Sprinklers.
(a) The employer shall assure that only approved sprinklers are
used on systems.
(b) The employer may not use older style sprinklers to replace
standard sprinklers without a complete engineering review of the
altered part of the system.
(c) The employer shall assure that sprinklers are protected
from mechanical damage.
(9) Sprinkler alarms. On all sprinkler systems having more than
twenty sprinklers, the employer shall assure that a local water-flow
alarm is provided which sounds an audible signal on the premises
upon water flow through the system equal to the flow from a single
sprinkler.
(10) Sprinkler spacing. The employer shall assure that sprinklers
are spaced to provide a maximum protection area per sprinkler, a
minimum of interference to the discharge pattern by building or
structural members or building contents and suitable sensitivity
to possible fire hazards. The minimum vertical clearance between
sprinklers and material below shall be eighteen inches.
(11) Hydraulically designed systems. The employer shall assure
that hydraulically designed automatic sprinkler systems or portions
thereof are identified and that the location, number of sprinklers
in the hydraulically designed section, and the basis of the design
is indicated. Central records may be used in lieu of signs at sprinkler
valves provided the records are available for inspection and copying
by the director.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-60705, filed 12/24/81.]
WAC
296-24-60799 Appendix A-Automatic sprinkler systems.
(1) Scope and application. This section contains the minimum requirements
for design, installation and maintenance of sprinkler systems that
are needed for employee safety. The occupational safety and health
administration is aware of the fact that the National Board of Fire
Underwriters is no longer an active organization, however, sprinkler
systems still exist that were designed and installed in accordance
with that organization's standards. Therefore, WISHA will recognize
sprinkler systems designed to, and maintained in accordance with,
NBFU and earlier NFPA standards.
(2) Exemptions. In an effort to assure that employers will continue
to use automatic sprinkler systems as the primary fire protection
system in workplaces, WISHA is exempting from coverage those systems
not required by a particular WISHA standard and which have been
installed in workplaces solely for the purpose of protecting property.
Many of these types of systems are installed in areas or buildings
with little or no employee exposure. An example is those warehouses
where employees may enter occasionally to take inventory or move
stock. Some employers may choose to shut down those systems which
are not specifically required by WISHA rather than upgrade them
to comply with the standards. WISHA does not intend to regulate
such systems. WISHA only intends to regulate those systems which
are installed to comply with a particular WISHA standard.
(3) Design. There are two basic types of sprinkler system design.
Pipe schedule designed systems are based on pipe schedule tables
developed to protect hazards with standard sized pipe, number of
sprinklers, and pipe lengths. Hydraulic designed systems are based
on an engineered design of pipe size which will produce a given
water density or flow rate at any particular point in the system.
Either design can be used to comply with this standard.
The National Fire Protection Association's Standard No. 13, "Automatic
Sprinkler Systems," contains the tables needed to design and install
either type of system. Minimum water supplies, densities, and pipe
sizes are given for all types of occupancies.
The employer may check with a reputable fire protection engineering
consultant or sprinkler design company when evaluating existing
systems or designing a new installation.
With the advent of new construction materials for the manufacture
of sprinkler pipe, materials, other than steel, have been approved
for use as sprinkler pipe. Selection of pipe material should be
made on the basis of the type of installation and the acceptability
of the material to local fire and building officials where such
systems may serve more than one purpose.
Before new sprinkler systems are placed into service, an acceptance
test is to be conducted. The employer should invite the installer,
designer, insurance representative, and a local fire official to
witness the test. Problems found during the test are to be corrected
before the system is placed into service.
(4) Maintenance. It is important that any sprinkler system maintenance
be done only when there is minimal employee exposure to the fire
hazard. For example, if repairs or changes to the system are to
be made, they should be made during those hours when employees are
not working or are not occupying that portion of the workplace protected
by the portion of the system which has been shut down.
The procedures for performing a flow test via a main drain test
or by the use of an inspector's test valve can be obtained from
the employer's fire insurance company or from the National Fire
Protection Association's Standard No. 13A, "Sprinkler System, Maintenance."
(5) Water supplies. The water supply to a sprinkler system is one
of the most important factors an employer should consider when evaluating
a system. Obviously, if there is no water supply, the system is
useless. Water supplies can be lost for various reasons such as
improperly closed valves, excessive demand, broken water mains,
and broken fire pumps. The employer must be able to determine if
or when this type of condition exists either by performing a main
drain test or visual inspection. Another problem may be an inadequate
water supply. For example, a light hazard occupancy may, through
rehabilitation or change in tenants, become an ordinary or high
hazard occupancy. In such cases, the exiting water supply may not
be able to provide the pressure or duration necessary for proper
protection. Employers must assure that proper design and tests have
been made to assure an adequate water supply. These tests can be
arranged through the employer's fire insurance carrier or through
a local sprinkler maintenance company or through the local fire
prevention organization.
Any time the employer must shut down the primary water supply for
a sprinkler system, the standard requires that equivalent protection
be provided. Equivalent protection may include a fire watch with
extinguishers or hose lines in place and manned, or a secondary
water supply such as a tank truck and pump, or a tank or fire pond
with fire pumps, to protect the areas where the primary water supply
is limited or shut down. The employer may also require evacuation
of the workplace and have an emergency action plan which specifies
such action.
(6) Protection of piping. Piping which is exposed to corrosive
atmospheres, either chemical or natural, can become defective to
the extent that it is useless. Employers must assure that piping
is protected from corrosion by its material of construction, e.g.,
stainless steel, or by a protective coating, e.g., paint.
(7) Sprinklers. When an employer finds it necessary to replace
sprinkler system components or otherwise change a sprinkler's design,
employer should make a complete fire protection engineering survey
of that part of the system being changed. This review should assure
that the changes to the system will not alter the effectiveness
of the system as it is presently designed. Water supplies, densities
and flow characteristics should be maintained.
(8) Protection of sprinklers. All components of the system must
be protected from mechanical impact damage. This can be achieved
with the use of mechanical guards or screens or by locating components
in areas where physical contact is impossible or limited.
(9) Sprinkler alarms. The most recognized sprinkler alarm is the
water-motor gong or bell that sounds when water begins to flow through
the system. This is not however, the only type of acceptable water
flow alarm. Any alarm that gives an indication that water is flowing
through the system is acceptable. For example, a siren, a whistle,
a flashing light, or similar alerting device which can transmit
a signal to the necessary persons would be acceptable. The purpose
of the alarm is to alert persons that the system is operating, and
that some type of planned action is necessary.
(10) Sprinkler spacing. For a sprinkler system to be effective
there must be an adequate discharge of water spray from the sprinkler
head. Any obstructions which hinder the designed density or spray
pattern of the water may create unprotected areas which can cause
fire to spread. There are some sprinklers that, because of the system's
design, are deflected to specific areas. This type of obstruction
is acceptable if the system's design takes it into consideration
in providing adequate coverage.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-60799, filed 12/24/81.]
WAC
296-24-617 Fixed extinguishing systems, general.
This section applies to criteria required for fixed extinguisher
systems and all sections of this chapter having number WAC
296-24-617 in the section number shall apply.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-617, filed 12/24/81.]
WAC
296-24-61701 Scope and application.
(1) This section applies to all fixed extinguishing systems installed
to meet a particular WISHA standard except for automatic sprinkler
systems which are covered by WAC
296-24-607.
(2) This section also applies to fixed systems not installed
to meet a particular WISHA standard, but which, by means of their
operation, may expose employees to possible injury, death, or
adverse health consequences caused by the extinguishing agent.
Such systems are only subject to the requirements of WAC
296-24-61703 (4) through (7) and 296-24-61705.
(3) Systems otherwise covered in subsection (2) of this section
which are installed in areas with no employee exposure are exempted
from the requirements of this section.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-61701, filed 12/24/81.]
WAC
296-24-61703 General requirements.
(1) Fixed extinguishing system components and agents shall be designed
and approved for use on the specific fire hazards they are expected
to control or extinguish.
(2) If for any reason a fixed extinguishing system becomes inoperable,
the employer shall notify employees and take the necessary temporary
precautions to assure their safety until the system is restored
to operating order. Any defects or impairments shall be properly
corrected by trained personnel.
(3) The employer shall provide a distinctive alarm or signaling
system which complies with WAC
296-800-310, and is capable of being perceived above ambient
noise or light levels, on all extinguishing systems in those portions
of the workplace covered by the extinguishing system to indicate
when the extinguishing system is discharging. Discharge alarms
are not required on systems where discharge is immediately recognizable.
(4) The employer shall provide effective safeguards to warn employees
against entry into discharge areas where the atmosphere remains
hazardous to employee safety or health.
(5) The employer shall post hazard warning or caution signs at
the entrance to, and inside of, areas protected by fixed extinguishing
systems which use agents in concentrations known to be hazardous
to employee safety and health.
(6) The employer shall assure that fixed systems are inspected
annually by a person knowledgeable in the design and function of
the system to assure that the system is maintained in good operating
condition.
(7) The employer shall assure that the weight and pressure of refillable
containers is checked at least semiannually. If the container shows
a loss in net content or weight of more than five percent, or a
loss in pressure of more than ten percent, it shall be subjected
to maintenance.
(8) The employer shall assure that factory charged nonrefillable
containers which have no means of pressure indication are weighed
at least semiannually. If a container shows a loss in net weight
of more than five percent it shall be replaced.
(9) The employer shall assure that inspection and maintenance dates
are recorded on the container, on a tag attached to the container,
or in a central location. A record of the last semiannual check
shall be maintained until the container is checked again or for
the life of the container, whichever is less.
(10) The employer shall train employees designated to inspect,
maintain, operate, or repair fixed extinguishing systems and annually
review their training to keep them up-to-date in the functions they
are to perform.
(11) The employer shall not use chlorobromomethane or carbon tetrachloride
as an extinguishing agent where employees may be exposed.
(12) The employer shall assure that systems installed in the presence
of corrosive atmospheres are constructed of noncorrosive material
or otherwise protected against corrosion.
(13) Automatic detection equipment shall be approved, installed
and maintained in accordance with WAC
296-24-629.
(14) The employer shall assure that all systems designed for and
installed in areas with climatic extremes shall operate effectively
at the expected extreme temperatures.
(15) The employer shall assure that at least one manual station
is provided for discharge activation of each fixed extinguishing
system.
(16) The employer shall assure that manual operating devices are
identified as to the hazard against which they will provide protection.
(17) The employer shall provide and assure the use of the personal
protective equipment needed for immediate rescue of employees trapped
in hazardous atmospheres created by an agent discharge.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-61703, filed 12/24/81.]
WAC
296-24-61705 Total flooding systems with potential health and
safety hazards to employees.
(1) The employer shall provide an emergency action plan in accordance
with WAC
296-24-567 for each area within a workplace that is protected
by a total flooding system which provides agent concentrations
exceeding the maximum safe levels.
(2) Systems installed in areas where employees cannot enter during
or after the system's operation are exempt from the requirements
of this section.
(3) On all total flooding systems the employer must provide a predischarge
employee alarm which will give employees time to safely exit from
the discharge area prior to system discharge.
Your predischarge employee alarm systems must:
- Provide enough warning to allow employees to safely escape from
the workplace or the immediate work area or both;
-
Be capable of being perceived above ambient noise or light
levels by all employees in the affected portions of the workplace
before system discharge;
-
Be distinctive and recognizable as a signal to evacuate the
work area;
-
Be kept in operating condition except when undergoing repairs
or maintenance.
You must explain to each employee how to report emergencies in
your workplace. Methods of reporting emergencies include manual
pull box alarms, public address systems, radio, or telephones. Post
emergency telephone numbers near telephones, or employee notice
boards, or other conspicuous locations if you use telephones to
report emergencies.
If you use a communication system that also serves as an employee
alarm system, all emergency messages must have priority over all
nonemergency messages.
(4) The employer shall provide automatic actuation of total flooding
systems by means of an approved fire detection device installed
and interconnected with a predischarge employee alarm system to
give employees time to safely exit from the discharge area prior
to system discharge.
[Statutory Authority: RCW 49.17.010,
.040, .050. 01-11-038 (Order 99-36), § 296-24-61705, filed 05/09/01,
effective 09/01/01. Statutory Authority: RCW 49.17.040 and 49.17.050.
82-02-003 (Order 81-32), § 296-24-61705, filed 12/24/81.]
WAC
296-24-61799 Appendix A-Fixed extinguishing systems, general.
(1) Scope and application. This section contains the general requirements
that are applicable to all fixed extinguishing systems installed
to meet WISHA standards. It also applies to those fixed extinguishing
systems, generally total flooding, which are not required by WISHA,
but which, because of the agent's discharge, may expose employees
to hazardous concentrations of extinguishing agents or combustion
byproducts. Employees who work around fixed extinguishing systems
must be warned of the possible hazards associated with the system
and its agent. For example, fixed dry chemical extinguishing systems
may generate a large enough cloud of dry chemical particles that
employees may become visually disoriented. Certain gaseous agents
can expose employees to hazardous byproducts of combustion when
the agent comes into contact with hot metal or other hot surface.
Some gaseous agents may be present in hazardous concentrations when
the system has totally discharged because an extra rich concentration
is necessary to extinguish deep-seated fires. Certain local application
systems may be designed to discharge onto the flaming surface of
a liquid, and it is possible that the liquid can splatter when hit
with the discharging agent. All of these hazards must be determined
before the system is placed into operation, and must be discussed
with employees.
Based on the known toxicological effects of agents such as carbon
tetrachloride and chlorobromomethane, WISHA is not permitting the
use of these agents in areas where employees can be exposed to the
agent or its side effects. However, chlorobromomethane has been
accepted and may be used as an explosion suppression agent in unoccupied
spaces. WISHA is permitting the use of this agent only in areas
where employees will not be exposed.
(2) Distinctive alarm signals. A distinctive alarm signal is required
to indicate that a fixed system is discharging. Such a signal is
necessary on those systems where it is not immediately apparent
that the system is discharging. For example, certain gaseous agents
make a loud noise when they discharge. In this case, no alarm signal
is necessary. However, where systems are located in remote locations
or away from the general work area and where it is possible that
a system could discharge without anyone knowing that it is doing
so, then a distinctive alarm is necessary to warn employees of the
hazards that may exist. The alarm can be a bell, gong, whistle,
horn, flashing light, or any combination of signals as long as it
is identifiable as a discharge alarm.
(3) Maintenance. The employer is responsible for the maintenance
of all fixed systems, but this responsibility does not preclude
the use of outside contractors to do such work. New systems should
be subjected to an acceptance test before placed in service. The
employer should invite the installer, designer, insurance representative
and others to witness the test. Problems found during the test need
to be corrected before the system is considered operational.
(4) Manual discharge stations. There are instances, such as for
mechanical reasons and others, where the standards call for a manual
backup activation device. While the location of this device is not
specified in the standard, the employer should assume that the device
should be located where employees can easily reach it. It could,
for example, be located along the main means of egress from the
protected area so that employees could activate the system as they
evacuate the work area.
(5) Personal protective equipment. The employer is required to
provide the necessary personal protective equipment to rescue employees
who may be trapped in a totally flooded environment which may be
hazardous to their health. The equipment would normally include
a positive-pressure self-contained breathing apparatus and any necessary
first aid equipment. In cases where the employer can assure the
prompt arrival of the local fire department or plant emergency personnel
which can provide the equipment, this can be considered as complying
with the standards.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-61799, filed 12/24/81.]
WAC
296-24-622 Fixed extinguishing systems, dry chemical.
The design and installation requirements specifically applicable
to fixed extinguishing systems, using dry chemical as the extinguishing
agent, are contained in this section.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-622, filed 12/24/81.]
WAC
296-24-62201 Scope and application.
This section applies to all fixed extinguishing systems using
dry chemical as the extinguishing agent, installed to meet a particular
WISHA standard. These systems shall also comply with WAC
296-24-617.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62201, filed 12/24/81.]
WAC
296-24-62203 Specific requirements.
(1) The employer shall assure that dry chemical agents are compatible
with any foams or wetting agents with which they are used.
(2) The employer may not mix together dry chemical extinguishing
agents of different compositions. The employer shall assure that
dry chemical systems are refilled with the chemical stated on the
approval nameplate or an equivalent compatible material.
(3) When dry chemical discharge may obscure vision, the employer
must provide a predischarge employee alarm which will give employees
time to safely exit from the discharge area prior to system discharge.
Your predischarge employee alarm systems must:
- Provide enough warning to allow employees to safely escape from
the workplace or the immediate work area or both;
-
Be capable of being perceived above ambient noise or light
levels by all employees in the affected portions of the workplace
before system discharge;
-
Be distinctive and recognizable as a signal to evacuate the
work area;
-
Be kept in operating condition except when undergoing repairs
or maintenance.
You must explain to each employee how to report emergencies in
your workplace. Methods of reporting emergencies include manual
pull box alarms, public address systems, radio, or telephones. Post
emergency telephone numbers near telephones, or employee notice
boards, or other conspicuous locations if you use telephones to
report emergencies.
If you use a communication system that also serves as an employee
alarm system, all emergency messages must have priority over all
nonemergency messages.
(4) The employer shall sample the dry chemical supply of all but
stored pressure systems at least annually to assure that the dry
chemical supply is free of moisture which may cause the supply to
cake or form lumps.
(5) The employer shall assure that the rate of application of dry
chemicals is such that the designed concentration of the system
will be reached within thirty seconds of initial discharge.
[Statutory Authority: RCW 49.17.010,
.040, .050. 01-11-038 (Order 99-36), § 296-24-62203, filed 05/09/01,
effective 09/01/01. Statutory Authority: RCW 49.17.040 and 49.17.050.
82-02-003 (Order 81-32), § 296-24-62203, filed 12/24/81.]
WAC
296-24-62299 Appendix A-Fixed extinguishing systems, dry chemical.
(1) Scope and application. The requirements of this section apply
only to dry chemical systems. These requirements are to be used
in conjunction with the requirements of WAC
296-24-617.
(2) Maintenance. The employer is responsible for assuring that
dry chemical systems will operate effectively. To do this, periodic
maintenance is necessary. One test that must be conducted during
the maintenance check is one which will determine if the agent has
remained free of moisture. If an agent absorbs any moisture, it
may tend to cake and thereby clog the system. An easy test for acceptable
moisture content is to take a lump of dry chemical from the container
and drop it from a height of four inches. If the lump crumbles into
fine particles, the agent is acceptable.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62299, filed 12/24/81.]
WAC
296-24-623 Fixed extinguishing systems, gaseous agent.
This section contains the design and installation requirements
for fixed extinguishing systems using gaseous agents.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-623, filed 12/24/81.]
WAC
296-24-62301 Scope and application.
(1) Scope. This section applies to all fixed extinguishing systems,
using a gas as the extinguishing agent, installed to meet a particular
WISHA standard. These systems shall also comply with WAC
296-24-617. In some cases, the gas may be in a liquid state
during storage.
(2) Application. The requirements of WAC
296-24-61703 (2) and (4) through (7) shall apply only to total
flooding systems.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62301, filed 12/24/81.]
WAC
296-24-62303 Specific requirements.
(1) Agents used for initial supply and replenishment shall be of
the type approved for the system's application. Carbon dioxide obtained
by dry ice conversion to liquid is not acceptable unless it is processed
to remove excess water and oil.
(2) Except during overhaul, the employer shall assure that the
designed concentration of gaseous agents is maintained until the
fire has been extinguished or is under control.
(3) The employer shall assure that employees are not exposed to
toxic levels of gaseous agent or its decomposition products.
(4) The employer shall assure that the designed extinguishing concentration
is reached within thirty seconds of initial discharge except for
Halon systems which must achieve design concentration within ten
seconds.
(5) The employer shall provide a distinctive predischarge employee
alarm capable of being perceived above ambient light or noise levels
when agent design concentrations exceed the maximum safe level for
employee exposure. A predischarge employee alarm for alerting employees
before system discharge shall be provided on Halon 1211 and carbon
dioxide systems with a design concentration of four percent or greater,
and for Halon 1301 systems with a design concentration of ten percent
or greater. The predischarge employee alarm shall provide employees
time to safely exit the discharge area prior to system discharge.
(6)(a) Where egress from an area cannot be accomplished within
one minute, the employer shall not use Halon 1301 in concentrations
greater than seven percent.
(b) Where egress takes greater than thirty seconds but less than
one minute, the employer shall not use Halon 1301 in a concentration
greater than ten percent.
(c) Halon 1301 concentrations greater than ten percent are only
permitted in areas not normally occupied by employees provided
that any employee in the area can escape within thirty seconds.
The employer shall assure that no unprotected employees enter
the area during agent discharge.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62303, filed 12/24/81.]
WAC
296-24-62399 Appendix A-Fixed extinguishing systems, gaseous
agent.
(1) Scope and application. This section applies only to those systems
which use gaseous agents. The requirements of WAC
296-24-617 also apply to the gaseous agent systems covered
in this section.
(2) Design concentrations. Total flooding gaseous systems are based
on the volume of gas which must be discharged in order to produce
a certain designed concentration of gas in an enclosed area. The
concentration needed to extinguish a fire depends on several factors
including the type of fire hazard and the amount of gas expected
to leak away from the area during discharge. At times it is necessary
to "super-saturate" a work area to provide for expected leakage
from the enclosed area. In such cases, employers must assure that
the flooded area has been ventilated before employees are permitted
to reenter the work area without protective clothing and respirators.
(3) Toxic decomposition. Certain halogenated hydrocarbons will
break down or decompose when they are combined with high temperatures
found in the fire environment. The products of the decomposition
can include toxic elements or compounds. For example, when Halon
1211 is placed into contact with hot metal it will break down and
form bromide or fluoride fumes. The employer must find out which
toxic products may result from decomposition of a particular agent
from the manufacturer, and take the necessary precautions to prevent
employee exposure to the hazard.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62399, filed 12/24/81.]
WAC
296-24-627 Fixed extinguishing systems, water spray and foam.
This section contains the design and installation requirements
for extinguishing systems using water or foam solution as the extinguishing
agent.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-627, filed 12/24/81.]
WAC
296-24-62701 Scope and application.
This section applies to all fixed extinguishing systems, using
water or foam solution as the extinguishing agent, installed to
meet a particular WISHA standard. These systems shall also comply
with WAC
296-24-617. This section does not apply to automatic sprinkler
systems which are covered under WAC
296-24-607.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62701, filed 12/24/81.]
WAC
296-24-62703 Specific requirements.
(1) The employer shall assure that foam and water spray systems
are designed to be effective in at least controlling fire in the
protected area or on protected equipment.
(2) The employer shall assure that drainage of water spray systems
is directed away from areas where employees are working and that
no emergency egress is permitted through the drainage path.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62703, filed 12/24/81.]
WAC
296-24-62799 Appendix A-Fixed extinguishing systems, water spray
and foam.
(1) Scope and application. This section applies to those systems
that use water spray or foam. The requirements of WAC
296-24-617 also apply to this type of system.
(2) Characteristics of foams. When selecting the type of foam for
a specific hazard, the employer should consider the following limitations
of some foams.
(a) Some foams are not acceptable for use on fires involving
flammable gases and liquefied gases with boiling points below
ambient workplace temperatures. Other foams are not effective
when used on fires involving polar solvent liquids.
(b) Any agent using water as part of the mixture should not be
used on fire involving combustible metals unless it is applied
under proper conditions to reduce the temperature of burning metal
below the ignition temperature. The employer should use only those
foams that have been tested and accepted for this application
by a recognized independent testing laboratory.
(c) Certain types of foams may be incompatible and break down
when they are mixed together.
(d) For fires involving water miscible solvents, employers should
use only those foams tested and approved for such use. Regular
protein foams may not be effective on such solvents.
Whenever employers provide a foam or water spray system, drainage
facilities must be provided to carry contaminated water or foam
overflow away from the employee work area and egress routes. This
drainage system should drain to a central impounding area where
it can be collected and disposed of properly. Other government
agencies may have regulations concerning environmental considerations.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62799, filed 12/24/81.]
WAC
296-24-629 Fire detection systems.
The requirements for installation, restoration, maintenance, testing
and protection of fire detection systems and the criteria for response
time can be found in this section.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-629, filed 12/24/81.]
WAC
296-24-62901 Scope and application.
This section applies to all automatic fire detection systems installed
to meet the requirements of a particular WISHA standard.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62901, filed 12/24/81.]
WAC
296-24-62903 Installation and restoration.
(1) The employer shall assure that all devices and equipment constructed
and installed to comply with this standard are approved for the
purpose for which they are intended.
(2) The employer shall restore all fire detection systems and components
to normal operating condition as promptly as possible after each
test or alarm. Spare detection devices and components which are
normally destroyed in the process of detecting fires shall be available
on the premises or from a local supplier in sufficient quantities
and locations for prompt restoration of the system.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62903, filed 12/24/81.]
WAC
296-24-62905 Maintenance and testing.
(1) The employer shall maintain all systems in an operable condition
except during repairs or maintenance.
(2) The employer shall assure that fire detectors and fire detection
systems are tested and adjusted as often as needed to maintain proper
reliability and operating condition except that factory calibrated
detectors need not be adjusted after installation.
(3) The employer shall assure that pneumatic and hydraulic operated
detection systems installed after July 1, 1982, are equipped with
supervised systems.
(4) The employer shall assure that the servicing, maintenance and
testing of fire detection systems, including cleaning and necessary
sensitivity adjustments are performed by a trained person knowledgeable
in the operations and functions of the system.
(5) The employer shall also assure that fire detectors that need
to be cleaned of dirt, dust, or other particulates in order to be
fully operational are cleaned at regular periodic intervals.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62905, filed 12/24/81.]
WAC
296-24-62907 Protection of fire detectors.
(1) The employer shall assure that fire detection equipment installed
outdoors or in the presence of corrosive atmospheres be protected
from corrosion. The employer shall provide a canopy, hood, or other
suitable protection for detection equipment requiring protection
from the weather.
(2) The employer shall locate or otherwise protect detection equipment
so that it is protected from mechanical or physical impact which
might render it inoperable.
(3) The employer shall assure that detectors are supported independently
of their attachment to wires or tubing.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62907, filed 12/24/81.]
WAC
296-24-62909 Response time.
(1) The employer shall assure that fire detection systems installed
for the purpose of actuating fire extinguishment or suppression
systems shall be designed to operate in time to control or extinguish
a fire.
(2) The employer shall assure that fire detection systems installed
for the purpose of employee alarm and evacuation be designed and
installed to provide a warning for emergency action and safe escape
of employees.
(3) The employer shall not delay alarms or devices initiated by
fire detector actuation for more than thirty seconds unless such
delay is necessary for the immediate safety of employees. When
such delay is necessary, it shall be addressed in an emergency
action plan meeting the requirements of WAC
296-24-567.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62909, filed 12/24/81.]
WAC
296-24-62911 Number, location and spacing of detecting devices.
The employer shall assure that the number, spacing and location
of fire detectors is based upon design data obtained from field
experience, or tests, engineering surveys, the manufacturer's recommendations,
or a recognized testing laboratory listing.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62911, filed 12/24/81.]
WAC
296-24-62999 Appendix A-Fire detection systems.
(1) Installation and restoration. Fire detection systems must be
designed by knowledgeable engineers or other professionals, with
expertise in fire detection systems and when the systems are installed,
there should be an acceptance test performed on the system to insure
it operates properly. The manufacturer's recommendations for system
design should be consulted. While entire systems may not be approved,
each component used in the system is required to be approved. Custom
fire detection systems should be designed by knowledgeable fire
protection or electrical engineers who are familiar with the workplace
hazards and conditions. Some systems may only have one or two individual
detectors for a small workplace, but good design and installation
is still important. An acceptance test should be performed on all
systems, including these smaller systems.
WISHA has a requirement that spare components used to replace those
which may be destroyed during an alarm situation be available in
sufficient quantities and locations for prompt restoration of the
system. This does not mean that the parts or components have to
be stored at the workplace. If the employer can assure that the
supply of parts is available in the local community or the general
metropolitan area of the workplace, then the requirements for storage
and availability have been met. The intent is to make sure that
the alarm system is fully operational when employees are occupying
the workplace, and that when the system operates it can be returned
to full service the next day or sooner.
(2) Supervision. Fire detection systems should be supervised. The
object of supervision is detection of any failure of the circuitry,
and the employer should use any method that will assure that the
system's circuits are operational. Electrically operated sensors
for air pressure, fluid pressure, or electrical circuits, can provide
effective monitoring and are the typical types of supervision.
(3) Protection of fire detectors. Fire detectors must be protected
from corrosion either by protective coating, by being manufactured
from noncorrosive materials or by location. Detectors must also
be protected from mechanical impact damage, either by suitable cages
or metal guards where such hazards are present, or by locating them
above or out of contact with materials or equipment which may cause
damage.
(4) Number, location, and spacing of detectors. This information
can be obtained from the approval listing for detectors or NFPA
standards. It can also be obtained from fire protection engineers
or consultants or manufacturers of equipment who have access to
approval listing and design methods.
[Statutory Authority: RCW 49.17.040
and 49.17.050. 82-02-003 (Order 81-32), § 296-24-62999, filed 12/24/81.]
WAC
296-24-63299 Appendix B-National consensus standards.
The following table contains a cross-reference listing of those
current national consensus standards which contains information
and guidelines that would be considered acceptable in complying
with requirements in the specific sections.
| Section |
National
Consensus Standard |
| WAC 296-24-58505 |
ANSI/NFPA
No. 1972, Structural Fire Fighter's Helmets. ANSI Z88.5 American
National Standard, Practice for Respirator Protection for
the Fire Service. ANSI/NFPA No. 1971, Protective Clothing
for Structural Fire Fighters. NFPA No. 1041, Fire Service
Instructor Professional Qualifications. |
| WAC 296-24-592 |
ANSI/NFPA
No. 10, Portable Fire Extinguishers. |
| WAC 296-24-602 |
ANSI/NFPA
No. 18, Wetting Agents. ANSI/NFPA No. 20, Centrifugal Fire
Pumps. NFPA No. 21, Steam Fire Pumps. ANSI/NFPA No. 22, Water
Tanks. NFPA No. 24, Outside Protection. NFPA No. 26, Supervision
of Valves. NFPA No. 13E, Fire Department Operations in Properties
Protected by Sprinkler, Standpipe Systems. ANSI/NFPA No. 194,
Fire Hose Connections. NFPA No. 197, Initial Fire Attack,
Training for. NFPA No. 1231, Water Supplies for Suburban and
Rural Fire Fighting. |
| WAC 296-24-607 |
ANSI/NFPA
No. 13, Sprinkler Systems. NFPA No. 13A, Sprinkler Systems,
Maintenance. ANSI/NFPA No. 18, Wetting Agents. ANSI/NFPA No.
20, Centrifugal Fire Pumps. ANSI/NFPA No. 22, Water Tanks.
NFPA No. 24, Outside Protection. NFPA No. 26, Supervision
of Valves. ANSI/NFPA No. 72B, Auxiliary Signaling Systems.
NFPA No. 1231, Water Supplies for Suburban and Rural Fire
Fighting. |
| WAC 296-24-617 |
ANSI/NFPA
No. 11, Foam Systems. ANSI/NFPA No. 11A, High Expansion Foam
Extinguishing Systems. ANSI/NFPA No. 11B, Synthetic Foam and
Combined Agent Systems. ANSI/NFPA No. 12, Carbon Dioxide Systems.
ANSI/NFPA No. 12A, Halon 1301 Systems. ANSI/NFPA No. 12B,
Halon 1211 Systems. ANSI/NFPA No. 15, Water Spray Systems.
ANSI/NFPA No. 16, Foam-Water Spray Systems. ANSI/NFPA No.
17, Dry Chemical Systems. ANSI/NFPA No. 69, Explosion Suppression
Systems. |
| WAC 296-24-622 |
ANSI/NFPA
No. 11B, Synthetic Foam and Combined Agent Systems. ANSI/NFPA
No. 17, Dry Chemical Systems. |
| WAC 296-24-623 |
ANSI/NFPA
No. 12, Carbon Dioxide Systems. ANSI/NFPA No. 12A, Halon 1211
Systems. ANSI/NFPA No. 12B, Halon 1301 Systems. ANSI/NFPA
No. 69, Explosion Suppression Systems. |
| WAC 296-24-627 |
ANSI/NFPA
No. 11, Foam Extinguishing Systems. ANSI/NFPA No. 11A, High
Expansion Foam Extinguishing Systems. ANSI/NFPA No. 11B, Synthetic
Foam and Combined Agent Systems. ANSI/NFPA No. 15, Water Spray
Fixed Systems. ANSI/NFPA No. 16, Foam-Water Spray Systems.
ANSI/NFPA No. 18, Wetting Agents. NFPA No. 26, Supervision
of Valves. |
| WAC 296-24-629 |
ANSI/NFPA
No. 71, Central Station Signaling Systems. ANSI/NFPA No. 72A,
Local Protective Signaling Systems. ANSI/NFPA No. 72B, Auxiliary
Signaling Systems. ANSI/NFPA No. 72D, Proprietary Protective
Signaling Systems. ANSI/NFPA No. 72E, Automatic Fire Detectors.
ANSI/NFPA No. 101, Life Safety Code. |
| WAC 296-24-631 |
ANSI/NFPA
No. 71, Central Station Signaling Systems. ANSI/NFPA No. 72A,
Local Protective Signaling Systems. ANSI/NFPA No. 72B, Auxiliary
Protective Signaling Systems. ANSI/NFPA No. 72C, Remote Station
Protective Signaling Systems. ANSI/NFPA No. 72D, Proprietary
Protective Signaling Systems. ANSI/NFPA No. 101, Life Safety
Code. |
| Metric
Conversion |
ANSI/ASTM
NSo. E380, American National Standard for Metric Practice. |
NFPA standards are available from the National Fire Protection
Association; Batterymarch Park, Quincy, MA 02269-9101.
ANSI Standards are available from the American National Standards
Institute; 11 West 42nd Street; New York, NY 10036.
[Statutory Authority: Chapter 49.17
RCW. 94-15-096 (Order 94-07), § 296-24-63299, filed 7/20/94, effective
9/20/94. Statutory Authority: RCW 49.17.040 and 49.17.050. 82-02-003
(Order 81-32), § 296-24-63299, filed 12/24/81.]
WAC
296-24-63399 Appendix C-Fire protection references for further
information.
(1) Appendix general references. The following references provide
information which can be helpful in understanding the requirements
contained in all of the sections of Part G:
(a) Fire Protection Handbook, National Fire Protection Association,
Batterymarch Park, Quincy, MA 02269-9101.
(b) Accident Prevention Manual for Industrial Operations, National
Safety Council, 444 North Michigan Avenue, Chicago, IL 60611.
(c) Various associations also publish information which may be
useful in understanding these standards. Examples of these associations
are: Fire Equipment Manufacturers Association (FEMA) of Cleveland,
OH 44115-2851, and the National Association of Fire Equipment
Distributors (NAFED) of Chicago, IL 60611-4267.
(2) Appendix references applicable to individual sections. The
following references are grouped according to individual sections
contained in Part G. These references provide information which
may be helpful in understanding and implementing the standards of
each section of Part G.
(a) WAC 296-24-58505 - Fire brigades:
(i) Private Fire Brigades, NFPA 27; National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269-9101.
(ii) Initial Fire Attack, Training Standard On, NFPA 197; National
Fire Protection Association, Batterymarch Park, Quincy, MA 02269-9101.
(iii) Fire Fighter Professional Qualifications, NFPA 1001;
National Fire Protection Association, Batterymarch Park, Quincy,
MA 02269-9101.
(iv) Organization for Fire Services, NFPA 1201; National Fire
Protection Association, Batterymarch Park, Quincy, MA 02269-9101.
(v) Organization of a Fire Department, NFPA 1202; National
Fire Protection Association, Batterymarch Park, Quincy, MA 02269-9101.
(vi) Protective Clothing for Structural Fire Fighting, ANSI/NFPA
1971; National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269-9101.
(vii) American National Standards Institute for Men's Safety-Toe
Footwear, ANSI Z41.1; American National Standards Institute,
New York, NY 10036.
(viii) American National Standards Institute for Occupational
and Educational Eye and Face Protection, ANSI Z87.1; American
National Standards Institute, New York, NY 10036.
(ix) American National Standards Institute, Safety Requirements
for Industrial Head Protection, ANSI Z89.1; American National
Standards Institute, New York, NY 10036.
(x) Specifications for Protective Headgear for Vehicular Users,
ANSI Z90.1; American National Standards Institute, New York,
NY 10036.
(xi) Testing Physical Fitness; Davis and Santa Maria, Fire
Command, April 1975.
(xii) Development of a Job-Related Physical Performance Examination
for Fire Fighters; Dotson and Others. A summary report for the
National Fire Prevention and Control Administration, Washington,
D.C., March 1977.
(xiii) Proposed Sample Standards for Fire Fighters' Protective
Clothing and Equipment; International Association of Fire Fighters,
Washington, D.C. 20006-5395.
(xiv) A Study of Facepiece Leakage of Self-Contained Breathing
Apparatus by DOP Man Tests; Los Alamos National Laboratory,
Los Alamos, N.M.
(xv) The Development of Criteria for Fire Fighters' Gloves;
Vol. II: Glove Criteria and Test Methods; National Institute
for Occupational Safety and Health, Cincinnati, Ohio, 1976.
(xvi) Model Performance Criteria for Structural Fire Fighters'
Helmets; National Fire Prevention and Control Administration,
Washington, D.C., 1977.
(xvii) Fire Fighters; Job Safety and Health Magazine, Occupational
Safety and Health Administration, Washington, D.C., June 1978.
(xviii) Eating Smoke-The Dispensable Diet; Utech, H.P. The
Fire Independent, 1975.
(xix) Project Monoxide-A Medical Study of an Occupational Hazard
of Fire Fighters; International Association of Fire Fighters,
Washington, D.C. 20006-5395.
(xx) Occupational Exposures to Carbon Monoxide in Baltimore
Fire Fighters; Radford Baltimore, MD. Journal of Occupational
Medicine, September, 1976.
(xxi) Fire Brigades; National Safety Council, Chicago, IL 60611,
1966.
(xxii) American National Standards Institute, Practice for
Respiratory Protection for the Fire Service, ANSI Z88.5; American
National Standards Institute, New York, NY 10036.
(xxiii) Respirator Studies for the Nuclear Regulatory Commission;
October 1, 1977-September 30, 1978. Evaluation and Performance
of Open-Circuit Breathing Apparatus. NUREG/CR-1235. Los Alamos
National Laboratory; Los Alamos, NM 87545, January, 1980.
(b)
WAC 296-24-592 - Portable fire extinguishers:
(i) Standard for Portable Fire Extinguishers, ANSI/NFPA 10;
National Fire Protection Association, Batterymarch Park, Quincy,
MA 02269.
(ii) Methods for Hydrostatic Testing of Compressed-Gas Cylinders,
C-1; Compressed Gas Association, 1725 Jefferson Davis Highway,
Arlington, VA 22202-4100.
(iii) Recommendations for the Disposition of Unserviceable
Compressed-Gas Cylinders, C-2; Compressed Gas Association, 1725
Jefferson Davis Highway, Arlington, VA 22202-4100.
(iv) Standard for Visual Inspection of Compressed-Gas Cylinders,
C-6; Compressed Gas Association, 1725 Jefferson Davis Highway,
Arlington, VA 22202-4100.
(v) Portable Fire Extinguisher Selection Guide, National Association
of Fire Equipment Distributors, 401 North Michigan Avenue Chicago,
IL 60611-4267.
(c) WAC
296-24-602 - Standpipe and hose systems:
(i) Standard for the Installation of Sprinkler Systems, ANSI/NFPA
13; National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269-9101.
(ii) Standard of the Installation of Standpipe and Hose Systems,
ANSI/NFPA 14; National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269-9101.
(iii) Standard for the Installation of Centrifugal Fire Pumps,
ANSI/NFPA 20; National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269-9101.
(iv) Standard for Water Tanks for Private Fire Protection,
ANSI/NFPA 22; National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269-9101.
(v) Standard for Screw Threads and Gaskets for Fire Hose Connections,
ANSI/NFPA 194; National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269-9101.
(vi) Standard for Fire Hose, NFPA 196; National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269-9101.
(vii) Standard for the Care of Fire Hose, NFPA 198; National
Fire Protection Association, Batterymarch Park, Quincy, MA 02269-9101.
(d) WAC
296-24-607 - Automatic sprinkler systems:
(i) Standard of the Installation of Sprinkler Systems, ANSI/NFPA
13; National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269-9101.
(ii) Standard for the Care and Maintenance of Sprinkler Systems,
ANSI/NFPA 13A; National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269-9101.
(iii) Standard for the Installation of Standpipe and Hose Systems,
ANSI/NFPA 14; National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269-9101.
(iv) Standard for the Installation of Centrifugal Fire Pumps,
ANSI/NFPA 20; National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269-9101.
(v) Standard for Water Tanks for Private Fire Protection, ANSI/NFPA
22; National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269-9101.
(vi) Standard for Indoor General Storage, ANSI/NFPA 231; National
Fire Protection Association, Batterymarch Park, Quincy, MA 02269-9101.
(vii) Standard for Rack Storage of Materials, ANSI/NFPA 231C;
National Fire Protection Association, Batterymarch Park, Quincy,
MA 02269-9101.
(e) WAC
296-24-617 0 - Fixed extinguishing systems, general information:
(i) Standard for Foam Extinguishing Systems, ANSI/NFPA 11;
National Fire Protection Association, Batterymarch Park, Quincy,
MA 02269-9101.
(ii) Standard for Hi-Expansion Foam Systems, ANSI/NFPA 11A;
National Fire Protection Association, Batterymarch Park, Quincy,
MA 02269-9101.
(iii) Standard on Synthetic Foam and Combined Agent Systems,
ANSI/NFPA 11B; National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269-9101.
(iv) Standard on Carbon Dioxide Extinguishing Systems, ANSI/NFPA
12; National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269-9101.
(v) Standard on Halon 1301, ANSI/NFPA 12A; National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269-9101.
(vi) Standard on Halon 1211, ANSI/NFPA 12B; National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269-9101.
(vii) Standard for Water Spray Systems, ANSI/NFPA 15; National
Fire Protection Association, Batterymarch Park, Quincy, MA 02269-9101.
(viii) Standard for Foam-Water Sprinkler Systems and Foam-Water
Spray Systems, ANSI/NFPA 16; National Fire Protection Association,
Batterymarch Park, Quincy, MA 02269-9101.
(ix) Standard for Dry Chemical Extinguishing Systems, ANSI/NFPA
17; National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269-9101.
(f) WAC
296-24-622 - Fixed extinguishing systems, dry chemical:
(i) Standard for Dry Chemical Extinguishing Systems, ANSI/NFPA
17; National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269-9101.
(ii) National Electrical Code, ANSI/NFPA 70; National Fire
Protection Association, Batterymarch Park, Quincy, MA 02269-9101.
(iii) Standard for the Installation of Equipment for the Removal
of Smoke and Grease-Laden Vapor from Commercial Cooling Equipment,
NFPA 96; National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269-9101.
(g) WAC
296-24-623 - Fixed extinguishing systems, gaseous agents:
(i) Standard on Carbon Dioxide Extinguishing Systems, ANSI/NFPA
12; National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269-9101.
(ii) Standard on Halon 1301, ANSI/NFPA 12B; National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269-9101.
(iii) Standard on Halon 1211, ANSI/NFPA 12B; National Fire
Protection Association, Batterymarch Park, Quincy, MA 02269-9101.
(iv) Standard on Explosion Prevention Systems, ANSI/NFPA 69;
National Fire Protection Association, Batterymarch Park, Quincy,
MA 02269-9101.
(v) National Electrical Code, ANSI/NFPA 70; National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269-9101.
(vi) Standard on Automatic Fire Detectors, ANSI/NFPA 72E; National
Fire Protection Association, Batterymarch Park, Quincy, MA 02269-9101.
(vii) Determination of Halon 1301/1211 Threshold Extinguishing
Concentrations Using the Cup Burner Method, Riley and Olson,
Ansul Report AL-530-A.
(h) WAC
296-24-627 - Fixed extinguishing systems, water spray and
foam agents:
(i) Standard for Foam Extinguisher Systems, ANSI/NFPA 11; National
Fire Protection Association, Batterymarch Park, Quincy, MA 02269-9101.
(ii) Standard for High-Expansion Foam Systems, ANSI/NFPA 11A;
National Fire Protection Association, Batterymarch Park, Quincy,
MA 02269-9101.
(iii) Standard for Water Spray Fixed Systems for Fire Protection,
ANSI/NFPA 15; National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269-9101.
(iv) Standard for the Installation of Foam-Water Sprinkler
Systems and Foam-Water Spray Systems, ANSI/NFPA 16; National
Fire Protection Association, Batterymarch Park, Quincy, MA 02269-9101.
(i) WAC
296-24-629 - Fire detection systems:
(i) National Electrical Code, ANSI/NFPA 70; National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269-9101.
(ii) Standard for Central Station Signaling Systems, ANSI/NFPA
71; National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269-9101.
(iii) Standard on Automatic Fire Detectors, ANSI/NFPA 72E;
National Fire Protection Association, Batterymarch Park, Quincy,
MA 02269-9101.
(j)
WAC 296-800-310 - Employee alarm systems:
(i) National Electrical Code, ANSI/NFPA 70; National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269-9101.
(ii) Standard for Central Station Signaling Systems, ANSI/NFPA
71; National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269-9101.
(iii) Standard for Local Protective Signaling Systems, ANSI/NFPA
72A; National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269-9101.
(iv) Standard for Auxiliary Protective Signaling Systems, ANSI/NFPA
72B; National Fire Protection Association, Batterymarch Park,
Quincy, MA 02269-9101.
(v) Standard for Remote Station Protective Signaling Systems,
ANSI/NFPA 72C; National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269-9101.
(vi) Standard for Proprietary Protective Signaling Systems,
ANSI/NFPA 72D; National Fire Protection Association, Batterymarch
Park, Quincy, MA 02269-9101.
(vii) Vocal Emergency Alarms in Hospitals and Nursing Facilities:
Practice and Potential, National Institute of Standards and
Technology, Quince Orchard and Clopper Roads, Gaithersburg,
MD 20899-0011, July, 1977.
(viii) Fire Alarm and Communication Systems, National Institute
of Standards and Technology, Quince Orchard and Clopper Roads,
Gaithersburg, MD 20899-0011, April, 1976.
[Statutory Authority: Chapter 49.17
RCW. 94-15-096 (Order 94-07), § 296-24-63399, filed 7/20/94, effective
9/20/94; 92-23-017 (Order 92-13), § 296-24-63399, filed 11/10/92,
effective 12/18/92; 88-14-108 (Order 88-11), § 296-24-63399, filed
7/6/88; 87-24-051 (Order 87-24), § 296-24-63399, filed 11/30/87.
Statutory Authority: RCW 49.17.040 and 49.17.050. 82-02-003 (Order
81-32), § 296-24-63399, filed 12/24/81.]
WAC
296-24-63499 Appendix D-Availability of publications incorporated
by references in WAC 296-24-58505-Fire brigades.
The final standard for fire brigades, WAC
296-24-585, contains provisions which incorporate certain
publications by reference. The publications provide criteria and
test methods for protective clothing worn by those fire brigade
members who are expected to perform interior structural fire fighting.
The standard references the publications as the chief sources
of information for determining if the protective clothing affords
the required level of protection.
It is appropriate to note that the final standard does not require
employers to purchase a copy of the referenced publications. Instead,
employers can specify (in purchase orders to the manufacturers)
that the protective clothing meet the criteria and test methods
contained in the referenced publications and can rely on the manufacturers
assurances of compliance. Employers, however, may desire to obtain
a copy of the referenced publications for their own information.
The section designation of the standard where the referenced publications
appear, the title of the publications, and the availability of the
publications are as follows:
| Section
Designation |
Referenced
Publication |
Available
From |
| WAC 296-24-58513
(3)(b) |
"Protective
clothing for Structural Fire Fighting." NFPA No. 1971 (1975) |
National
Fire Protection Association, Batterymarch Park, Quincy, MA
02269-9101. |
| WAC 296-24-58513(4)(a) |
"Development
of Criteria for Fire Fighter's Gloves; Vol. II, Part II: Test
Methods." (1976) |
U.S. Government
Printing Office, Washington, D.C. 20401. Stock No. for Vol.
II is: 071-033-021-1 |
| WAC 296-24-58513(5)(a) |
"Model
Performance Criteria for Structural Firefighter's Helmet"
(1977) |
U.S. Fire
Administration, National Safety and Research Office, 16825
South Seton Avenue, Emmitsburg, Maryland 21727 |
The referenced publications (or a microfiche of the publications)
are available for review at many universities and public libraries
throughout the country. These publications may also be examined
at the OSHA Technical Data Center, Room N2439-Rear, United States
Department of Labor, 200 Constitution Avenue Northwest, Washington,
D.C. 20210 (202-219-7500), or at any OSHA Regional Office (see telephone
directories under United States Government-Labor Department).
[Statutory Authority: RCW
49.17.010, .040, .050. 02-12-098 (Order 00-20), § 296-24-63499,
filed 06/05/02, effective 08/01/02. Statutory Authority: Chapter
49.17 RCW. 94-15-096 (Order 94-07), § 296-24-63499, filed 7/20/94,
effective 9/20/94. Statutory Authority: RCW 49.17.040 and 49.17.050.
82-02-003 (Order 81-32), § 296-24-63499, filed 12/24/81.]
WAC
296-24-63599 Appendix E-Test methods for protective clothing.
This appendix contains test methods which must be used to determine
if protective clothing affords the required level of protection
as specified in WAC 296-24-58505 - fire brigades.
(1) Puncture resistance test method for foot protection.
(a) Apparatus. The puncture resistance test shall be performed
on a testing machine having a movable platform adjusted to travel
at one-quarter-inch per minute (0.1 cm/sec). Two blocks of hardwood,
metal, or plastic shall be prepared as follows: The blocks shall
be of such size and thickness as to insure a suitable rigid test
ensemble and allow for at least one-inch of the pointed end of
an 8D nail to be exposed for the penetration. One block shall
have a hole drilled to hold an 8D common nail firmly at an angle
of 98°. The second block shall have a maximum one-half inch (1.3
cm) diameter hole drilled through it so that the hole will allow
free passage of the nail after it penetrates the insole during
the test.
(b) Procedure. The test ensemble consisting of the sample unit,
the two prepared blocks, a piece of leather outsole ten to eleven
irons thick and a new 8D nail, shall be placed as follows: The
8D nail in the hole, the sample of outsole stock superimposed
above the nail, the area of the sole plate to be tested placed
on the outsole, and the second block with hole so placed as to
allow for free passage of the nail after it passes through the
outsole stock and sole plate in that order. The machine shall
be started and the pressure, in pounds required for the nail to
completely penetrate the outsole and sole plate, recorded to the
nearest five pounds. Two determinations shall be made on each
sole plate and the results averaged. A new nail shall be used
for each determination.
(c) Source. These test requirements are contained in "Military
Specification For Fireman's Boots," MIL-B-2885D (1973 and amendment
dated 1975) and are reproduced for your convenience.
(2) Test method for determining the strength of cloth by tearing:
Trapezoid method.
(a) Test specimen. The specimen shall be a rectangle of cloth
three-inches by six-inches (7.6 cm by 15.2 cm). The long dimension
shall be parallel to the warp for warp tests and parallel to the
filling for filling tests. No two specimens for warp tests shall
contain the same warp yarns, nor shall any two specimens for filling
tests contain the same filling yarns. The specimen shall be taken
no nearer the selvage than 1/10 the width of the cloth. An isosceles
trapezoid having an altitude of three inches (7.6 cm) and bases
of one inch (2.5 cm) and four inches (10.2 cm) in length, respectively,
shall be marked on each specimen, preferably with the aid of a
template. A cut approximately three-eighths inch (1 cm) in length
shall then be made in the center of a perpendicular to the one
inch (2.5 cm) edge.
(b) Apparatus.
(i) Six-ounce (.17 kg) weight tension clamps shall be used
so designed that the six ounces (.17 kg) of weight are distributed
evenly across the complete width of the sample.
(ii) The machine shall consist of three main parts: Straining
mechanism, clamps for holding specimen, and load and elongation
recording mechanisms.
(iii) A machine wherein the specimen is held between two clamps
and strained by a uniform movement of the pulling clamp shall
be used.
(iv) The machine shall be adjusted so that the pulling clamp
shall have a uniform speed of 12 ± 10.5 inches per minute (0.5
± .02 cm/sec).
(v) The machine shall have two clamps with two jaws on each
clamp. The design of the two clamps shall be such that one gripping
surface or jaw may be an integral part of the rigid frame of
the clamp or be fastened to allow a slight vertical movement,
while the other gripping surface or jaw shall be completely
moveable. The dimension of the immovable jaw of each clamp parallel
to the application of the load shall measure one inch, and the
dimension of the jaw perpendicular to this direction shall measure
three inches or more. The face of the moveable jaw of each clamp
shall measure one inch by three inches.
Each jaw face shall have a flat, smooth, gripping surface.
All edges which might cause a cutting action shall be rounded
to a radius of not over 1/64 inch (.04 cm). In cases where a
cloth tends to slip when being tested, the jaws may be faced
with rubber or other material to prevent slippage. The distance
between the jaws (gage length) shall be one inch at the start
of the test.
(vi) Calibrated dial; scale or chart shall be used to indicate
applied load and elongation. The machine shall be adjusted or
set, so that the maximum load required to break the specimen
will remain indicated on the calibrated dial or scale after
the test specimen has ruptured.
(vii) The machine shall be of such capacity that the maximum
load required to break the specimen shall be not greater than
eighty-five percent or less than fifteen percent of the rated
capacity.
(viii) The error of the machine shall not exceed two percent
up to and including a fifty-pound load (22.6 kg) and one percent
over a fifty-pound load (22.6 kg) at any reading within its
loading range.
(ix) All machine attachments for determining maximum loads
shall be disengaged during this test.
(c) Procedure.
(i) The specimen shall be clamped in the machine along the
nonparallel sides of the trapezoid so that these sides lie along
the lower edge of the upper clamp and the upper edge of the
lower clamp with the cut halfway between the clamps. The short
trapezoid base shall be held taut and the long trapezoid base
shall lie in the folds.
(ii) The machine shall be started and the force necessary to
tear the cloth shall be observed by means of an autographic
recording device. The speed of the pulling clamp shall be 12
inches ± 0.5-inch per minute (0.5 ± .02 cm/sec).
(iii) If a specimen slips between the jaws, breaks in or at
the edges of the jaws, or if for any reason attributable to
faulty technique, an individual measurement falls markedly below
the average test results for the sample unit, such result shall
be discarded and another specimen shall be tested.
(iv) The tearing strength of the specimen shall be the average
of the five highest peak loads of resistance registered for
three inches (7.6 cm) of separation of the tear.
(d) Report.
(i) Five specimens in each of the warp and filling direction
shall be tested from each sample unit.
(ii) The tearing strength of the sample unit shall be the average
of the result obtained from the specimens tested in each of
the warp and filling directions and shall be reported separately
to the nearest 0.1 pound (.05 kg).
(e) Source. These test requirements are contained in "Federal
Test Method Standard 191, Method 5136," and are reproduced for
your convenience.
(3) Test method for determining flame resistance of cloth; vertical.
(a) Test specimen. The specimen shall be a rectangle of cloth
two and three-quarter inches (7.0 cm) by twelve inches (30.5 cm)
with the long dimension parallel to either the warp or filling
direction of the cloth. No two warp specimens shall contain the
same warp yarns, and no two filling specimens shall contain the
same filling yarn.
(b) Number of determinations. Five specimens from each of the
warp and filling directions shall be tested from each sample unit.
(c) Apparatus.
(i) Cabinet. A cabinet and accessories shall be fabricated
in accordance with the requirements specified in Figures L-1,
L-2, and L-3. Galvanized sheet metal or other suitable metal
shall be used. The entire inside back wall of the cabinet shall
be painted black to facilitate the viewing of the test specimen
and pilot flame.
(ii) Burner. The burner shall be equipped with a variable orifice
to adjust the flame height, a barrel having a three-eighth inch
(9.5 mm) inside diameter and a pilot light.
(A) The burner may be constructed by combining a three-eighth
inch (1 cm) inside diameter barrel 3 ± 1/4-inches (7.6 ± .6
cm) long from a fixed orifice burner with a base from a variable
orifice burner.
(B) The pilot light tube shall have a diameter of approximately
one-sixteenth inch (.2 cm) and shall be spaced one-eighth
inch (.3 cm) away from the burner edge with a pilot flame
one-eighth inch (.3 cm) long.
(C) The necessary gas connections and the applicable plumbing
shall be as specified in Figure L-4 except that a solenoid
valve may be used in lieu of the stopcock valve to which the
burner is attached. The stopcock valve or solenoid valve,
whichever is used, shall be capable of being fully opened
or fully closed in 0.1 second.
(D) On the side of the barrel of the burner, opposite the
pilot light there shall be a metal rod of approximately one-eighth
inch (.3 cm) diameter spaced one-half inch (1.3 cm) from the
barrel and extending above the burner. The rod shall have
two five-sixteenth inch (.8 cm) prongs marking the distances
of three-quarters inch (1.9 cm), and one and one-half inches
(3.8 cm) above the top of the burner.
(E) The burner shall be fixed in a position so that the center
of the barrel of the burner is directly below the center of
the specimen.
(iii) There shall be a control valve system with a delivery
rate designed to furnish gas to the burner under a pressure
of 2-1/2 ± 1/4 (psi) (17.5 ± 1.8 kPa) at the burner inlet. The
manufacturer's recommended delivery rate for the valve system
shall be included in the required pressure.
(iv) A synthetic gas mixture shall be of the following composition
within the following limits (analyzed at standard conditions):
55 ± 3 percent hydrogen, 24 ± 1 percent methane, 3 ± 1 percent
ethane, and 18 ± 1 percent carbon monoxide which will give a
specific gravity of 0.365 ± 0.018 (air = 1) and a B.T.U. content
of 540 ± 20 per cubic foot (20.1 ± 3.7 kJL) (dry basis) at 69.8
F (21 C).
(v) There shall be metal hooks and weights to produce a series
of total loads to determine length of char. The metal hooks
shall consist of No. 19 gage steel wire or equivalent and shall
be made from three inch (7.6 cm) lengths of wire and bent one-half
inch (1.3 cm) from one end to a 45-degree hook. One end of the
hook shall be fastened around the neck of the weight to be used.
(vi) There shall be a stop watch or other device to measure
the burning time 0.2 second.
(vii) There shall be a scale, graduated in 0.1 inch (.3 cm)
to measure the length of char.
(d) Procedure.
(i) The material undergoing test shall be evaluated for the
characteristics of after-flame time and char length on each
specimen.
(ii) All specimens to be tested shall be at moisture equilibrium
under standard atmospheric conditions in accordance with subsection
(3)(c) of this appendix. Each specimen to be tested shall be
exposed to the test flame within twenty seconds after removal
from the standard atmosphere. In case of dispute, all testing
will be conducted under standard atmospheric conditions in accordance
with subsection (3)(c) of this appendix.
(iii) The specimen in its holder shall be suspended vertically
in the cabinet in such a manner that the entire length of the
specimen is exposed and the lower end is three-quarters inch
(1.9 cm) above the top of the gas burner. The apparatus shall
be set up in a draft-free area.
(iv) Prior to inserting the specimen, the pilot flame shall
be adjusted to approximately one-eighth inch (.3 cm) in height
measured from its lowest point to the tip.
The burner flame shall be adjusted by means of the needle valve
in the base of the burner to give a flame height of one and
one-half inches (3.8 cm) with the stopcock fully open and the
air supply to burner shut off and taped. The one and one-half
inch (3.8 cm) flame height is obtained by adjusting the valve
so that the uppermost portion (tip) of the flame is level with
the tip of the metal prong (see Fig. L-2) specified for adjustment
of flame height. It is an important aspect of the evaluation
that the flame height to be adjusted with the tip of the flame
level with the tip of the metal prong. After inserting the specimen,
the stopcock shall be fully opened, and the burner flame applied
vertically at the middle of the lower edge of the specimen for
twelve seconds and the burner turned off. The cabinet door shall
remain shut during testing.
(v) The after-flame shall be the time the specimen continues
to flame after the burner flame is shut off.
(vi) After each specimen is removed, the test cabinet shall be
cleared of fumes and smoke prior to testing the next specimen.
(vii) After both flaming and glowing have ceased, the char length
shall be measured. The char length shall be the distance from
the end of the specimen, which was exposed to the flame, to the
end of a tear (made lengthwise) of the specimen through the center
of the charred area as follows: The specimen shall be folded lengthwise
and creased by hand along a line through the highest peak of the
charred area. The hook shall be inserted in the specimen (or a
hole, one-quarter inch (.6 cm) diameter or less, punched out for
the hook) at one side of the charred area one-quarter inch (.6
cm) from the adjacent outside edge and one-quarter inch (.6 cm)
in from the lower end. A weight of sufficient size such that the
weight and hook together shall equal the total tearing load required
in Table L-2 of this section shall be attached to the hook.
(viii) A tearing force shall be applied gently to the specimen
by grasping the corner of the cloth at the opposite edge of the
char from the load and raising the specimen and weight clear of
the supporting surface. The end of the tear shall be marked off
on the edge and the char length measurement made along the undamaged
edge.
Loads for determining char length applicable to the weight of
the test cloth shall be as shown in Table L-2.
TABLE L-2
| Specified
weight per square yard of cloth before any fire retardant
treatment or coating - ounces |
Total
learning weight for determining the charred length - pound |
| 2.0 to
6.0 |
0.25 |
| Over 6.0
to 15.0 |
0.50 |
| Over 15.0
to 23.0 |
0.75 |
| Over 23.0 |
1.0 |
To change into S.I. (System International) units, 1 ounce = 28.35
grams, 1 pound = 453 grams, 1 yard = .91 metre.
(ix) The after-flame time of the specimen shall be recorded
to the nearest 0.2 second and the char length to the nearest
0.1 inch (.3 cm).
(e) Report.
(i) The after-flame time and char length of the sample unit
shall be the average of the results obtained from the individual
specimens tested. All values obtained from the individual specimens
shall be recorded.
(ii) The after-flame time shall be reported in the nearest
0.2 second and the char length to the nearest 0.1 inch (.3 cm).
(f) Source. These test requirements are contained in "Federal
Test Method Standard 191, Method 5903 (1971)," and are reproduced
for your convenience.

Figure L-1 - Vertical flame resistance textile apparatus. All given
dimensions are in inches. System International (S.I.) unit: 1 inch
= 2.54 cm.

Figure L-2 - Vertical flame resistance textile apparatus, door
and top view w/baffle. All given dimensions are in inches. System
International (S.I.) unit: 1 inch = 2.54 cm.

Figure L-3 - Vertical flame resistance textile apparatus, views
and details. All given dimensions are in inches. System International
(S.I.) unit: 1 inch = 2.54 cm.

Figure L-4 - Vertical flame resistance textile apparatus (side
view showing gas hose connection.) All given dimensions are in inches.
System International (S.I.) unit: 1 inch = 2.54 cm.
[Statutory Authority: Chapter 49.17
RCW. 92-23-017 (Order 92-13), § 296-24-63599, filed 11/02/92, effective
12/18/92; 87-24-051 (Order 87-24), §296-24-63599, filed 11/30/87.
Statutory Authority: RCW.49.17.040 and 49.17.052. 82-02-003 (Order
81-32), § 296-24-63599, filed 12/24/81.]
|